Herunterladen Inhalt Inhalt Diese Seite drucken

Effekta USV Handbuch Seite 95

Inhaltsverzeichnis

Werbung

USV THOR T2-Serie
Registeransicht: Setting (3) -> Parallel Amount
120KVA
ID:01
Command
Parallel ID
UPS Output
Float Volt Revise
Parallel Amount
Internal Module amount
Registeransicht: Setting (3) -> Internal Module amount
120KVA
ID:01
Command
Parallel ID
UPS Output
Float Volt Revise
Parallel Amount
Internal Module amount
Registeransicht: Setting (4) -> Single Battery Volt.
120KVA
ID:01
Command
Single Battery Volt.
Battery Number
Battery Group
Single Battery Capa.
Boost Upper Limit Volt.
Float Base Volt.
Battery Protect Volt.
Boost Charge
Boost Last Time
Max Charge Current
Serie T2
On-Line
Setting
Record
Parallel Amount
03
Ensure
Cancel
On-Line
Setting
Record
Internal Module amount
05
Ensure
Cancel
On-Line
Setting
Record
Single Battery Volt.
12V
Ensure
Cancel
Gerätebetrieb und Bedienung
23-05-2012
08:00
Version
01
Enable
0.001
04
05
Back
Next
23-05-2012
08:00
Version
01
Enable
0.001
04
05
Back
Next
23-05-2012
08:00
Version
12V
20
1
100Ah
2.31
2.25
1.70
Enable
Back
231 Min
25A
Next
Mit diesem Parameter „Parallele
Anzahl" wird definiert, wie viele
Anlagen innerhalb dieses
Parallel-Systems parallelge-
schaltet sind.
Hier im Beispiel seien es 3
Anlagen.
Es können maximal 4 Anlagen
parallelgeschaltet sein.
Mit diesem Parameter „Einge-
baute Modul-Anzahl" wird
definiert, wie viele USV-Module
sich in dieser Anlage befinden.
Hier im Beispiel sind 5 USV-
Module eingetragen.
Hinweis: Die Module sind
innerhalb der Anlage automa-
tisch von unten nach oben
durchnummeriert.
Auf der vierten Seite der Einstel-
lung sind die Werte und Para-
meter zur Akkubank und Lade-
einheit zusammengefasst.
Mit der „Nominalspannung" wird
die Spannung des einzelnen
Akkumulators definiert.
Hier in unserem Beispiel hat der
einzelnen Akkumulator eine
Nominalspannung von 12 V.