Fusing data
Fusing data
Inverter
Cable installation in compli-
ance with
without mains choke
Circuit breaker
Characteristics
Max. rated current
Fuse
Characteristics
Max. rated current
with mains choke
Circuit breaker
Characteristics
Max. rated current
Fuse
Characteristics
Max. rated current
Earth-leakage circuit breaker
3-phase mains connection
Fusing data
Inverter
Cable installation in compli-
ance with
without mains choke
Circuit breaker
Characteristics
Max. rated current
Fuse
Characteristics
Max. rated current
with mains choke
Circuit breaker
Characteristics
Max. rated current
Fuse
Characteristics
Max. rated current
Earth-leakage circuit breaker
3-phase mains connection
I51AE125D
I51AE137D
A
10
A
10
A
10
A
10
I51AE222D
A
25
A
25
A
25
A
25
≥ 30 mA, type B
3-phase mains connection 230/240 V
I51AE155D
I51AE175D
EN 60204-1
B
10
16
gG/gL or gRL
10
16
B
10
16
gG/gL or gRL
10
16
≥ 30 mA, type B
I51AE240C
EN 60204-1
B
32
gG/gL or gRL
32
B
32
gG/gL or gRL
32
Electrical installation
Mains connection
I51AE211D
I51AE215D
16
25
16
25
16
25
16
25
I51AE255C
32
32
32
32
≥ 300 mA, type B
25
25
25
25
107