Failure
50
Maintenance: Due to external influences, the instrument function is
limited. The measurement is affected, but the measured value is still
valid. Plan in maintenance for the instrument because a failure is
expected in the near future (e.g. due to buildup).
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
The following table shows the error codes in the status message
"Failure" and gives information on the reason and rectification. Keep in
mind that some information is only valid with four-wire instruments.
Code
Cause
Text mes-
sage
F013
l Sensor does not detect an
echo during operation
no measured
value avail-
l Antenna system contami-
able
nated or defective
F017
l Adjustment not within
specification
Adjustment
span too small
F025
l Index markers are not
continuously rising, for ex-
Error in the
amle unlogical value pairs
linearization
table
F036
l Failed or interrupted soft-
ware update
No operable
software
F040
l Hardware defect
Error in the
electronics
F080
l General software error
F105
l The instrument is still in the
start phase, the measured
Determine
value could not yet be
measured val-
determined
ue
F113
l EMC interferences
Communica-
l Transmission error with the
tion error
external communication
with 4-wire power supply
unit
LEVEL TRANSMITTER 8136 • 4 ... 20 mA/HART - two-wire
Rectification
l Check or correct installa-
tion and/or parameter ad-
justment
l Clean or exchange process
component or antenna
l Change adjustment ac-
cording to the limit values
(difference between min.
and max. ≥ 10 mm)
l Check linearization table
l Delete table/Create new
l Repeat software update
l Check electronics version
l Exchange of the elec-
tronics
l Send instrument for repair
l Exchange of the elec-
tronics
l Send instrument for repair
l Separate operating voltage
briefly
l Wait for the warm-up phase
l Duration depending on the
version and parameter ad-
justment up to approxi-
mately 3 min.
l Remove EMC influences
l Exchange 4-wire power
supply unit or electronics