5. Commissioning, operation
Writing new parameters
Take note of the new communication parameters before writing them, as the parameters
will be required again for any new access to the transmitter.
Write the new values in the right fields (below the button "Write on instrument").
Designation
Tag number (name of instrument)
Address
Baud rate
Parity
Termination
Gas mixture SF
[%]
6
Gas mixture partner
By pressing the button "Write on instrument" the data in the fields is transmitted to the
instrument register. To finish the writing operation, interrupt the voltage supply of the
transmitter after the transmission before restoring it.
Afterwards, during the reading operation, the entered data becomes visible on the left-
hand side.
If Windows® is used with non-Latin character sets (i.e. Chinese), the area
settings of the system control must be changed to English (USA), since
otherwise, communication problems might occur.
WIKA operating instructions gas density monitor, model GDM-100-TI-D
Valid values
16 characters in ASCII code
1 ... 247
1,200 ... 115,200
None, Even
Off, On
0 ... 100
N
, CF
2
4
EN
19