Mounting and installation instructions,
Self-production of
The following guidance values are applicable to swimming pools with self-production of
chlorine
chlorine:
Salt (NaCl)
Total dissolved solids
pH
Total alkalinity
Calcium hardness
Sulphates
Langelier Saturation
It is advisable to use the Langelier Saturation index to ensure that the combination of
index
the different water parameters is acceptable.
Contact Dantherm Air Handling A/S if necessary.
continued
Chemicals
ppm
2700-3400
< 5500
7,2-7,6
80-150
250-450
< 360
28