Herunterladen Inhalt Inhalt Diese Seite drucken

Installation Conditions - Graf CARAT XXL Einbau-/ Montage-/ Und Wartungsanleitung

Löschwasserbehälter
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

mail@graf.info
www.graf.info
2.

Installation conditions

Teleskop-Domschacht LKW
(Abdeckung nach DIN 3223 -
bauseits zu stellen)
750 - 1050
Covering heights with telescopic lorry dome
shaft (cover in accordance with DIN 3223 - to be
provided by the customer) in landscaped areas
suitable for pedestrian loading 750-1050 mm.
max. 1500
Maximum covering height with extension sleeve
and telescopic lorry dome shaft (cover in ac-
cordance with DIN 3223 - to be provided by the
customer).
Maximum covering height 1500 mm.
> 800 < 1500
Covering heights with telescopic lorry dome
shaft (cover in accordance with DIN 3223 – to
be provided by the customer) in area driven over
by vehicles >800<1500 mm.
max. 40 to
max. 8 to
Covering heights with telescopic lorry dome
shaft (cover in accordance with DIN 3223 – to
> 1000 < 1500
be provided by the customer) in area driven over
by lorries >1000<1500 mm.
(Load up to max. 40 t)
The tanks may only be installed in ground water
with some limitations. If you can expect the
> 800 < 1500
ground water to be higher than shown in this
figure, even if only occasionally, it should be
Max.
Max.
discharged through drainage.
Covering heights with ground water >800<1500
mm.
17 / 56