  • Seite 1 Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment SERVICE CENTER REPAIRS WE BUY USED EQUIPMENT • FAST SHIPPING AND DELIVERY Experienced engineers and technicians on staff Sell your excess, underutilized, and idle used equipment at our full-service, in-house repair center We also offer credit for buy-backs and trade-ins •...
  • Seite 2: Mounting Instructions

    EDK82EV113 .1p} Montageanleitung Mounting Instructions Instructions de montage 8200vec062 Global Drive 8200 vector 3 kW ... 11 kW Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Seite 3 Lire attentivement les instructions de montage avant toute opération ! Respecter les consignes de sécurité. Le manuel comprenant une description complète du convertisseur de fréquence 8200 vector peut être commandé auprès de votre agence Lenze. ã 2007 Lenze Drive Systems GmbH 8.1 05/2007 TD29...
  • Seite 4 X3.1 X1.2 X1.1  ‚ ƒ X2.1 X2.2 8200vec315 Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Seite 5: Lieferumfang

    Lieferumfang Position Beschreibung Frequenzumrichter 8200 vector Montageanleitung und Start−Hilfe ^ 18 Halterung für Standardbefestigung ^ 20 EMV−Schirmblech mit Schirmklammern für die Motorleitung und für die Zuleitung Motortemperatur− Überwachung ^ 20 Klemmleiste 2−polig für Motor−PE und Motor−Schirm an X2.1 ^ 20 EMV−Schirmblech mit Befestigungsschrauben und Schirmschelle für geschirmte Steuerleitungen ^ 32 Stiftleiste 2*13−polig für Funktionsmodule an Schnittstelle FIF...
  • Seite 6 Diese Dokumentation ist gültig für Antriebsregler 8200 vector für den Gerätestand  ‚ ƒ E82xV 55 Aerzen Hans-Lenze-Str. 1 ‚ ƒ D-31855 Aerzen ‚ ƒ Inverter 8200 vector Version: Id.-No: Version: Prod.-No: Ser.-No: E = Einbaugerät Ser.-No: Input: 1D74 D = Einbaugerät in Durchstoßtechnik Output: C = Einbaugerät in Cold Plate−Technik...
  • Seite 7 Hinweis! Aktuelle Dokumentationen und Software−Updates zu Lenze Produkten finden Sie im Internet jeweils im Bereich "Downloads" unter http://www.Lenze.com Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Seite 8: Inhaltsverzeichnis

    Inhalt Sicherheitshinweise ..........Technische Daten .
  • Seite 9: Sicherheitshinweise

    Sicherheitshinweise Allgemeine Sicherheits− und Anwendungshinweise für Lenze−Antriebsregler (gemäß Niederspannungsrichtlinie 73/23/EWG) Allgemein Lenze−Antriebsregler (Frequenzumrichter, Servo−Umrichter, Stromrichter) können wäh- rend des Betriebs − ihrer Schutzart entsprechend − spannungsführende, auch bewegliche oder rotierende Teile haben. Oberflächen können heiß sein. Bei unzulässigem Entfernen der erforderlichen Abdeckung, bei unsachgemäßem Einsatz, bei falscher Installation oder Bedienung besteht die Gefahr von schweren Personen−...
  • Seite 10 Sicherheitshinweise Bestimmungsgemäße Verwendung Antriebsregler sind Komponenten, die zum Einbau in elektrische Anlagen oder Maschinen bestimmt sind. Sie sind keine Haushaltsgeräte, sondern als Komponenten ausschließlich für die Verwendung zur gewerblichen Nutzung bzw. professionellen Nutzung im Sinne der EN 61000−3−2 bestimmt. Die Dokumentation enthält Hinweise zur Einhaltung der Grenz- werte nach EN 61000−3−2.
  • Seite 11 Sicherheitshinweise Elektrischer Anschluß Beachten Sie bei Arbeiten an unter Spannung stehenden Antriebsreglern die geltenden na- tionalen Unfallverhütungsvorschriften (z. B. VBG 4). Führen Sie die elektrische Installation nach den einschlägigen Vorschriften durch (z. B. Lei- tungsquerschnitte, Absicherungen, Schutzleiteranbindung). Zusätzliche Hinweise enthält die Dokumentation.
  • Seite 12 Sicherheitshinweise Personenschutz Überprüfen Sie vor Arbeiten am Antriebsregler, ob alle Leistungsklemmen, der Relaisausgang und die Pins der Schnittstelle FIF spannungslos sind, da – nach dem Netzabschalten die Leistungsklemmen U, V, W, +UG, −UG, BR1 und BR2 noch mindestens 3 Minuten gefährliche Spannung führen. –...
  • Seite 13 Sicherheitshinweise Schutz der Maschine/Anlage Antriebe können gefährliche Überdrehzahlen erreichen (z. B. Einstellung hoher Ausgangsfrequenzen bei dafür ungeeigneten Motoren und Maschinen): – Die Antriebsregler bieten keinen Schutz gegen solche Betriebsbedingungen. Setzen Sie dafür zusätzliche Komponenten ein. Schütze in der Motorleitung nur bei gesperrtem Regler schalten. Werden Schütze in der Motorleitung bei freigegebenem Regler geschaltet, –...
  • Seite 14: Hinweistext (Beschreibt Die Gefahr Und Gibt Hinweise, Wie Sie Vermieden Werden Kann)

    Sicherheitshinweise Gestaltung der Sicherheitshinweise Alle Sicherheitshinweise in dieser Anleitung sind einheitlich aufgebaut: Piktogramm (kennzeichnet die Art der Gefahr) Gefahr! (kennzeichnet die Schwere der Gefahr) Hinweistext (beschreibt die Gefahr und gibt Hinweise, wie sie vermieden werden kann) Piktogramm Signalwort Bedeutung Folgen bei Mißachtung Gefahr! Unmittelbar drohende Gefahr für Perso- Tod oder schwerste Verletzungen...
  • Seite 15: Technische Daten

    Technische Daten Normen und Einsatzbedingungen Normen Konformität Niederspannungsrichtlinie (73/23/EWG) Approbationen UL 508C Power Conversion Equipment (File−No. E132659) Umweltbedingungen Klimatische Bedingungen Lagerung IEC/EN 60721−3−1 1K3 (−25 ... +60 °C) < 6 Monate 1K3 (−25 ... +40 °C) > 6 Monate > 2 Jahre: Zwischenkreis−Kondensato- ren formieren Transport IEC/EN 60721−3−2...
  • Seite 16: Allgemeine Elektrische Daten

    Technische Daten Allgemeine elektrische Daten Einhaltung der Anforderungen nach EN 61800−3/A11 Störaussendung Einhaltung der Grenzwertklassen A und B nach EN 55011 E82EVxxxKxC0xx ohne zusätzliche Maßnahmen E82EVxxxKxC2xx mit externen Filtermaßnahmen Störfestigkeit Anforderungen nach EN 61800−3 incl. A11 Anforderungen Norm Schärfegrade EN 61000−4−2 3, d.
  • Seite 17: Betrieb Mit Bemessungsleistung (Normalbetrieb)

    Technische Daten Betrieb mit Bemessungsleistung (Normalbetrieb) Netz−Bemessungsspannung Leistung Netzstrom [A] Ausgangsstrom [A] Masse  ‚ [kW] (60 s) [kg] E82EV302K2C 15,6 12,0 12,0 18,0 3/PE AC 230/240 V E82EV402K2C 21,3 16,0 16,5 24,8 50 Hz E82EV552K2C 29,3 21,0 22,5 33,8 DC 325 V E82EV752K2C −...
  • Seite 18 Technische Daten Betrieb mit erhöhter Bemessungsleistung Der Antriebsregler kann unter den hier beschriebenen Einsatzbedingungen im Dauerbe- trieb mit einem leistungsstärkeren Motor betrieben werden. Die Überlastfähigkeit ist auf 120 % reduziert. Typische Anwendungen sind Pumpen mit quadratischer Lastkennlinie oder Lüfter. Hinweis! Der Betrieb mit erhöhter Bemessungsleistung ist nur erlaubt mit den genannten Antriebsreglern im genannten Netzspannungsbereich...
  • Seite 19: Mechanische Installation

    Mechanische Installation Abmessungen bei Standard−Befestigung 8200 vector 3 ... 11 kW −2−8200vec060 Unterschiedliche Baugrößen nur nach rechts kleiner werdend anreihen! Maße in mm E82EV302K2C E82EV402K2C E82EV552K2C 62,5 280 ... 295 E82EV752K2C E82EV302K4C E82EV402K4C E82EV552K4C E82EV752K4C 62,5 E82EV113K4C 280 ... 295 Seitliche Montage nur möglich mit schwenkbarer Halterung E82ZJ006 (Zubehör) mit E82ZJ006 EDK82EV113 DE/EN/FR 8.1...
  • Seite 20: Elektrische Installation

    Elektrische Installation Klemmleisten verdrahten Die mitgelieferten Klemmleisten sind geprüft nach den Spezifikationen der DIN VDE 0627:1986−06 (in Teilen) DIN EN 60999:1994−04 (in Teilen) Geprüft wurden u. a. mechanische, elektrische und thermische Beanspruchung, Vibration, Leiterbeschädigung, Leiterlockerung, Korrosion und Alterung. Stop! Um Klemmleisten und Kontakte des Antriebsreglers nicht zu beschädigen: Nur bei vom Netz getrenntem Antriebsregler aufstecken oder abziehen! Klemmleisten erst verdrahten, dann aufstecken! Unbenutzte Klemmleisten ebenfalls aufstecken, um die Kontakte zu...
  • Seite 21: Emv−Gerechte Installation (Ce−Typisches Antriebssystem)

    Elektrische Installation EMV−gerechte Installation (CE−typisches Antriebssystem) L < 40 mm L < 500 mm −3−8200vec066 EDK82EV113 DE/EN/FR 8.1 Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Seite 22 Elektrische Installation EMV−gerechte Installation (CE−typisches Antriebssystem) Stop! Steuerleitungen und Netzleitungen räumlich getrennt von der Motorleitung verlegen, um Störeinkopplungen zu vermeiden. Steuerleitungen immer geschirmt ausführen. Generell empfehlen wir, die Zuleitung zum PTC oder Thermokontakt abgeschirmt und räumlich getrennt von der Motorleitung zu verlegen. Wenn Sie die Adern für den Motoranschluß...
  • Seite 23: Netzanschluß 230 V/240 V

    Elektrische Installation Netzanschluß 230 V/240 V Stop! Antriebsregler Typ E82EVxxxK2C nur an Netzspannung 3/PE AC 100 ... 264 V anschließen. Höhere Netzspannung zerstört den Antriebsregler! Der Ableitstrom gegen Erde (PE) ist > 3.5 mA. Nach EN 50178 ist eine Festinstallation erforderlich. Der PE muß doppelt ausgeführt sein. X1.1 3 PE AC 230/240 V 45Hz -0%...65Hz +0% 100 V -0%...264 V +0%...
  • Seite 24 Elektrische Installation Netzanschluß 230 V/240 V Sicherungen und Leitungsquerschnitte (Betrieb mit Bemessungsleistung) Betrieb ohne Netzdrossel Installation nach EN 60204−1 Installation nach UL  ‚  8200 vector Netz L1, L2, L3, L1, L2, L3, [kW] [AWG] E82EV302K2C M20 A B20 A 20 A 3/PE AC ³...
  • Seite 25 Elektrische Installation Netzanschluß 230 V/240 V Sicherungen und Leitungsquerschnitte (Betrieb mit erhöhter Bemessungsleistung) Betrieb ohne Netzdrossel Installation nach EN 60204−1 Installation nach UL  ‚  8200 vector Netz L1, L2, L3, L1, L2, L3, [kW] [AWG] E82EV302K2C 3/PE AC M25 A B25 A 25 A...
  • Seite 26: Netzanschluß 400 V/500 V

    Elektrische Installation Netzanschluß 400 V/500 V Stop! Antriebsregler Typ E82EVxxxK4C nur an Netzspannung 3/PE AC 320 ... 550 V anschließen. Höhere Netzspannung zerstört den Antriebsregler! Der Ableitstrom gegen Erde (PE) ist > 3.5 mA. Nach EN 50178 ist eine Festinstallation erforderlich. Der PE muß doppelt ausgeführt sein. X1.1 3 PE AC 400 V 45 Hz -0 %...65 Hz +0 % 320 V -0 %...550 V +0 %...
  • Seite 27 Elektrische Installation Netzanschluß 400 V/500 V Sicherungen und Leitungsquerschnitte (Betrieb mit Bemessungsleistung) Betrieb ohne Netzdrossel Installation nach EN 60204−1 Installation nach UL  ‚  8200 vector Netz L1, L2, L3, L1, L2, L3, [kW] [AWG] E82EV302K4C M16 A B16 A 15 A E82EV402K4C M16 A...
  • Seite 28: Sicherungen Und Leitungsquerschnitte (Betrieb Mit Erhöhter Bemessungsleistung)

    Elektrische Installation Netzanschluß 400 V/500 V Sicherungen und Leitungsquerschnitte (Betrieb mit erhöhter Bemessungsleistung) Betrieb ohne Netzdrossel Installation nach EN 60204−1 Installation nach UL  ‚  8200 vector Netz L1, L2, L3, L1, L2, L3, [kW] [AWG] E82EV302K4C M16 A B16 A 15 A 3/PE AC...
  • Seite 29: Anschluß Motor / Bremswiderstand

    Elektrische Installation Anschluß Motor / Bremswiderstand 0,7...0,8 Nm 6.2...7.1 lb-in 6 mm / 0.24 in 8200 vector X2.1 X2.2 T1 T2 X2.1 ϑ> X2.2 −6−8200vec064 £ 75 pF/m; ab 2,5 mm £ 100 pF/m; Ader/Schirm £ 150 pF/m) Kapazitätsarme Motorleitungen verwenden! (Ader/Ader bis 1,5 mm Möglichst kurze Motorleitungen wirken sich positiv auf das Antriebsverhalten aus! HF−Schirmabschluß...
  • Seite 30: Anschluß Relaisausgang

    Elektrische Installation Anschluß Relaisausgang −7−8200vec061 Funktion Relaisstellung ge- Meldung Technische Daten schaltet (Lenze−Einstellung) X1.2/K11 Relaisausgang Öffner geöffnet TRIP AC 250 V/3 A X1.2/K12 Relais−Mittelkontakt DC 24 V/2 A ... DC 240 V/0.16 A X1.2/K14 Relaisausgang Schließer geschlossen TRIP HF−Schirmabschluß durch PE−Anbindung über Schirmschelle Hinweis! Für das Schalten von Steuersignalen geschirmte Leitungen verwenden und...
  • Seite 31: Anschluß Relaisausgang Ksr Für "Sicherer Halt

    Elektrische Installation Anschluß Relaisausgang K für "Sicherer Halt" (nur aktiv bei Variante E82EVxxxK4Cx4x)−8− Die Variante x4x der Antriebsregler unterstützt die Sicherheitsfunktion "Sicherer Halt", Schutz gegen unerwarteten Anlauf, nach den Anforderungen der EN 954−1 Steuerungs- kategorie 3" und EN 1037. Dafür sind die Antriebsregler mit einem integrierten Sicherheitsrelais mit Rückmeldekon- takt ausgestattet.
  • Seite 32: Anschluß Relaisausgang K

    Elektrische Installation Anschluß Relaisausgang K für "Sicherer Halt" +24V X3.1 X3.1 34 33 K32 K31 + 5 V 8200 vector IGBT 8200vec266 Klemmenbelegung Daten Bezugspotential für den Eingang Si- Sicherheitsrelais Spulenspannung bei +40°C DC +24 V (+19.5 ... 36 V) cherheitsabschaltung Spulenstrom bei 24 V DC 30 mA...
  • Seite 33: Funktionsmodul (Option)

    Funktionsmodul (Option) Montage Wichtige Hinweise Die Antriebsregler haben in der Grundausführung keine Steuerklemmen. Es stehen ver- schiedene I/O−Funktionsmodule für die Schnittstelle FIF zur Verfügung, um die Antriebs- regler mit Steuerklemmen auszustatten. Demontieren Sie ein Funktionsmodul nur, wenn es unbedingt notwendig ist (z. B. beim Aus- tausch des Antriebsreglers).
  • Seite 34 Funktionsmodul (Option) Montage Montage von Funktionsmodulen in Ausführung "PT"  ‚ −10−8200vec372 Bringen Sie zusätzlich den Sicherungsbügel an, damit das Modul nicht zusammen mit den Klemmleisten abgezogen werden kann: 1. Sicherungsbügel 4 in die Aussparungen einsetzen. 2. Sicherungsbügel über das Funktionsmodul klappen und einrasten. EDK82EV113 DE/EN/FR 8.1 Artisan Technology Group - Quality Instrumentation ...
  • Seite 35: Demontage

    Funktionsmodul (Option) Demontage Demontage der Funktionsmodule  ‚ 3 min 8200vec072 1. Antriebsregler vom Netz trennen und mindestens 3 Minuten warten! 2. Mit einer Zange den Steg der Stiftleiste fassen und ziehen 0. Stiftleiste und Funktionsmodul werden gemeinsam demontiert. EDK82EV113 DE/EN/FR 8.1 Artisan Technology Group - Quality Instrumentation ...
  • Seite 36 Funktionsmodul (Option) Demontage Demontage der Funktionsmodule Ausführung "PT"  ‚ ƒ 8200vec372 Bei Funktionsmodulen Ausführung "PT" muss nach dem Abschalten zunächst der Siche- rungsbügel entfernt werden. 1. Schraubendreher zwischen Sicherungsbügel und Funktionsmodul ansetzen 0. Durch Drücken nach rechts den Sicherungsbügel ausrasten. 2.
  • Seite 37: Kommunikationsmodul (Option)

    Kommunikationsmodul (Option) Montage/Demontage  ‚ −11−8200vec073 Jumper zur Auswahl der Spannungsversorgung  Spannungsversorgung extern (Lieferzustand) ‚ Spannungsversorgung über interne Spannungsquelle Kommunikationsmodul auf die Schnittstelle AIF aufstecken bzw. davon abziehen. Das ist auch während des Betriebs mög- lich. Mögliche Kombinationen Kommunikationsmodul auf AIF Keypad LECOM LECOM−B...
  • Seite 38: Inbetriebnahme

    Inbetriebnahme Vor dem ersten Einschalten Hinweis! Halten Sie die jeweilige Einschaltreihenfolge ein. Bei Störungen während der Inbetriebnahme hilft Ihnen das Kapitel "Störungen erkennen und beseitigen". Um Personenschäden oder Sachschäden zu vermeiden, überprüfen Sie ..vor dem Zuschalten der Netzspannung: Die Verdrahtung auf Vollständigkeit, Kurzschluß...
  • Seite 39: Wahl Der Richtigen Betriebsart

    Inbetriebnahme Wahl der richtigen Betriebsart Für Standardanwendungen hilft Ihnen die folgende Tabelle, die richtige Betriebsart zu wäh- len. Sie können wählen zwischen U/f−Kennliniensteuerung, Vector−Regelung und sensor- loser Drehmoment−Regelung: Die U/f−Kennliniensteuerung ist die klassische Betriebsart für Standardanwendungen. Mit der Vector−Regelung erzielen Sie gegenüber der U/f−Kennliniensteuerung verbesserte Antriebseigenschaften durch: höheres Drehmoment über den gesamten Drehzahlbereich höhere Drehzahlgenauigkeit und höhere Rundlaufgüte...
  • Seite 40 Inbetriebnahme Wahl der richtigen Betriebsart Anwendung Betriebsart Einstellung in C0014 Einzelantriebe empfohlen alternativ mit stark wechselnden Lasten mit Schweranlauf mit Drehzahlregelung (Drehzahlrückführung) mit hoher Dynamik (z. B. Positionier− und Zustellantriebe) − mit Drehmoment−Sollwert − mit Drehmomentbegrenzung (Leistungsregelung) Drehstrom−Reluktanzmotoren − Drehstrom−Verschiebeankermotoren −...
  • Seite 41: Mit Dem Keypad E82Zbc − Parametrierung

    Inbetriebnahme Mit dem Keypad E82ZBC − Parametrierung Beschreibung Das Keypad ist als Zubehör erhältlich. Die vollständige Beschreibung des Keypad finden Sie in der Anleitung, die mit dem Keypad geliefert wird. Keypad aufstecken Sie können das Keypad auch während des Betriebs auf die Schnittstelle AIF stecken und wieder abnehmen.
  • Seite 42 Störung aktiv Bargraphanzeige In C0004 eingestellter Wert in % Anzeigebereich: − 180 % ... + 180 % (jeder Teil- strich = 20 %) (Lenze−Einstellung: Geräteauslastung C0056) Funktionsleiste 1 Funktion Bedeutung Erläuterung Nicht möglich bei aktivem Paßwortschutz (Display = Sollwertvorgabe über "loc"...
  • Seite 43 Sie in das Menü all wechseln. Aktion Tastenfolge Ergebnis Bemerkung Keypad aufstecken Die Funktion ist aktiv. Angezeigt wird der erste Code im User−Menü (C0517/1, Lenze−Einstellung: C0050 = Ausgangsfre- xx.xx quenz).  Ggf. in das Menü "ALL" Wechsel in Funktionsleiste 2 wechseln Menü...
  • Seite 44 Inbetriebnahme Mit dem Keypad E82ZBC − Parametrierung Menüstruktur Alle Parameter, mit denen Sie den Antriebsregler parametrieren oder überwachen können, sind in sogenannten Codes gespeichert. Die Codes sind numeriert und in der Dokumenta- tion mit einem "C" gekennzeichnet. In einigen Codes sind die Parameter in numerierten Subcodes"...
  • Seite 45 Hinweis! Über C0002 "Parametersatz−Transfer/Lieferzustand herstellen" können Sie mit dem Keypad Konfigurationen von Antriebsregler zu Antriebsregler übertragen oder wieder den Lieferzustand herstellen, indem Sie die Lenze−Einstellung laden (z. B. wenn Sie beim Parametrieren die Übersicht verloren haben). EDK82EV113 DE/EN/FR 8.1 Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Seite 46 Inbetriebnahme Mit dem Keypad E82ZBC − Parametrierung Œ Œ 0050 0050   s u e r AL L ~5 s … … Œ 0050 ‚ Œ Œ 0XXX 000X ‚ ‚ C000x C517/1 user Œ Œ 0XYZ 0XYZ C000x+1 ‚...
  • Seite 47: Mit Dem Keypad E82Zbc − Lineare U/F−Kennliniensteuerung

    (0 ... 5 V/0 ... 10 V/0 ... 20 mA) Passen Sie die Klemmenkonfiguration an die Œ 0007 ‚ Verdrahtung an (C0007) Lenze−Einstellung: −0−, d. h. E1: JOG1/3 Auswahl Festsollwerte E2: JOG2/3 E3: DCB Gleichstrombremse E4: CW/CCW Rechtslauf/Linkslauf Stellen Sie die minimale Ausgangsfrequenz ein...
  • Seite 48 Stellen Sie die U/f−Nennfrequenz ein (C0015) 100% Lenze−Einstellung: 50.00 Hz Stellen Sie die U −Anhebung ein (C0016) Die Lenze−Einstellung ist für alle gängigen Anwendungen geeignet Lenze−Einstellung: hängt ab vom Antriebsregler- C0015 Wenn Sie weitere Einstellungen vornehmen Z. B. Festfrequenzen (JOG) (C0037, C0038, C0039) oder Motortempera- wollen, müssen Sie in das Menü...
  • Seite 49: Mit Dem Keypad E82Zbc − Vector−Regelung

    Grundeinstellungen für Ihren Antrieb ausführen können Passen Sie die Klemmenkonfiguration an die Œ 0007 ‚ Verdrahtung an (C0007) Lenze−Einstellung: 0, d. h. E1: JOG1/3 Auswahl Festsollwerte E2: JOG2/3 E3: DCB Gleichstrombremse E4: CW/CCW Rechtslauf/Linkslauf Stellen Sie die minimale Ausgangsfrequenz ein (C0010) C0011 Lenze−Einstellung: 0.00 Hz...
  • Seite 50 Lenze−Einstellung: 0, dard−I/O) (0 ... 5 V/0 ... 10 V/0 ... 20 mA) Geben Sie die Motordaten ein Siehe Motor−Typenschild Motor−Bemessungsdrehzahl (C0087) Lenze−Einstellung: 1390 rpm Motor−Bemessungsstrom (C0088) Wert für die gewählte Motor−Schal- tungsart (Stern/Dreieck) eintragen! Lenze−Einstellung: geräteabhängig Motor−Bemessungsfrequenz (C0089) Lenze−Einstellung: 50 Hz Motor−Bemessungsspannung (C0090)
  • Seite 51: Vector−Regelung Optimieren

    Inbetriebnahme Mit dem Keypad E82ZBC − Vector−Regelung Einschaltreihenfolge Bemerkung Wenn Sie alle Parameter eingestellt haben: Sollwert vorgeben Z. B. über Potentiometer an Klem- men 7, 8, 9 Regler freigeben Klemme X3/28 = HIGH misc002 Der Antrieb läuft jetzt, z. B. mit 30 Hz Wenn der Antrieb nicht anläuft, zu- Œ...
  • Seite 52: Mit Dem Keypad Xt Emz9371Bc − Parametrierung

    Inbetriebnahme Mit dem Keypad XT EMZ9371BC − Parametrierung Beschreibung Das Keypad ist als Zubehör erhältlich. Die vollständige Beschreibung des Keypad finden Sie in der Anleitung, die mit dem Keypad geliefert wird. Keypad aufstecken Sie können das Keypad auch während des Betriebs auf die Schnittstelle AIF stecken und wieder abnehmen.
  • Seite 53 Inbetriebnahme Mit dem Keypad XT EMZ9371BC − Parametrierung Übernahme der Parameter Anzeige Bedeutung Erläuterung Parameter wird sofort übernommen Grundgerät arbeitet sofort mit dem neuen Para- meterwert Grundgerät arbeitet mit dem neuen Parameter- SHPRG Parameter muß bestätigt werden mit wert, nachdem bestätigt wurde SHPRG Parameter muß...
  • Seite 54: Funktionstasten

    Inbetriebnahme Mit dem Keypad XT EMZ9371BC − Parametrierung Funktionstasten Hinweis! Tastenkombinationen mit T: T drücken und halten, dann zweite Taste zusätzlich drücken. Taste Funktion−13− Menü−Ebene Code−Ebene Parameter−Ebene Betriebs−Ebene Wechseln in die Parameter− Wechseln in die Betriebs− Wechseln in die Code− Ebene Ebene Ebene...
  • Seite 55 Inbetriebnahme Mit dem Keypad XT EMZ9371BC − Parametrierung Parameter ändern und speichern Alle Parameter, mit denen Sie den Antriebsregler parametrieren oder überwachen können, sind in sogenannten Codes gespeichert. Die Codes sind numeriert und in der Dokumenta- tion mit einem "C" gekennzeichnet. In einigen Codes sind die Parameter in numerierten Subcodes"...
  • Seite 56 Inbetriebnahme Mit dem Keypad XT EMZ9371BC − Parametrierung Schritt Tastenfolge Aktion z y Z Y Menü auswählen Mit den Pfeiltasten das gewünschte Menü auswählen In die Code−Ebene wechseln Anzeige erster Code im Menü Code oder Subcode auswählen Anzeige des aktuellen Parameterwerts In die Parameter−Ebene wechseln Wenn SHPRG angezeigt wird, Regler sper- Der Antrieb trudelt aus...
  • Seite 57: Menüstruktur

    Inbetriebnahme Mit dem Keypad XT EMZ9371BC − Parametrierung Menüstruktur Hauptmenü Untermenüs Beschreibung Nr. Anzeige Anzeige USER−Menu In C0517 definierte Codes Code list Alle verfügbaren Codes Alle verfügbaren Codes aufsteigend sortiert (C0001 ... C7999) Para set 1 Codes im Parametersatz 1 (C0001 ... C1999) Para set 2 Codes im Parametersatz 2 (C2001 ...
  • Seite 58 Inbetriebnahme Mit dem Keypad XT EMZ9371BC − Parametrierung Hauptmenü Untermenüs Beschreibung Beschreibung Anzeige Anzeige Main FB Siehe Anleitung des Keypad Konfiguration Funktionsblöcke Controller Siehe Anleitung des Keypad Konfiguration interner Regelungsparameter Terminal I/O Siehe Anleitung des Keypad Verknüpfung der Eingänge und Ausgänge mit internen Signalen und Anzeige der Signalpegel an den Klemmen LECOM/AIF Siehe Anleitung des Keypad...
  • Seite 59: Mit Dem Keypad Xt Emz9371Bc − Lineare U/F−Kennliniensteuerung

    Code die Menü−Ebene wechseln benötigen. Die digitalen Eingänge Para Quick start sind in Lenze−Einstellung konfigu- z z Z z in das Menü "Quick start" und riert: V / f q u i c k dort in das Untermenü "V/f quick" wechseln...
  • Seite 60 Lenze−Einstellung: 50.00 Hz Stellen Sie die U −Anhebung ein (C0016) Die Lenze−Einstellung ist für alle gängigen Anwendungen geeignet Lenze−Einstellung: abhängig vom Typ des An- triebsreglers C0015 Aktivieren Sie die Motortemperatur−Überwa- Einstellmöglichkeiten: (^ 72) chung (C0119), wenn Sie einen PTC oder Ther- mokontakt an den Klemme X2.2 angeschlossen...
  • Seite 61: Mit Dem Keypad Xt Emz9371Bc − Vector−Regelung

    Code die Menü−Ebene wechseln dung benötigen. Die digitalen Ein- Para Quick start gänge sind in Lenze−Einstellung z z Z z in das Menü "Quick start" und konfiguriert: V e c t o r C t r l q u dort in das Untermenü "VectorCtrl qu" wechseln...
  • Seite 62 Inbetriebnahme Mit dem Keypad XT EMZ9371BC − Vector−Regelung Einschaltreihenfolge Bemerkung Stellen Sie die minimale Ausgangsfrequenz ein (C0010) C0011 Lenze−Einstellung: 0.00 Hz Stellen Sie die maximale Ausgangsfrequenz ein (C0011) C0010 Lenze−Einstellung: 50.00 Hz 100 % Stellen Sie die Hochlaufzeit T ein (C0012)
  • Seite 63 Aktivieren Sie die Motortemperatur−Überwa- Einstellmöglichkeiten: (^ 72) chung (C0119), wenn Sie einen PTC oder Ther- mokontakt an den Klemme X2.2 angeschlossen haben Lenze−Einstellung: ausgeschaltet Sollwert vorgeben Z. B. über Potentiometer an den Klemmen 7, 8, 9 Regler freigeben Klemme X3/28 = HIGH misc002 Der Antrieb läuft jetzt...
  • Seite 64 Inbetriebnahme Mit dem Keypad XT EMZ9371BC − Vector−Regelung Vector−Regelung optimieren Die Vector−Regelung ist nach der Motorparameter−Identifizierung in der Regel ohne wei- tere Maßnahmen betriebsfähig. Sie müssen die Vector−Regelung nur bei folgendem An- triebsverhalten optimieren:−14− Antriebsverhalten Abhilfe Rauher Motorlauf und Motorstrom (C0054) > 60 % Motor−Bemes- 1.
  • Seite 65: Die Wichtigsten Codes Für Die Inbetriebnahme

    Code, Subcode oder Auswahl nur verfügbar bei Betrieb mit Application−I/O Code ist in der Lenze−Einstellung im USER−Menü enthalten uSEr Bezeichnung Bezeichnung des Code Lenze Lenze−Einstellung (Wert bei Auslieferung oder nach Wiederherstellen des Lieferzu- stands mit C0002) à Die Spalte "WICHTIG" enthält weitere Information Auswahl 99 min. Wert {Einheit} max.
  • Seite 66 Inbetriebnahme Die wichtigsten Codes für die Inbetriebnahme Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0002* Parametersatz- Bereit PAR1 ... PAR4: verwaltung Parametersätze des Antriebsreglers −15− PAR1 ... PAR4 enthalten auch die uSEr Parameter für die Funktionsmodule Standard−I/O, Application−I/O, AS− interface, Systembus (CAN)
  • Seite 67 Inbetriebnahme Die wichtigsten Codes für die Inbetriebnahme Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl ð C0002* Parametersätze Gewählten Parametersatz und ggf. Keypad PAR1 (+ FPAR1) mit Keypad über- FPAR1 mit den entsprechenden Daten mit Funktionsmodul Application−I/O, INTER- tragen des Keypad überschreiben uSEr BUS, PROFIBUS−DP, LECOM−B, DeviceNet/...
  • Seite 68 Inbetriebnahme Die wichtigsten Codes für die Inbetriebnahme Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl ð C0002* eigene Grundein- Sie können für die Parameter des An- PAR1 eigene Grundeinstellung stellung spei- triebsreglers eine eigene Grundeinstel- chern lung speichern (z. B. den Lieferzu-...
  • Seite 69 Inbetriebnahme Die wichtigsten Codes für die Inbetriebnahme Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0007 Feste Konfigura- Änderung von C0007 wird in den tion digitale Ein- entsprechenden Subcode von gänge C0410 kopiert. Freie Konfiguration uSEr in C0410 setzt C0007 = 255!
  • Seite 70 Inbetriebnahme Die wichtigsten Codes für die Inbetriebnahme Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0007 H/Re = Hand/Remote−Umschaltung PCTRL1−I−OFF = I−Anteil Prozeß- CCW/QSP CW/QSP TRIP−Set JOG1/3 regler ausschalten uSEr CCW/QSP CW/QSP DOWN DFIN1−ON = Digitaler Frequenzein- (Forts.) CCW/QSP CW/QSP JOG1/3 gang 0 ... 10 kHz...
  • Seite 71 50.00 7.50 {0.02 Hz} 650.00 à Drehzahlstellbereich 1 : 6 für gangsfrequenz Lenze−Getriebemotoren: Bei Be- à 87 Hz uSEr trieb mit Lenze−Getriebemotoren un- bedingt einstellen. C0012 Hochlaufzeit 5.00 0.00 {0.02 s} 1300.00 Bezug: Frequenzänderung 0 Hz ... Hauptsollwert C0011 uSEr ð...
  • Seite 72 Inbetriebnahme Die wichtigsten Codes für die Inbetriebnahme Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0014 Betriebsart Inbetriebnahme ohne Identifizie- U/f−Kennliniensteuerung U ~ f rung der Motorparameter möglich (lineare Kennlinie mit konstanter U −An- hebung) Vorteil der Identifizierung mit C0148: – Verbesserter Rundlauf bei klei- nen Drehzahlen U/f−Kennliniensteuerung U ~ f...
  • Seite 73 Inbetriebnahme Die wichtigsten Codes für die Inbetriebnahme Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0034* Bereich Sollwert- Jumperstellung des Funktionsmoduls vorgabe beachten! Application−I/O uSEr 1 X3/1U, X3/1I Spannung unipolar 0 ... 5 V / 0 ... 10 V 2 X3/2U, X3/2I Spannung bipolar −10 V ...
  • Seite 74 Inbetriebnahme Die wichtigsten Codes für die Inbetriebnahme Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0140* Additiver Fre- 0.00 −650.00 {0.02 Hz} 650.00 Vorgabe über Funktion quenzsollwert Keypad oder Parameterkanal (NSET1−NADD) Wirkt additiv auf den Hauptsollwert Wert wird bei Netzschalten oder bei Abziehen des Keypad gespei-...
  • Seite 75: Störungen Erkennen Und Beseitigen

    Störungen erkennen und beseitigen Fehlverhalten des Antriebs Fehlverhalten Ursache Abhilfe Motor dreht nicht Zwischenkreisspannung zu niedrig Netzspannung prüfen (Rote LED blinkt im 0.4 s Takt; Anzeige Keypad: Antriebsregler gesperrt Reglersperre aufheben, Reglersperre kann über mehrere Quellen gesetzt sein (Grüne LED blinkt, Anzeige Keypad: Automatischer Start gesperrt (C0142 = 0 oder 2) LOW−HIGH−Flanke an X3/28 Evtl.
  • Seite 76 Vector−Regelung optimieren (^ 50) gelung nicht zufriedenstellend Einbruch des Drehmoments im verschiedene Rücksprache mit Lenze Feldschwächbereich Kippen des Motors bei Betrieb im Feldschwächbereich EDK82EV113 DE/EN/FR 8.1 Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Seite 77: Störungsmeldungen

    Störungen erkennen und beseitigen Störungsmeldungen LED’s am Antriebsregler (Statusanzeige) −18− Betriebszustand  ‚ grün Antriebsregler freigegeben Netz eingeschaltet und automatischer Start gesperrt blinkt langsam Antriebsregler gesperrt blinkt schnell Motorparameter−Identifizierung wird durchgeführt blinkt schnell Unterspannungsabschaltung blinkt langsam Störung aktiv, Kontrolle in C0161 ...
  • Seite 78: Störungsmeldungen Am Keypad Oder Im Parametrierprogramm Global Drive Control

    (C0370): (konfigurierbar in Systembus−Konfiguration prüfen C0126) Slave antwortet nicht. Kommunika- tions−Überwachungszeit überschritten Bei Betrieb mit Modul auf FIF: Rücksprache mit Lenze erforderlich Interner Fehler Funktionsmodul CAN Controller meldet Zustand "War- Prüfen, ob Busabschluß vorhanden Systembus (CAN) auf nung" oder "BUS−OFF"...
  • Seite 79 C0126) Externe Störung (TRIP− Ein mit der Funktion TRIP−Set belegtes Externen Geber überprüfen SET) digitales Signal ist aktiviert Interne Störung Rücksprache mit Lenze erforderlich Fehlerhafte Parameter− Motor nicht angeschlossen Motor anschließen Identifizierung Fehler in Motorphase Ausfall einer/mehrerer Motorpha- Motorzuleitungen prüfen (Anzeige, wenn C0597 −Anhebung prüfen,...
  • Seite 80 (Motor vom Umrichter trennen) Parameter−Übertragung Alle Parametersätze sind defekt Vor Reglerfreigabe unbedingt den Daten- mit dem Keypad fehler- transfer wiederholen oder die Lenze−Ein- stellung laden haft PAR1 mit dem Keypad PAR1 ist defekt falsch übertragen PAR2 mit dem Keypad PAR2 ist defekt falsch übertragen...
  • Seite 81 Störungen erkennen und beseitigen Störungsmeldungen Keypad Störung Ursache Abhilfe Interne Störung Rücksprache mit Lenze erforderlich Zeitfehler bei Parame- Datenfluß vom Keypad oder vom PC Vor Reglerfreigabe unbedingt den Daten- tersatz−Transfer unterbrochen, z. B. Keypad wurde transfer wiederholen oder Lenze−Einstel- während der Datenübertragung abge- lung laden.
  • Seite 82 Störungen erkennen und beseitigen Störungsmeldungen EDK82EV113 DE/EN/FR 8.1 Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Seite 83: Items Supplied

    Items supplied Position Description 8200 vector frequency inverters Mounting Instructions and Getting Started ^ 95 Holder for standard mounting ^ 97 EMC shield sheet with shield clips for the motor cable and the supply for the motor temperature monitoring ^ 97 2−pole terminal strip for motor PE and motor shield at X2.1 ^ 97 EMC shield sheet with mounting screws and shield clamps for shielded control cables...
  • Seite 84 This documentation is only valid for 8200 vector frequency inverters as of version:  ‚ ƒ E82xV 55 Aerzen Hans-Lenze-Str. 1 ‚ ƒ D-31855 Aerzen ‚ ƒ Type Inverter 8200 vector Version: Id.-No: Version: Prod.-No: Ser.-No: E = Built−in unit Ser.-No:...
  • Seite 85 Note! Current documentation and software updates for Lenze products can be found on the internet in the "Downloads" area under http://www.Lenze.com Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Seite 86 Contents Safety instructions ..........Technical data .
  • Seite 87: Safety Instructions

    Safety and application notes for Lenze controllers (in conformity with Low−Voltage Directive 73/23/EEC) General Lenze controllers (frequency inverters, servo inverters, DC controllers) can include live and rotating parts − depending on their type of protection − during operation. Surfaces can be hot.
  • Seite 88 Safety instructions Transport, storage Please observe the notes on transport, storage and appropriate handling. Observe the climatic conditions according to EN 50178. Installation The controllers must be installed and cooled according to the regulation and instructions given in the corresponding documentation. Ensure proper handling and avoid mechanical stress.
  • Seite 89 Safety instructions Safe standstill −19− Variant V004 of the controller series 9300 and 9300 vector, variante x4x of the controller series 8200 vector and axis controller ECSxAxxx support the function "Safe standstill", protection against unintended start, according to the requirements of Appendix I, No. 1.2.7 of the EC Directive "Machinery"...
  • Seite 90 Safety instructions Controller protection All pluggable connection terminals must only be connected or disconnected when no voltage is applied! Cyclic connection and disconnection of the supply voltage can overload and destroy the input current limitation of the controller: – In case of cyclic mains switching over a longer period of time three minutes have to pass between two starting operations! Motor protection Depending on the controller settings, the connected motor can be overheated:...
  • Seite 91 Safety instructions Layout of safety instructions All safety instructions given in these Instructions have got the same structure: Pictograph (indicates the type of danger) Danger! (indicates the degree of danger) Note (describes the danger and explains how to avoid it) Pictograph Signal word Meaning...
  • Seite 92: Technical Data

    Technical data Normes et application conditions Standards Conformity Low−Voltage Directive (73/23/EEC) Approvals UL 508C Power Conversion Equipment (File−No. E132659) Environmental conditions Climatic conditions Storage IEC/EN 60721−3−1 1K3 (−25 ... +60 °C) < 6 month 1K3 (−25 ... +40 °C) > 6 month >...
  • Seite 93: General Technical Data

    Technical data General technical data Compliance with EN 61800−3/A11 Noise emission Compliance with limit value classes A and B to EN 55011 E82EVxxxKxC0xx without additional measures E82EVxxxKxC2xx by means of external filters Noise immunity Requirements to EN 61800−3 incl. A11 Requirements Standard Severities...
  • Seite 94: Operation With Rated Power (Normal Operation)

    Technical data Operation with rated power (normal operation) Type Rated mains voltage Power Mains current [A] Output current [A] Weight  ‚ [kW] (60 s) [kg] E82EV302K2C 15.6 12.0 12.0 18.0 3/PE AC 230/240 V E82EV402K2C 21.3 16.0 16.5 24.8 50 Hz E82EV552K2C 29.3...
  • Seite 95: Operation With Increased Rated Power

    Technical data Operation with increased rated power Under the application conditions described here the controller can be operated in continuous operation with a motor of higher performance. The overload capacity is reduced to 120 %. Typical applications are pumps with square−law load characteristic or blowers. Note! Operation with increased rated power is only permissible with the drive controllers mentioned...
  • Seite 96: Mechanical Installation

    Mechanical installation Dimensions for standard fixing 8200 vector 3 ... 11 kW −20−8200vec060 Different sizes can only be mounted side−by−side when the smaller units are mounted to the right−hand−side of the bigger units! Dimensions in mm E82EV302K2C E82EV402K2C E82EV552K2C 62.5 280 ...
  • Seite 97: Electrical Installation

    Electrical installation Wiring of terminal strips The enclosed terminal strips are tested according to the specifications of the DIN VDE 0627:1986−06 (partially) DIN EN 60999:1994−04 (partially) Checked and tested are, for instance, mechanical, electrical and thermal load, vibration, damage of conductors, loose conductors, corrosion, ageing. Stop! Proceed as follows to avoid damage of the contacts: Mount only when the controller is not connected to the mains.
  • Seite 98: Installation According To Emc Requirements (Ce−Typical Drive System)

    Electrical installation Installation according to EMC requirements (CE−typical drive system) L < 40 mm L < 500 mm −21−8200vec066 EDK82EV113 DE/EN/FR 8.1 Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Seite 99 Electrical installation Installation according to EMC requirements (CE−typical drive system) Stop! Control cables and mains cables must be separated from the motor cable to avoid interferences. Control cable must always be shielded. We recommend to shield the supply cable for the PTC or thermal contact and route it separetely from the motor cable.
  • Seite 100: Mains Connection 230 V/240 V

    Electrical installation Mains connection 230 V/240 V Stop! Controller type E82EVxxxK 2C must only be connected to a mains voltage of 3/PE AC 100 ... 264 V. Higher mains voltages will destroy the controller! The discharge current to PE is > 3.5 mA. EN 50178 requires a fixed installation.
  • Seite 101 Electrical installation Mains connection 230 V/240 V Fuses and cable cross−section (operation with rated power) Operation without mains choke Installation to EN 60204−1 Installation to UL  ‚  8200 vector mains L1, L2, L3, L1, L2, L3, Type [kW] [AWG] E82EV302K2C M20 A...
  • Seite 102 Electrical installation Mains connection 230 V/240 V Fuses and cable cross−sections (operation with increased rated power) Operation without mains choke Installation to EN 60204−1 Installation to UL  ‚  8200 vector mains L1, L2, L3, L1, L2, L3, Type [kW] [AWG] E82EV302K2C...
  • Seite 103: Mains Connection 400 V/500 V

    Electrical installation Mains connection 400 V/500 V Stop! Controller type E82EVxxxK 4C must only be connected to a mains voltage of 3/PE AC 320 ... 550 V. Higher mains voltages will destroy the controller! The discharge current to PE is > 3.5 mA. EN 50178 requires a fixed installation.
  • Seite 104 Electrical installation Mains connection 400 V/500 V Fuses and cable cross−section (operation with rated power) Operation without mains choke Installation to EN 60204−1 Installation to UL  ‚  8200 vector mains L1, L2, L3, L1, L2, L3, Type [kW] [AWG] E82EV302K4C M16 A...
  • Seite 105 Electrical installation Mains connection 400 V/500 V Fuses and cable cross−sections (operation with increased rated power) Operation without mains choke Installation to EN 60204−1 Installation to UL  ‚  8200 vector mains L1, L2, L3, L1, L2, L3, Type [kW] [AWG] E82EV302K4C...
  • Seite 106: Connection Of Motor / Brake Resistor

    Electrical installation Connection of motor / brake resistor 0,7...0,8 Nm 6.2...7.1 lb-in 6 mm / 0.24 in 8200 vector X2.1 X2.2 T1 T2 X2.1 ϑ> X2.2 −24−8200vec064 £ 75 pF/m; from 2.5 mm £ 100 pF/m; core/shield £ 150 pF/m) Use low−capacity motor cables! (core/core up to 1.5 mm The shorter the motor cables, the better the drive response! HF−shield end by PE connection through shield bracket or EMC cable connection.
  • Seite 107: Connection Of Relay Output

    Electrical installation Connection of relay output −25−8200vec061 Function Message Relay position set Technical data (Lenze setting) X1.2/K11 Relay output normally−closed open TRIP contact AC 250 V/3 A X1.2/K12 Mid position contact DC 24 V/2 A ... DC 240 V/0.16 A X1.2/K14...
  • Seite 108: Connection Of Relay Output Ksr For Safe Standstill

    Electrical installation Connection of relay output K for Safe standstill" (only active at variant E82EVxxxK4Cx 4 x)−26− Variant x 4 x of the controller supports the safety function "Safe standstill", protection against unexpected start, according to the requirements of the EN 954−1 control category 3"...
  • Seite 109 Electrical installation Connection of relay output K for Safe standstill" +24V X3.1 X3.1 34 33 K32 K31 + 5 V 8200 vector IGBT 8200vec266 Fig. 1 Relay K Terminal assignment Data Reference potential for the input Safety relay Coil voltage at +40°C DC +24 V (+19.5 ...
  • Seite 110: Function Module (Optional)

    Function module (optional) Mounting Important notes The basic controller version is not equipped with control terminals. The controllers can be equipped with control terminals by using different I/O function modules for the FIF interface. Dismount the function module only if it is absolutely necessary (e.g. when the controller is replaced).
  • Seite 111 Function module (optional) Mounting Mounting of function modules in "PT" version  ‚ −28− 8200vec372 In addition fix the safety clip, so that the module is prevented from being pulled out together with the terminal strips: 1. Turn the safety clip 4 in the openings. 2.
  • Seite 112: Dismounting

    Function module (optional) Dismounting Dismounting of the function modules  ‚ 3 min 8200vec072 1. Disconnect the controller from the mains and wait for at least 3 minutes! 2. Catch the bar of the plug connector with pliers and pull. 0 Plug connector and function module are dismounted together.
  • Seite 113 Function module (optional) Dismounting Dismounting of the function module version "PT"  ‚ ƒ 8200vec372 After the function module version "PT" has been switched off, first of all the safety clip must be removed. 1. Position the screw driver between safety clip and function module 0. The safety clip is disengaged by pressing to the right.
  • Seite 114: Communication Module (Option)

    Communication module (Option) Mounting/dismounting  ‚ −29−8200vec073 Jumper for selecting the voltage supply  External voltage supply (delivery state) ‚ Voltage supply via internal voltage source Attach/detach the communication module to/from the AIF interface. This is also possible during operation. Possible combinations Communication module on AIF Keypad...
  • Seite 115: Commissioning

    Commissioning Before switching on Note! Do not change the switch−on sequence. In the event of an error during commissioning, please see the chapter "Fault detection and elimination". To avoid injury to persons or damage to property, check..before the mains voltage is connected: The wiring for completeness, short circuit and earth fault "Emergency−off"...
  • Seite 116: Selection Of The Correct Operating Mode

    Commissioning Selection of the correct operating mode The following table helps you to find the correct control mode for standard applications. You can choose between V/f characteristic control, vector control and sensorless torque control: V/f characteristic control is the classic control mode for standard applications. The vector control provides better control features than the V/f characteristic control because of: a higher torque over the whole speed range...
  • Seite 117 Commissioning Selection of the correct operating mode Application Operating mode Setting in C0014 Stand−alone drives recommended alternatively with extremely alternating loads with heavy start conditions with speed control (speed feedback) with high dynamic response (e. g. positioning and infeed drives) −...
  • Seite 118: Using The Keypad E82Zbc − Parameter Setting

    Commissioning Using the keypad E82ZBC − Parameter setting Description The keypad is available as accessory. A full description of the keypad can be obtained from the Instructions included in the keypad delivery. Plugging in the keypad It is possible to plug in the keypad onto the AIF interface or remove it during operation. As soon as the keypad is supplied with voltage, it carries out a self−test.
  • Seite 119 Fault active Bargraph display Value set under C0004 in % Display range: − 180 % ... + 180 % (every bar = 20 %) (Lenze setting: Controller load C0056) Function bar 1 Function Meaning Explanation Not possible when password protection is active (display Setpoint selection via "loc"...
  • Seite 120: Change And Save Parameters

    Keys Result Note Plug in the keypad Function is activated. The first code in the user menu will be displayed (C0517/1, Lenze setting: C0050 = output xx.xx frequency).  If necessary change to the Change to function bar 2 menu "ALL"...
  • Seite 121 The menu user – is active after every mains switching or keypad attachment during operation. – contains all codes for a standard application with linear V/f characteristic control (Lenze setting). – can be modified as required under C0517. The menu all –...
  • Seite 122 Use C0002 "Parameter set transfer/restorage of default setting" to transfer configurations from one controller to the other with keypad or restore the default setting by loading the Lenze setting (e.g. if you lost track during parameter setting). EDK82EV113 DE/EN/FR 8.1...
  • Seite 123 Commissioning Using the keypad E82ZBC − Parameter setting Œ Œ 0050 0050   s u e r AL L ~5 s … … Œ 0050 ‚ Œ Œ 0XXX 000X ‚ ‚ C000x C517/1 user Œ Œ 0XYZ 0XYZ C000x+1 ‚...
  • Seite 124: Using The Keypad E82Zbc − Linear V/F Characteristic Control

    (0 ... 5 V/0 ... 10 V/0 ... 20 mA) Adapt the terminal configuration to the wiring Œ 0007 ‚ (C0007) Lenze setting: −0−, i. e. E1: JOG1/3 fixed setpoint selection E2: JOG2/3 E3: DCB DC brake E4: CW/CCW operation Set the minimum output frequency (C0010) C0011 Lenze setting: 0.00 Hz...
  • Seite 125 Set the V/f−rated frequency (C0015) 100% Lenze setting: 50.00 Hz Set the V boost (C0016) The Lenze setting is suitable for all common applications Lenze settings: Depending on the controller type C0015 If you want to change the settings, please go to activate e.
  • Seite 126: Using The Keypad E82Zbc − Vector Control

    Adapt the terminal configuration to the wiring Œ 0007 ‚ (C0007) Lenze setting: 0, i. e. E1: JOG1/3 fixed setpoint selection E2: JOG2/3 E3: DCB DC brake E4: CW/CCW operation Set the minimum output frequency (C0010) C0011 Lenze setting: 0.00 Hz...
  • Seite 127 0034 ‚ setpoint (C0034) standard−I/O to the same range (see Mounting Instructions for the Lenze setting: 0, (0 ... 5 V/0 ... 10 V/0 ... 20 mA) standard−I/O) Enter the motor data See motor nameplate Rated motor speed (C0087) Lenze setting: 1390 rpm...
  • Seite 128: Vector Control Optimisation

    Commissioning Using the keypad E82ZBC − Vector control Switch−on sequence Note If necessary, adjust more parameters Activate e. g. JOG frequencies (JOG) (C0037, C0038, C0039 or motor parameter monitoring (C0119) After parameter setting: Setpoint selection E.g. via potentiometer at terminals 7, 8, 9 Enable the controller.
  • Seite 129: Using The Keypad Xt Emz9371Bc − Parameter Setting

    Commissioning Using the keypad XT EMZ9371BC − Parameter setting Description The keypad is available as accessory. A full description of the keypad can be obtained from the Instructions included in the keypad delivery. Plug in the keypad It is possible to plug in the keypad onto the AIF interface or remove it during operation. As soon as the keypad is supplied with voltage, it carries out a self−test.
  • Seite 130 Commissioning Using the keypad XT EMZ9371BC − Parameter setting Adoption of parameters Display Meaning Explanation Parameters are adopted immediately Basic device operates immediately with the new parameter value Basic device operates with the new parameter SHPRG Parameter must be confirmed with value, after it was confirmed SHPRG In case of controller inhibit the parameter must be...
  • Seite 131 Commissioning Using the keypad XT EMZ9371BC − Parameter setting Function keys Note! Press the key combinations with T: T and keep them pressed, then additionally press the second key. Press key Function −31− Menu level Code level Parameter level Operation level Change to the parameter Change to the operation Change to the code level...
  • Seite 132 Commissioning Using the keypad XT EMZ9371BC − Parameter setting Change and save parameters All parameters for controller setting or monitoring are saved in codes. The codes are numbered and labelled in the documentation with a "C". Some codes store the parameters in numbered subcodes", so that a clear parameter setting is ensured (e.
  • Seite 133: Menu Structure

    Commissioning Using the keypad XT EMZ9371BC − Parameter setting Menu structure Main menu Submenus Description No. Display Display USER menu Defined codes in C0517 Code list All available codes All available codes in ascending order (C0001 ... C7999) Para set 1 Codes in parameter set 1 (C0001 ...
  • Seite 134 Commissioning Using the keypad XT EMZ9371BC − Parameter setting Main menu Submenus Description Description Display Display Main FB See description of the keypad Configuration of function blocks Controller See description of the keypad Configuration of internal control parameters Terminal I/O See description of the keypad Linkage of inputs and outputs with internal signals and display of the signal levels at the terminals LECOM/AIF...
  • Seite 135: Using The Keypad Xt Emz9371Bc − Linear V/F Characteristic Control

    Set the DIP switch on the analog setpoint (C0034) standard I/O to the same range (see Mounting Instructions for the Lenze setting: 0, (0 ... 5 V/0 ... 10 V/0 ... 20 mA) standard I/O) If necessary, adapt the JOG setpoints. JOG 1 (C0037)
  • Seite 136: In The Menu "Diagnostic" The Most Important Drive Parameters Can Be Monitored

    Set the V/f−rated frequency (C0015) 100% Lenze setting: 50.00 Hz Set the V boost (C0016) The Lenze setting is suitable for all common applications Lenze setting: dependent on the controller type C0015 Activate the motor temperature monitoring Setting possibilities: (^ 148) (C0119) if a PTC or thermal contact is connected to the terminal X2.2.
  • Seite 137: Using The Keypad Xt Emz9371Bc − Vector Control

    Set the DIP switch on the analog setpoint (C0034) standard I/O to the same range (see Mounting Instructions for the Lenze setting: 0, (0 ... 5 V/0 ... 10 V/0 ... 20 mA) standard I/O) If necessary, adapt the JOG setpoints. JOG 1 (C0037)
  • Seite 138 Lenze setting: 5.00 s T i r T i f = deceleration time wanted Set the control mode "Vector control" (C0014 = Lenze setting: Linear V/f characteristic control SHPRG Menu 0014 Code (C0014 = 2) Para...
  • Seite 139 Activate the motor temperature monitoring Setting possibilities: (^ 148) (C0119), if a PTC or thermal contact is connected to the terminal X2.2 Lenze setting: switched−off Setpoint selection e. g. via potentiometer at the terminals 7, 8, 9 Enable the controller.
  • Seite 140 Commissioning Using the keypad XT EMZ9371BC − Vector control Vector control optimisation In general, the vector control is ready for operation after the motor parameters have been identified. Vector control must only be optimised for the following drive performance: −32− Drive performance Remedy Rough motor run and motor current (C0054) >...
  • Seite 141: The Most Important Codes For Commissioning

    With Lenze setting the code is available in the USER−menu uSEr Name Name of the code Lenze Lenze setting (value at delivery or after restoring the delivery state with C0002) à Further information can be obtained from "IMPORTANT" Selection 99 Min. value {unit} Max.
  • Seite 142 Commissioning The most important codes for commissioning Code Possible settings IMPORTANT Name Lenze Selection C0002* Parameter set Ready PAR1 ... PAR4: management Parameter sets of the controller −33− PAR1 ... PAR4 also contain uSEr parameters for Standard−I/O, Application−I/O, AS interface or...
  • Seite 143 Commissioning The most important codes for commissioning Code Possible settings IMPORTANT Name Lenze Selection ð C0002* Parameter set Overwrite selected parameter set and, Keypad PAR1 (+ FPAR1) transfer using if necessary, FPAR1 with the With function module Application−I/O, the keypad...
  • Seite 144 Commissioning The most important codes for commissioning Code Possible settings IMPORTANT Name Lenze Selection ð C0002* Saving of own You can save your own basic settings PAR1 Own settings settings for a controller (e.g. machine delivery status): uSEr 1. Ensure that parameter set 1 is (cont.)
  • Seite 145 Commissioning The most important codes for commissioning Code Possible settings IMPORTANT Name Lenze Selection C0007 Fixed Change under C0007 will be copied configuration of to the corresponding subcode of digital inputs C0410. Free configuration under uSEr C0410 sets C0007 = 255!
  • Seite 146 Commissioning The most important codes for commissioning Code Possible settings IMPORTANT Name Lenze Selection C0007 H/Re = Hand/remote changeover PCTRL1−I−OFF = Switch off CCW/QSP CW/QSP TRIP set JOG1/3 process controller I component uSEr CCW/QSP CW/QSP DOWN DFIN1−ON = Digital frequency input (cont.)
  • Seite 147 C0010 only limits the analog input C0011 Maximum output 50.00 7.50 {0.02 Hz} 650.00 à Speed setting range 1 : 6 for frequency Lenze geared motors: Setting à 87 Hz uSEr absolutely required for operation with Lenze geared motors. C0012 Acceleration time 5.00 0.00...
  • Seite 148 Commissioning The most important codes for commissioning Code Possible settings IMPORTANT Name Lenze Selection C0014 Operating mode Commissioning without motor V/f characteristic control V ~ f parameter identification possible (Linear characteristic with constant V boost) Benefit of identification with C0148: –...
  • Seite 149 Commissioning The most important codes for commissioning Code Possible settings IMPORTANT Name Lenze Selection C0034* Setpoint Observe the jumper setting of the selection range function module! Application I/O uSEr 1 X3/1U, X3/1I Unipolar voltage 0 ... 5 V / 0 ... 10 V 2 X3/2U, X3/2I Bipolar voltage −10 V ...
  • Seite 150 C0517/1 will be displayed. 1 Memory 1 C0050 Output frequency (MCTRL1−NOUT) In Lenze setting, the user menu contains the most important codes 2 Memory 2 C0034 Analog setpoint selection range for starting−up the control mode...
  • Seite 151: Fault Detection And Elimination

    Fault detection and elimination Malfunction of the drive Fault Cause Remedy Motor does not rotate DC−bus voltage too low Check mains voltage (Red LED is blinking every 0.4 s; keypad display Controller inhibited Remove the controller inhibit, controller inhibit can be set through several (Green LED is blinking, keypad display: sources Automatic start inhibited (C0142 = 0 or 2)
  • Seite 152 Unacceptable drive response various Optimise vector control (^ 127) with vector control Torque dip in the field weakening various Contact Lenze range Stalling of the motor when operating in the field weakening range EDK82EV113 DE/EN/FR 8.1 Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Seite 153: Fault Messages

    Fault detection and elimination Fault messages LED’s at the drive controller (status display) −36− Operating status  ‚ green Controller enabled Mains switched on and automatic start inhibited slowly blinking Controller inhibited fast blinking Motor parameter identification fast blinking Undervoltage switch−off slowly blinking Fault active, check under C0161 ...
  • Seite 154 (configurable in C0126) Check system bus configuration Slave does not answer. Communication monitoring time exceeded. For operation with module in FIF: Contact Lenze Internal fault Function module CAN controller sets "Warning" or "BUS Check whether bus terminator available system bus (CAN) on OFF"...
  • Seite 155 External fault A digital input assigned to the Check external encoder (TRIP−SET) TRIP−Set function has been activated. Internal fault Contact Lenze Faulty parameter Motor not connected Connect motor identification Fault in motor phase Failure of one/several motor Check motor cables...
  • Seite 156 Fault detection and elimination Fault messages Keypad Error Cause Remedy Motor overload (I Motor is thermally overloaded, for overload) instance, because of impermissible continuous current Check drive selection frequent or too long acceleration Check setting of C0120 processes Heat sink temperature Ambient temperature too high Allow controller to cool and ensure better >...
  • Seite 157 Remedy Faulty parameter All parameter sets are defective It is absolutely necessary to repeat the data transfer when using transfer or load the Lenze setting before the keypad enabling the controller. Wrong PAR1 transfer PAR1 is defective. when using the keypad.
  • Seite 158 Fault detection and elimination Fault messages EDK82EV113 DE/EN/FR 8.1 Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Seite 159: Equipement Livré

    Equipement livré Position Description Convertisseur de fréquence 8200 vector Instructions de montage et aide à la mise en service ^ 172 Eléments pour fixation standard ^ 174 Tôle de blindage CEM avec colliers de blindage pour le câble moteur et le câble de surveillance de température moteur ^ 174 Bornier à...
  • Seite 160 Le présent fascicule s’applique aux convertisseurs de fréquence 8200 vector des versions suivantes :  ‚ ƒ E82xV 55 Aerzen Hans-Lenze-Str. 1 ‚ ƒ D-31855 Aerzen ‚ ƒ Inverter 8200 vector Version: Id.-No: Version: Prod.-No: Ser.-No: E = Appareil sans coffret Ser.-No:...
  • Seite 161: Remarque Importante

    Remarque importante ! Les mises à jours de logiciels et les documentations récentes relatives aux produits Lenze sont disponibles dans la zone "Downloads" (téléchargement) du site internet : http://www.Lenze.com Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Seite 162 Sommaire Consignes de sécurité ..........Spécifications techniques .
  • Seite 163: Consignes De Sécurité

    Lenze Conformes à la directive Basse Tension 73/23/CEE Généralités Selon leur degré de protection, les variateurs de vitesse Lenze (convertisseurs de fréquence, servovariateurs, variateurs de vitesse) peuvent avoir, pendant leur fonctionnement, des parties sous tension, éventuellement en mouvement ou tournantes.
  • Seite 164 Consignes de sécurité Utilisation conforme à l’application Les variateurs de vitesse sont des composants destinés à être incorporés dans des installations ou machines électriques. Ils ne constituent pas des appareils domestiques, mais des éléments à usage industriel et professionnel au sens de la norme EN 61000−3−2. Cette documentation contient des indications au sujet du respect des valeurs limites selon EN 61000−3−2.
  • Seite 165 Consignes de sécurité Raccordement électrique Lorsque des travaux sont effectués sur le variateur de vitesse sous tension, les prescriptions nationales pour la prévention d’accidents doivent être respectées (par exemple VBG 4). L’installation électrique doit être exécutée en conformité avec les prescriptions applicables (par exemple sections des conducteurs, protection par coupe−circuit à...
  • Seite 166 Consignes de sécurité Arrêt sécurisé −37− La variante V004 des variateurs 9300 et 9300 vector, la variante x4x du convertisseur 8200 vector et le variateur ECSxAxxx prennent en charge la fonction "Arrêt sécurisé", qui protège contre un démarrage incontrôlé, conformément à l’annexe 1.2.7 de la Directive CE "Machines"...
  • Seite 167 Consignes de sécurité Protection des appareils Ne retirer ou enficher les borniers de raccordement qu’à l’état hors tension ! Mises sous tension répétées : des mises sous tension répétées peuvent perturber la limitation du courant d’entrée du variateur de vitesse : –...
  • Seite 168 Consignes de sécurité Warnings! The device has no overspeed protection. Must be provided with external or remote overload protection. Suitable for use on a circuit capable of delivering not more than 5000 rms symmetrical amperes, 240 V maximum (240 V devices) or 500 V maximum (400/500 V devices) resp.
  • Seite 169: Spécifications Techniques

    Spécifications techniques Normes et conditions d’utilisation Normes Conformité Directive Basse Tension (73/23/CEE) Homologations UL 508C Power Conversion Equipment (File−No. E132659) Conditions ambiantes Conditions climatiques Stockage IEC/EN 60721−3−1 1K3 (−25 ... +60 °C) < 6 mois 1K3 (−25 ... +40 °C) >...
  • Seite 170: Caractéristiques Électriques Générales

    Spécifications techniques Caractéristiques électriques générales Respect des exigences selon EN 61800−3/A11 Essai d’émission Respect des valeurs limites classe A et B selon EN 55011 E82EVxxxKxC0xx sans mesure supplémentaire E82EVxxxKxC2xx avec filtres externes Antiparasitage Valeurs limites respectées selon EN 61800−3, A11 compris Exigences Norme Degré...
  • Seite 171 Spécifications techniques Fonctionnement avec puissance nominale (fonctionnement standard) Type Tension nominale réseau Puissan Courant réseau [A] Courant de sortie [A] Poids  ‚ [kW] (60 s) [kg] E82EV302K2C 15,6 12,0 12,0 18,0 3/PE 230/240 V CA E82EV402K2C 21,3 16,0 16,5 24,8 50 Hz E82EV552K2C...
  • Seite 172 Spécifications techniques Fonctionnement avec puissance nominale accrue Dans des conditions de fonctionnement décrites par la suite, le convertisseur de fréquence peut fonctionner, en service permanent, avec un moteur plus puissant. La capacité de surcharge est réduite à 120 % de surcharge de courant. Le fonctionnement avec puissance nominale accrue est parfaitement adapté...
  • Seite 173: Installation Mécanique

    Installation mécanique Encombrements avec fixation standard 8200 vector 3 ... 11 kW −38−8200vec060 Pour la juxtaposition de tailles différentes, positionner la taille plus petite à droite ! Encombrements en mm E82EV302K2C E82EV402K2C E82EV552K2C 62,5 280 ... 295 E82EV752K2C E82EV302K4C E82EV402K4C E82EV552K4C E82EV752K4C 62,5...
  • Seite 174: Installation Électrique

    Installation électrique Raccordement des borniers Les borniers compris dans la livraison ont été vérifiés et contrôlés conformément aux normes et réglementations suivantes : DIN VDE 0627 : 1986−06 (en partie) DIN EN 60999 : 1994−04 (en partie) Les borniers ont été soumis à des tests de charges mécaniques, électriques et thermiques, à...
  • Seite 175: Installation Conforme Cem (Système D'entraînement Ce)

    Installation électrique Installation conforme CEM (système d’entraînement CE) L < 40 mm L < 500 mm −39−8200vec066 EDK82EV113 DE/EN/FR 8.1 Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Seite 176 Installation électrique Installation conforme CEM (système d’entraînement CE) Stop ! Veiller à ce que les câbles de commande et les câbles bus de terrain ne passent pas dans les mêmes canalisations que les câbles moteur afin d’éviter des interférences radio. Blinder impérativement les câbles de commande.
  • Seite 177: Raccordement Réseau 230 V/240 V

    Installation électrique Raccordement réseau 230 V/240 V Stop ! Ne raccorder le convertisseur de fréquence type E82EVxxxK 2C qu’à un réseau 3/PE 100 ... 264 V CA. Toute tension réseau plus élevée risque d’endommager le convertisseur ! Le courant de fuite vers la terre (PE) est de > 3,5 mA. D’après la norme EN 50178, une installation fixe est nécessaire.
  • Seite 178 Installation électrique Raccordement réseau 230 V/240 V Fusibles et sections de câbles (fonctionnement avec puissance nominale) Fonctionnement sans self réseau Installation selon EN 60204−1 Installation selon UL  ‚  8200 vector Réseau L1, L2, L3, L1, L2, L3, Types [kW] [AWG] E82EV302K2C...
  • Seite 179 Installation électrique Raccordement réseau 230 V/240 V Fusibles et sections de câbles (fonctionnement avec puissance nominale accrue) Fonctionnement sans self réseau Installation selon EN 60204−1 Installation selon UL  ‚  8200 vector Réseau L1, L2, L3, L1, L2, L3, Types [kW] [AWG]...
  • Seite 180: Raccordement Réseau 400 V/500 V

    Installation électrique Raccordement réseau 400 V/500 V Stop ! Ne raccorder le convertisseur de fréquence type E82EVxxxK 4C qu’à un réseau 3/PE 320 ... 550 V CA. Toute tension réseau plus élevée risque d’endommager le convertisseur ! Le courant de fuite sur PE est de > 3,5 mA. D’après la norme EN 50178, une installation fixe est nécessaire.
  • Seite 181 Installation électrique Raccordement réseau 400 V/500 V Fusibles et sections de câbles (fonctionnement avec puissance nominale) Fonctionnement sans self réseau Installation selon EN 60204−1 Installation selon UL  ‚  8200 vector Réseau L1, L2, L3, L1, L2, L3, Types [kW] [AWG] E82EV302K4C...
  • Seite 182 Installation électrique Raccordement réseau 400 V/500 V Fusibles et sections de câbles (fonctionnement avec puissance nominale accrue) Fonctionnement sans self réseau Installation selon EN 60204−1 Installation selon UL  ‚  8200 vector Réseau L1, L2, L3, L1, L2, L3, Types [kW] [AWG]...
  • Seite 183: Raccordement Moteur/Résistance Externe

    Installation électrique Raccordement moteur/résistance externe 0,7...0,8 Nm 6.2...7.1 lb-in 6 mm / 0.24 in 8200 vector X2.1 X2.2 T1 T2 X2.1 ϑ> X2.2 −42−8200vec064 £ 75 pF/m ; à partir de 2,5 mm £ 100 pF/m ; Utiliser des câbles moteur de faible capacité ! (brin/brin jusqu’à 1,5 mm brin/blindage £...
  • Seite 184 Installation électrique Raccordement moteur/résistance externe Sections de câbles U, V, W, PE Type Type E82EV302K2C E82EV302K4C E82EV402K2C E82EV402K4C E82EV552K2C E82EV552K4C E82EV752K2C E82EV752K4C E82EV113K4C Danger ! Après le raccordement d’une sonde thermique PTC ou d’un contact thermique, les bornes de commande ne possèdent plus qu’un isolement de base (espace interborne simple).
  • Seite 185: Raccordement Sortie Relais

    Installation électrique Raccordement sortie relais −43−8200vec061 Fonction Position relais Message Spécifications techniques commutée (réglage Lenze) X1.2/K11 Sortie relais (contact à Ouvert TRIP ouverture) 250 V/3 A CA X1.2/K12 Contact central relais 24 V/2 A CC ... 240 V/0,16 A CC X1.2/K14...
  • Seite 186: Raccordement Sortie Relais Ksr Pour "Arrêt Sécurisé

    Installation électrique Raccordement sortie relais K pour "Arrêt sécurisé" (uniquement actif avec la variante E82EVxxxK4Cx 4x)−44− La variante x 4 des variateurs de vitesse intègre la fonction de sécurité "Arrêt sécurisé" qui englobe la protection contre un démarrage incontrôlé, selon les exigences des normes EN 954−1 Catégorie de commande 3"...
  • Seite 187 Installation électrique Raccordement sortie relais K pour "Arrêt sécurisé" +24V X3.1 X3.1 34 33 K32 K31 + 5 V 8200 vector IGBT 8200vec266 Fig. 2 Relais K Affectation des bornes Données Potentiel de référence pour l’entrée Relais de sécurité Tension bobine pour +40°C +24 V (+19,5 ...
  • Seite 188: Module De Fonction (Option)

    Module de fonction (option) Montage Instructions importantes En version de base, les variateurs ne sont pas dotés de borniers de commande. Pour équiper le variateur de borniers de commande, différents modules de fonction E/S peuvent être enfichés sur l’interface FIF. Déclipser le module de fonction uniquement si le démontage s’impose (exemple : échange du variateur).
  • Seite 189 Module de fonction (option) Montage Montage des modules de fonction version "PT"  ‚ −46− 8200vec372 Monter également le dispositif de maintien afin d’éviter que le module ne soit retiré en même temps que les borniers. 1. Positionner le dispositif de maintien 4 dans l’encoche. 2.
  • Seite 190: Démontage

    Module de fonction (option) Démontage Démontage des modules de fonction  ‚ 3 min 8200vec072 1. Couper le variateur du réseau et attendre 3 minutes au minimum ! 2. Saisir le connecteur à broches à l’aide d’une pince et tirer 0. Le connecteur à broches et le module de fonction sont démontés simultanément.
  • Seite 191 Module de fonction (option) Démontage Démontage des modules de fonction version "PT"  ‚ ƒ 8200vec372 Après coupure réseau, il faut retirer le dispositif de maintien sur les modules de fonction version "PT" avant de procéder au démontage. 1. Positionner le tournevis entre le dispositif de maintien et le module de fonction 0. Déclipser le dispositif de maintien vers la droite.
  • Seite 192: Module De Communication (Option)

    Module de communication (option) Montage/démontage  ‚ −47− 8200vec073 Pont permettant de sélectionner l’alimentation   Alimentation externe (état à la livraison) ‚ Alimentation via source de tension interne Enficher le module de commutation dans l’interface AIF ou le retirer. (Cette opération peut s’effectuer pendant le fonctionnement.) Combinaisons possibles Module de communication sur AIF...
  • Seite 193: Mise En Service

    Mise en service Avant la première mise en service Remarque importante ! Respecter l’ordre des opérations ! En cas de problèmes lors de la mise en service, consulter le chapitre "Détection et élimination des défauts". Afin d’éviter des dommages corporels et matériels, vérifier ..
  • Seite 194: Sélection Du Mode De Fonctionnement Adapté

    Mise en service Sélection du mode de fonctionnement adapté Le tableau ci−après vous permet de sélectionner le mode de fonctionnement approprié pour votre application standard. Vous pouvez choisir le fonctionnement en U/f, le contrôle vectoriel ou la régulation de couple sans capteur. Le fonctionnement en U/f est le mode de fonctionnement classique pour les applications standard.
  • Seite 195 Mise en service Sélection du mode de fonctionnement adapté Applications Mode de fonctionnement Réglage sous C0014 Entraînements individuels Recommandation Au choix Avec variations de charge fréquentes Avec démarrage dans des conditions sévères Avec régulation de vitesse (bouclage de vitesse) Avec dynamique élevée (exemple : entraînements de positionnement et d’approche) −...
  • Seite 196: Paramétrage Par Clavier De Commande E82Zbc

    Mise en service Paramétrage par clavier de commande E82ZBC Description Le clavier est disponible en option. Une description détaillée du clavier de commande est contenue dans les instructions de mise en service comprises dans l’équipement livré. Enficher le clavier Le clavier peut être enfiché sur et retiré de l’interface AIF pendant le fonctionnement. Lorsque le clavier est mis sous tension, un auto−test est effectué.
  • Seite 197 Graphique en barres Valeur définie en C0004 en % Plage d’affichage : − 180 % ... + 180 % (chaque division = 20 %) (réglage Lenze : coefficient d’utilisation de l’appareil) Barre de fonction 1 Fonction Signification Explication Impossible avec protection par mot de passe activée Entrée de consigne via...
  • Seite 198 Mise en service Paramétrage par clavier de commande E82ZBC Barre de fonction 2 Fonction Signification Explication Sélectionner du jeu de paramètres 1 ... 4 à modifier Exemple : PS L’activation des jeux de paramètres est possible uniquement via signaux numériques (configuration sous C0410).
  • Seite 199 Remarque de touches Enficher le clavier. La fonction est activée. Le premier code du menu utilisateur est affiché (C0517/1, réglage Lenze : C0050 = xx.xx fréquence de sortie).  Le cas échéant, passer au Passage à la barre de fonction 2 menu "ALL".
  • Seite 200 Mise en service Paramétrage par clavier de commande E82ZBC Structure du menu Tous les paramètres permettant de configurer ou de surveiller l’entraînement sont contenus dans des "codes". Ces codes sont numérotés et signalés par un "C" dans la documentation. Dans certains codes, les paramètres sont enregistrés sous forme de sous−codes numérotés, afin de rendre le paramétrage transparent (ex.
  • Seite 201 à l’aide du clavier, des configurations d’un variateur vers l’autre ou de rétablir l’état à la livraison en programmant le réglage Lenze (si, par exemple, pendant le paramétrage vous ne savez plus où vous en êtes et que vous souhaitez recommencer vos réglage).
  • Seite 202 Mise en service Paramétrage par clavier de commande E82ZBC Œ Œ 0050 0050   s u e r AL L ~5 s … … Œ 0050 ‚ Œ Œ 0XXX 000X ‚ ‚ C000x C517/1 user Œ Œ 0XYZ 0XYZ C000x+1 ‚...
  • Seite 203: Paramétrage Par Clavier E82Zbc − Fonctionnement En U/F Linéaire

    Adapter la configuration des bornes E1 à E4 au Œ 0007 ‚ câblage (C0007). Réglage Lenze : −0−, c’est−à−dire E1: JOG1/3 sélection de consignes fixes E2 : JOG2/3 E3 : freinage courant continu FreinCC E4 : sens horaire/antihoraire CW/CCW (H/AH) Régler la fréquence de sortie mini (C0010).
  • Seite 204 Réglage Lenze : 50.00 Hz Régler l’accroissement U (C0016). Le réglage Lenze est adapté à toutes les applications courantes. Réglage Lenze : en fonction du type de variateur. C0015 Pour procéder à d’autres modifications, passer Ex. : activer les fréquences fixes...
  • Seite 205: Paramétrage Par Clavier E82Zbc − Contrôle Vectoriel

    Adapter la configuration des bornes au câblage Œ 0007 ‚ (C0007). Réglage Lenze : 0, c’est−à−dire E1 : JOG1/3 sélection consignes fixes E2 : JOG2/3 E3 : freinage courant continu FreinCC E4 : sens horaire/antihoraire CW/CCW (H/AH) Régler la fréquence de sortie mini (C0010).
  • Seite 206 ‚ réglage de la consigne analogique (C0034). DIP sur le module E/S standard (voir instructions de montage E/S Réglage Lenze : 0, (0 ... 5 V/0 ... 10 V/0 ... standard). 20 mA) Entrer les données moteur. Voir plaque signalétique moteur.
  • Seite 207: Optimiser Le Contrôle Vectoriel

    Mise en service Paramétrage par clavier E82ZBC − contrôle vectoriel Ordre des opérations Remarque Régler d’autres paramètres si nécessaire. Exemples : activation des fréquences fixes (JOG) (C0037, C0038, C0039) ou de la surveillance de température moteur (C0119) Après avoir réglé tous les paramètres : Entrer la consigne.
  • Seite 208: Paramétrage Par Clavier De Commande Xt Emz9371Bc

    Mise en service Paramétrage par clavier de commande XT EMZ9371BC Description Le clavier est disponible en option. Vous trouverez une description complète du clavier dans les instructions de mise en service fournies avec le clavier. Enficher le clavier Vous pouvez également enficher et retirer le clavier sur l’interface AIF pendant le fonctionnement.
  • Seite 209 Mise en service Paramétrage par clavier de commande XT EMZ9371BC Prise en compte des paramètres Affichage Signification Explication Le paramètre est immédiatement pris en compte. L’appareil de base fonctionne immédiatement avec le nouveau paramètre. L’appareil de base fonctionne avec le nouveau SHPRG Le paramètre doit être validé...
  • Seite 210: Touches De Fonction

    Mise en service Paramétrage par clavier de commande XT EMZ9371BC Touches de fonction Description voir tableau suivant Touches de fonction Nota ! Combinaison de touches avec T : Appuyer sur T, puis sans relâcher, appuyer sur la touche indiquée. Touche Fonction −49−...
  • Seite 211 Mise en service Paramétrage par clavier de commande XT EMZ9371BC Modification et enregistrement des paramètres Tous les paramètres permettant de paramétrer ou de surveiller le variateur sont sauvegardés dans les codes. Commençant par "C", ces codes sont numérotés. Pour certains codes, les paramètres sont compris dans les "sous−codes" numérotés afin de faciliter le paramétrage (exemple : C0517 Menu utilisateur).
  • Seite 212: Structure Du Menu

    Mise en service Paramétrage par clavier de commande XT EMZ9371BC Action Séquence de Action touches Affichage au niveau fonctionnement Affichage du code avec jeu de paramètres modifié Modifier d’autres paramètres. Reprendre la "boucle" par 1. ou 3. afin de régler d’autres paramètres.
  • Seite 213 Mise en service Paramétrage par clavier de commande XT EMZ9371BC Menu principal Sous−menus Description Description N° Affichage N° Affichage Param managm Gestion des jeux de paramètres Load/Store Transfert du jeu de paramètres au réglage usine, retour à l’état à la livraison Copy PAR1 −>2 Copier le jeu de paramètres 1 dans le jeu de paramètres 2.
  • Seite 214: Paramétrage Par Clavier Xt Emz9371Bc−Fonctionnement En U/F Linéaire

    (C0034). interrupteurs DIP sur le module E/S standard (voir instructions de Réglage Lenze : 0, (0 ... 5 V/0 ... 10 V/0 ... montage E/S standard). 20 mA) Si besoin est, adapter les consignes fixes JOG.
  • Seite 215: Remarque Importante

    Régler l’accroissement U (C0016). Le réglage Lenze est adapté à mini. toutes les applications courantes. Réglage Lenze : selon le type de l’appareil en fonction C0015 Activer la surveillance de température moteur si Possibilités de réglage : (^ 228) l’entrée PTC ou le contact thermique est raccordé(e) à...
  • Seite 216: Paramétrage Par Clavier Xt Emz9371Bc − Contrôle Vectoriel

    (C0034). interrupteurs DIP sur le module E/S standard (voir instructions de Réglage Lenze : 0, (0 ... 5 V/0 ... 10 V/0 ... montage E/S standard). 20 mA) Si besoin est, adapter les consignes fixes JOG.
  • Seite 217 Réglage Lenze : 5.00 s T i r T i f = temps de décélération souhaité Régler le mode de fonctionnement "contrôle vectoriel" (C0014 = 4). Réglage Lenze : fonctionnement en U/f avec SHPRG Menu 0014 Code courbe linéaire (C0014 = 2)
  • Seite 218 Si une sonde PTC ou un contact thermique a Réglages possibles : (^ 228) été connecté sur la borne X2.2, activer la surveillance de température moteur. Réglage Lenze : surveillance désactivée. Entrer la consigne. Ex. : via potentiomètre sur les bornes 7, 8, 9 Débloquer le variateur.
  • Seite 219 Mise en service Paramétrage par clavier XT EMZ9371BC − contrôle vectoriel Optimiser le contrôle vectoriel Après l’identification des paramètres moteur, le contrôle vectoriel peut être appliqué, en général, sans mesure supplémentaire. L’optimisation du contrôle vectoriel s’impose uniquement pour les cas suivants : −50−...
  • Seite 220: Codes Principaux Pour La Mise En Service

    E/S application Menu utilisateur, avec les réglages Lenze uSEr Désignation Désignation du code Lenze Réglage Lenze (réglage usine à la livraison ou après retour au réglage usine par C0002) à La colonne "IMPORTANT" contient des informations supplémentaires. Choix 99 Valeur mini {unité}...
  • Seite 221 Mise en service Codes principaux pour la mise en service Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0002* Gestion des jeux Prêt PAR1 ... PAR4 : de paramètres jeux de paramètres du variateur −51− PAR1 ... PAR4 comprennent uSEr également les paramètres pour les...
  • Seite 222 Mise en service Codes principaux pour la mise en service Code Réglages possibles IMPORTANT N° Désignation Lenze Choix ð C0002* Transfert de jeux Substituer le jeu de paramètres Clavier de commande PAR1 (+ FPAR1) de paramètres sélectionné et le cas échéant FPAR1...
  • Seite 223 Mise en service Codes principaux pour la mise en service Code Réglages possibles IMPORTANT N° Désignation Lenze Choix ð C0002* Sauvegarder le Il est possible de sauvegarder le PAR1 réglage utilisateur réglage réglage utilisateur des paramètres du utilisateur variateur (exemple : état à la livraison uSEr de votre machine).
  • Seite 224 Mise en service Codes principaux pour la mise en service Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0007 Configuration La modification de C0007 sera fixe des entrées copiée dans le sous−code numériques correspondant de C0410. uSEr Configuration réglée en C0410 déclenche C0007 = 255 !
  • Seite 225 Mise en service Codes principaux pour la mise en service Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0007 m/auto = Commutation mode manuel/automatique (à distance) AH/AR H/AR TRIP−Set JOG1/3 PCTRL1−I−OFF = Suppression de la uSEr AH/AR H/AR +vite −vite composante intégrale régulateur...
  • Seite 226 C0010 agit uniquement sur l’entrée analogique 1. à Plage de réglage de vitesse 1 : 6 C0011 Fréquence de 50.00 7.50 {0.02 Hz} 650.00 pour motoréducteurs Lenze sortie maxi à 87 Hz uSEr Réglage impératif pour fonctionnement avec motoréducteurs Lenze C0012 Temps 5.00...
  • Seite 227 Mise en service Codes principaux pour la mise en service Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0013 Temps de 5.00 0.00 {0.02 s} 1300.00 Concerne : modification de la décélération fréquence C0011 ... 0 Hz uSEr ð pour consigne Consigne supplémentaire...
  • Seite 228 Mise en service Codes principaux pour la mise en service Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0034* Plage consigne Tenir compte de la position des analogique interrupteurs DIP du module de E/S standard fonction ! (X3/8) Tension unipolaire 0 ... 5 V / 0 ... 10 V uSEr −52−...
  • Seite 229 Mise en service Codes principaux pour la mise en service Code Réglages possibles IMPORTANT N° Désignation Lenze Choix à à C0090 Tension {1 V} 230 V pour variateurs 230 V nominale moteur 400 V pour variateurs 400 V Cos ϕ moteur à...
  • Seite 230 Fréquence de sortie (MCTRL1−NOUT) Le menu utilisateur comprend les 2 Mémoire 2 C0034 Plage consigne analogique principaux codes (en réglage Lenze) pour la mise en service du 3 Mémoire 3 C0007 Configuration fixe des signaux d’entrée mode de fonctionnement en U/f − numériques courbe linéaire.
  • Seite 231: Détection Et Élimination Des Défauts

    Détection et élimination des défauts Anomalie de fonctionnement de l’entraînement Anomalie de fonctionnement Cause Solution Le moteur ne tourne pas. Tension du circuit intermédiaire trop faible Vérifier la tension réseau. (la LED rouge clignote (cycle de 0,4 s), affichage clavier : Variateur bloqué.
  • Seite 232 Optimiser le contrôle vectoriel (^ 206) d’entraînement avec contrôle vectoriel ne sont pas satisfaisantes. Réduction du couple dans la Divers Contacter votre centre S.A.V. Lenze. zone en puissance constante Décrochage du moteur en cas de fonctionnement dans la zone en puissance constante EDK82EV113 DE/EN/FR 8.1...
  • Seite 233: Messages De Défaut

    Détection et élimination des défauts Messages de défaut LEDs sur le variateur (affichage d’état) −54− Etat de fonctionnement  ‚ rouge verte ETEINTE ALLUMEE Variateur débloqué ALLUMEE ALLUMEE Mise sous tension et blocage démarrage automatique ETEINTE CLIGNOTE Variateur bloqué lentement ETEINTE CLIGNOTE Identification paramètres moteur achevée...
  • Seite 234 Vérifier la configuration bus système. C0126) l’esclave ne répond pas. Temps de surveillance communication dépassé En fonctionnement avec module sur Contacter votre service Lenze. FIF : défaut interne EDK82EV113 DE/EN/FR 8.1 Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Seite 235 Un signal numérique affecté de la Vérifier le codeur externe. (TRIP−SET) fonction "mise en défaut" (TRIP−Set) a été activé. Défaut interne Contacter votre service Lenze. Identification de Moteur non connecté. Raccorder le moteur. paramètres erronée Défaillance d’une ou de plusieurs Vérifier les câbles moteur.
  • Seite 236 Détection et élimination des défauts Messages de défaut Clavier de Défaut Origine Remède commande Mise à la terre Court−circuit à la masse d’une phase Vérifier le moteur ; vérifier le câble moteur. moteur Courant de charge capacitif du câble Utiliser des câbles moteurs plus courts ou moteur trop élevé...
  • Seite 237 Tous les jeux de paramètres sont Avant de débloquer le variateur, renouveler paramètres via clavier défectueux. impérativement le transfert de données ou erroné charger le réglage Lenze. Transfert via clavier de PAR1 défectueux commande de PAR1 erroné Transfert via clavier de PAR2 défectueux...
  • Seite 238 Détection et élimination des défauts Messages de défaut Clavier de Défaut Origine Remède commande Rupture de fil sur Courant sur entrée analogique Fermer le circuit à l’entrée analogique. < 4 mA pour plage de consigne entrée analogique 1 4 ... 20 mA Rupture de fil sur entrée analogique 2 N°...
  • Seite 239 Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment SERVICE CENTER REPAIRS WE BUY USED EQUIPMENT • FAST SHIPPING AND DELIVERY Experienced engineers and technicians on staff Sell your excess, underutilized, and idle used equipment at our full-service, in-house repair center We also offer credit for buy-backs and trade-ins •...