Herunterladen Inhalt Inhalt Diese Seite drucken

Victron energy 12/30 (1) Anleitung Seite 10

Blue power ip22 charger
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 41
Seven step charge sequence for lead-acid batteries:
1.
BULK
Charges the battery with maximum current until absorption
voltage is reached. The battery will then be about 80%
charged and is ready for use.
2.
ABS - Absorption
Charges the battery at constant voltage and with
decreasing current until it is fully charged.
See table above for absorption voltage at room
temperature.
Adaptive battery management:
The absorption time is short (minimum 30 minutes) if the
battery was (nearly) fully charged and increases to 8 hours
in case of a deeply discharged battery.
3.
RECONDITION
Optional reconditioning for deeply discharged lead-acid
batteries.
Reconditioning is applicable to the charge algorithms
NORMAL and HIGH and can be selected by pressing the
MODE button one more time after selection of the required
algorithm.
When in RECONDITION mode the battery will be charged
with low current up to a higher voltage at the end of the
absorption phase.
The RECONDITION LED will be on during charging, and
will blink during the reconditioning period.
During reconditioning the maximum current is equal to 8%
of the nominal current until the maximum voltage is
reached. Reconditioning is terminated after one hour or
when the maximum voltage is reached, whichever comes
first. See table.
Example:
For a 12/30 charger: the recondition current is
30 x 0,08 = 2,4A.
6

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

24/15 (3)24/15 (1)12/30 (3)

Inhaltsverzeichnis