Adjustment and alignment (voltage/current)
5 Adjustment and alignment (voltage/current)
The absolute encoder is aligned by setting the corresponding Lim inputs
(Uin > 8.4 V; Uin ≤ UB) of the working area.
I
out
1. Wire-Actuated encoder drive to the smallest position.
2. Activate LIM1 input (> 6 sec.).
3. Wire-Actuated Encoder drive to the largest position.
4. Activate LIM2 input (> 6 sec.).
The analog output has been aligned to the new measuring range. The set-
tings can be made using the ProTool SGH (for each signal).
OGW
10 V
Fig. 5: signal sequence voltage output (e.g. 0-10 V)
OGW
20 mA
4 mA
UGW
Fig. 6: signal sequence current output (e.g. 4-20 mA)
SGH25 · Date 29.01.2019 · Art. No. 89670 · Mod. status 019/19