Connecting the data communication cable to the AC
Combiner
General
If the AC Combiner is supplied without prefabricated data communication cables, the in-
staller is personally responsible for selecting and purchasing the appropriate cables.
Minimum requirement for cables
-
-
For installation outdoors:
-
-
Connecting the
1
data communica-
2
tion cables to the
AC Combiner
Open the
3
4
Min. CAT5
External diameter of cable 6 mm - max. 13 mm
The cables must be suitable for outdoor use.
The cables must be resistant to UV.
Further information on data communication cables:
http://www.fronius.com/QR-link/4204101938
Guidelines for DATCOM cabling
AC Combiner
Remove the metal covers
1
2
1
1
3
4
3
5
6
5
Loosen the M20 metric screw joints
Insert the data communication cables for external connection through the metric screw
joints from below into the AC Combiner
IMPORTANT! In the AC Combiner , the cable shields for the data communication ca-
bles must not be connected with earth potential.