The display of the first page depends on the controller type setting in the module configu-
ration menu.
The following settings apply to the signal device:
Electrodeless C
controller parameter
page 1
(signal device)
The set point (W) function is used to set the nominal value within the measuring range.
Value range (depending on selected measuring range):
Measuring range Value range
0..2mS
0..20mS
0..200mS
0..2000mS
The switch difference (XSD) function is used to specify the switch hysteresis around the
set point. The stated percentage refers to the nominal value.
Value range: 0.0 % to 30.0 %
The starting time of the corresponding relay can be delayed by the time specified with the
switch delay time on function.
Value range: 0 sec to 240 sec
The switch-off time of the corresponding relay can be delayed by the time specified with
the switch-off delay function.
Value range: 0 sec to 240 sec
The set point difference (LW) function can be used to enter the absolute interval between
switching point 2 and the set point.
Value range (depending on set measuring range):
Measuring range Value range
0..2mS
0..20mS
0..200mS
0..2000mS
The switch difference (X2SD) function can be used to specify a switch hysteresis around
switching point 2. The stated percentage refers to the absolute value of switching point 2.
Value range: 0.0 % to 30.0 %
Through selecting the module selection function one returns to configuration module se-
lection.
Page 2 displays additional parameters on a second page of settings.
The following settings apply to the 2-point PID controller:
Electrodeless C
controller
parameters page 1
(2-point-PID)
417101800_Anhang01_LF_induktiv.doc
Conductivity Measuring Module (electrodeless)
0.000 mS to 2.000 mS
0.00 mS to 20.00 mS
0.0 mS to 200.0 mS
0 mS to 2000 mS
0.000 mS to 2.000 mS
0.00 mS to 20.00 mS
0.0 mS to 200.0 mS
0 mS to 2000mS