If connecting leads and electric animal fence wires are installed near an overhead power line, the clearances
shall not be less than those shown in the table below.
Minimum clearances from power lines for electric animal fences
Less than or equal to 1 000
Greater than 1 000 and less than or equal to 33 000
Greater than 33 000
•
If connecting leads and electric animal fence wires are installed near an overhead power line, their height above
the ground shall not exceed 3 m
This height applies either side of the orthogonal projection of the outermost conductors of the power line on
the ground surface, for a distance of
·
2 m for power lines operating at a nominal voltage not exceeding 1 000 V;
·
15 m for power lines operating at a nominal voltage exceeding 1 000 V.
•
Electric animal fences intended for deterring birds, household pet containment or training animals such as cows
need only be supplied from low output energizers to obtain satisfactory and safe performance.
•
In electric animal fences intended for deterring birds from roosting on buildings, no electric fence wire shall be
connected to the energizer earth electrode. A warning sign shall be fi tted to every point where persons may
gain ready access to the conductors.
•
Fence wiring should be installed well away from any telephone or telegraph line or radio aerial.
•
Ensure that all mains operated, ancillary equipment connected to the electric animal fence circuit provides a
degree of isolation between the fence circuit and the supply mains equivalent to that provided by the energizer.
WARNING: Risk of Electric Shock. Do not connect the energizer simultaneously to a fence and to any other device
such as a cattle trainer or a poultry trainer. Otherwise, lightning striking your fence will be conducted to all other
devices.
This energizer complies with international safety regulations and is manufactured to international standards.
Gallagher reserves the right to make changes without notice to any product specifi cation to improve reliability,
function or design. E & OE.
Save these instructions
SERVICE OF DOUBLE-INSULATED APPLIANCES
In a double-insulated controller, two systems of insulation are provided instead of grounding. No equipment
grounding means is provided in the supply cord of a double-insulated controller, nor should a means for
equipment grounding be added to the controller. Servicing a double-insulated controller requires extreme care
and knowledge of the system, and should be done only by qualifi ed service personnel. Replacement parts of a
double insulated controller must be identical to the parts they replace.
4
Power line voltage
V
Clearance
m
3
4
8