AIR PURGING

Air and moisture that remain in the refrigerant system, e.g. after installation, can cause undesirable effects
or damage as indicated below:
Pressure in the system rises.
Operating current rises.
Cooling or heating efficiency drops.
Moisture in the refrigerant circuit may freeze and block capillary tubing.
Water may lead to corrosion of parts in the refrigeration system.
Damage of the compressor.
Therefore, the indoor unit and tubing between the indoor and outdoor unit must always be leak tested and
evacuated with aid of a vacuum pump to remove any noncondensables and moisture from the system.
Air purging with vacuum pump
Preparation
Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have
been properly connected and all wiring for the test run has been completed. Remove the service valve
caps from both the gas and the liquid side valves on the outdoor unit.
Note that both the liquid and the gas side service valves on the outdoor unit must kept closed at this
stage.
Pipe length and refrigerant amount:
Connective pipe lenght
Less than 5m
5~10m
5~10m
When relocate the unit to another place, perform evacuation using vacuum pump.
Make sure the refrigerant added into the air conditioner is in liquid form in any case.
Only use the type of refrigerant as stated on the rating label.

Caution in handling the packed valve

Open the valve stem until it hits against the stopper. Do not try to open it further.
Securely tighten the valve stem cap with a spanner or the like.
For valve stem cap tightening torque (See tightening torque table 1 in previous page).
Outdoor unit
A
B
Packed valve
on outdoor unit
see fig. 25
Air purging method
Use vacuum pump.
Use vacuum pump.
Use vacuum pump.
Indoor unit
C
D
Half union
Fig. 22
Additional amount above rating label amount of
refrigerant to be charged
------------------------
Liquid side pipe diameter:
ø 6.35 (mm)
(Pipe length-5)x30g
Liquid side pipe diameter:
ø 9.53 (mm)
(Pipe length-5)x30g
Valve body
Valve stem
Fig. 23
Flare nut
Stopper
Cap
4