Herunterladen Inhalt Inhalt Diese Seite drucken

Specifications - Emerson FloBoss 107 Anleitung

Durchfluss-computer
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 9
Safe Use Instructions – Emerson FloBoss 107 Flow Manager
Part D301594X012
February 2018
Do not open covers unless area is known to be non-
hazardous.

Specifications

POWER
External Power Charging Input: 8–30 V dc, reverse
polarity protection.
Input: 8–30 V dc, 3A max, 33 watts max.
ENVIRONMENTAL
Operating Ambient Temperature: –40 to 75C.
Storage Temperature: –50 to 85C.
Operating Humidity: 5 to 95%, non-condensing.
WEIGHT
0.76 kg (4-slot main unit and one CPU module).
APPROVALS
ATEX/IECEx
Evaluated per the following standards:
EN 60079-0 (2012/A11:2013)
EN 60079-15 (2010)
IEC 60079-0 (2011 Ed 6)
IEC 60079-15 (2010 Ed 4)
Certified by Sira as Model W40190.
ATEX Cert Sira 10ATEX4059X
IECEx Cert IECEx SIR 10.0028X
Product Markings for Hazardous Locations:
Ex nA IIC T4 Gc, –40°C  T
II 3 G.
The following tools are required for installation,
maintenance, and troubleshooting:
Personal computer running Microsoft
Windows 8.1, or Windows 10 and Emerson Field Tools
configuration software (providing ROCLINK™ 800
configuration software).
Phillips (cross-head) screwdriver.
Flat-head screwdriver.
1. You receive the FB107 in a box. Remove it from the
box.
2. The FB107 is provided in one of four main
configurations, depending on what was ordered.
Install the FB107 in a suitable ATEX- or IECEx-approved
IP54 or better enclosure, using the following
guidelines:
Main unit only. Position as desired on the enclosure
mounting plate and locate mounting holes on the
plate using the FB107 as a template. See
for FB107 dimensions. Drill and tap mounting
holes in the plate with an 8-32 UNC thread tap.
Position the FB107 over the tapped locations and
2
 +75°C
amb
Windows
®
Figure 2
attach to the plate with the four 8-32 UNC x 1.00
inch-long screws provided. Torque the screws to
approximately 1.1 to 1.4 N-m.
Note: If metric screws are substituted, use truss-
134.4
[
5.29 ]
Main unit mounted on adaptor panel. Position as
desired on the enclosure mounting plate and
locate mounting holes on the plate using the
adaptor panel slots as a template. See Figure 3 for
adaptor panel dimensions. Drill and tap mounting
holes in the plate with a 8-32 UNC thread tap.
Position the FB107 with adaptor panel over the
tapped locations and attach to the plate with the
four 8-32 UNC x .38 inch-long screws provided.
Tighten the screws securely.
7,
®
Main unit and expansion rack. Position the main
unit on the enclosure mounting plate and locate
mounting holes on the plate using the FB107 as a
template. See
with expansion rack. Drill and tap mounting holes
in the plate with an 8-32 UNC thread tap. Position
the main unit over the tapped locations and attach
to the plate with the four 8-32 UNC x 1.00 inch-
long screws provided. Do not fully tighten. Plug the
expansion rack into the main unit and while
head style screws to keep from fracturing
the plastic housing during tightening.
158.0
[
]
6.22
15.5
[
]
0.61
Figure 2. FB107 Dimensions
195.1
[ 7.68
]
165.1
[
]
6.50
127.0
[
]
5.00
Figure 3. Panel Dimensions
Figure 4
for dimensions of main unit
www.Emerson.com/RemoteAutomation
127.0
[ 0.19
]
4X Ø4.8
[ 5.00
]

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis