Herunterladen Inhalt Inhalt Diese Seite drucken

Combustion Adjustment; Recommended Nozzles - Riello Gulliver RG3 Montage Und Bedienungs Anleitung

Vorschau ausblenden Andere Handbücher für Gulliver RG3:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

4.
WORKING

4.1 COMBUSTION ADJUSTMENT

In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler, adjustment and
testing must be carried out observing the instruction manual of the boiler, including verification of the CO and
CO
concentration in the flue gases, their temperatures and the average temperature of the water in the boiler.
2
To suit the required appliance output, choose the proper nozzle and adjust the pump pressure, the setting of
the combustion head, and the air damper opening in accordance with the following schedule.
The values shown in the table are measured on a CEN boiler (as per EN 267).
They refer to 12.5% CO 2 at sea level and with light oil and room temperature of 20 °C.
Nozzle
GPH
Angle
1.75
60°
2.00
60°
2.25
60°
2.50
60°
3.00
60°
3.50
60°
3.50
60°

4.2 RECOMMENDED NOZZLES

Delavan type W - B ; Danfoss type S - B
Monarch type R
; Steinen type S - Q
For 3.00 - 3.50 GPH nozzles it is advisable to use
full cones.
TO FIT NOZZLE CARRY OUT THE FOLLOW-
ING ACTIONS:
Remove nozzle-holder assembly (1) after loosing
screws (2) and nut (3), remove the small cables
(4) from the control box and the photoresistance
(6). (See fig. 11).
Withdraw the small cables (4) from the elec-
trodes, remove the diffuser disc-holder assembly
(10) from the nozzle-holder assembly (1) after
loosing screw (3, fig. 12, page 7).
Screw the nozzle (11) correctly and tighten
it as shown in fig. 11.
ATTENTION
During the reassembly of the nozzle-holder assem-
bly screw the nut (3) as shown in the figure below.
TIGHTEN WITHOUT MOVING
BACKWARDS TO THE END
1891
Pump
Burner
pressure
output
bar
kg/h ± 4%
12
7.0
12
8.0
12
9.0
12
10.0
12
12.0
12
14.0
14
15.2
D5684
3
Combustion head
adjustment
Set-point
0
1
3
3.5
5
6
6
Fig. 11
6
GB
Air damper
adjustment
Set-point
1.3
2.3
2.6
3.0
3.5
4.4
5.6
S7642

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis