Operation

ELECTRIC SHOCK CAUSED BY LIVE PARTS
Severe burns or death caused by mains voltage (AC 230 V, 50 Hz) in the control
unit.
Verify that adjustment work is only performed by trained electricians.
Failure to follow these instructions will result in death or serious injury.
8.1
Making adjustments
The settings are made via the controls in the control unit when mains voltage
is applied.
The controls are located at the right side of the PCB.
1. After applying mains voltage, allow for a heat-up time of at least five min-
utes before performing adjustment work.
8.2
Operating mode
The product is equipped with an output relay that switches when the probe
comes into contact or loses contact with the stored medium. The relay is
used to control additional equipment such as pumps, valves, visual and audi-
ble alarm units, telecommunication devices, building control systems, etc.
Two operating modes can be selected for the switching function (fail-safe
principle). The settings are made via a switch on the PCB of the control unit.
The relay state is indicated by means of two indicator lamps in the control
unit:
Green lamp "Normal" is on: Relay is energised.
Red lamp "Alarm" is on: Relay is de-energised.
Operation
DANGER
CapFox® ENT 7
EN
22