14
Transmitter Promag 53***-***********2
Terminals
20
+ / –
+
Relay ➁
Designation
Functional
60 V DC/100 mA
values
or
30 V AC/500 mA
Intrinsically
no
safe circuit
U
=
260 V AC
m
I
=
m
Transmitter Promag 53***-***********4
Terminals
20
+
current input ➁
Designation
Functional
active: 4...20 mA
≤ 150 Ω
values
R
i
U
= 24 V DC
out
short-circuit proof
passive: 0/4...20 mA
≤ 150 Ω
R
i
U
= 30 V DC
max
Intrinsically
no
safe circuit
U
=
260 V AC
m
I
=
m
Transmitter Promag 53***-***********5
Terminals
20
+
Satus input ➁
Designation
Functional
3...30 V DC
values
R
= 5 kΩ
i
Intrinsically
no
safe circuit
U
=
260 V AC
m
I
=
m
21
22
23
–
+
–
Current output ➁
0/4...20 mA
< 700 Ω
active: R
L
passive:
max. 30 V DC
no
260 V AC
500 mA
21
22
23
–
+
–
Relay ➁
60 V DC/100 mA
or
30 V AC/500 mA
no
260 V AC
500 mA
21
22
23
–
+
–
current input ➁
active: 4...20 mA
≤ 150 Ω
R
i
U
= 24 V DC
out
short-circuit proof
passive: 0/4...20 mA
≤ 150 Ω
R
i
U
= 30 V DC
max
no
260 V AC
500 mA
Proline Promag 53
24
25
26
+
–
+
Pulse/frequency
Current output
output ➁
HART ➁
f = 2...10000 Hz
active: 0/4...20 mA
active: 24 V DC/
R
L
HART ≥ 250 Ω
25 mA
R
L
passive: 30 V DC/
passive:
250 mA
max. 30 V DC
no
260 V AC
260 V AC
24
25
26
+
–
+
Pulse/frequency
current output
output ➁
HART ➁
f = 2...10000 Hz
active: 0/4...20 mA
active: 24 V DC/
R
L
HART ≥ 250 Ω
25 mA
R
L
passive: 30 V DC/
passive:
250 mA
max. 30 V DC
no
260 V AC
260 V AC
24
25
26
+
–
+
Pulse/frequency
current output
output ➁
HART ➁
f = 2...10000 Hz
active: 0/4...20 mA
active: 24 V DC/
R
L
HART ≥ 250 Ω
25 mA
R
L
passive: 30 V DC/
passive:
250 mA
max. 30 V DC
no
260 V AC
260 V AC
Endress+Hauser
27
–
< 700 Ω
no
27
–
< 700 Ω
no
27
–
< 700 Ω
no