Technical datas
The power supplies and electrical control equipment are to be operated exclusively with the components authorised by
the manufacturer.
Electrical properties
Primary energy supply
Operating voltage supply:
System voltage:
Power consumption:
Power consumption (Standby):
Monitoring:
Terminal:
Fuse:
Secondary energy supply
Batteries:
Battery type:
Emergency power:
Charging time:
Terminal:
Monitoring:
Fuse:
Output
Voltage:
Ripple:
Power (nominal):
Power (temporary):
Opening / closing sequence:
Pause time during change of
polarity:
Timing in accordance with
prEN 12 101-9:
Automatic activation:
Cable monitoring function:
Terminal:
Drives / Magnetic clamps:
Fuse:
Call point output
Voltage:
Power:
Terminal:
max. Pieces:
Emergency power:
Automatic alarm unit output
Voltage:
Power:
Terminal:
Cable monitoring function:
max. Pieces:
Emergency power:
* pre-adjustment
07/24999513
SHE control panel TRZ Plus 2A and TRZ Plus Comfort;
Compact control panel 2A and Compact control panel 2A/M
230 V AC / 50 Hz, (±10 %), separately fused
27 V DC (nominal) (-25 % / +10 %)
max. 75 W
TRZ Plus 2A: < 5 W
TRZ Plus Comfort: < 5 W
TRZ Plus 2A/UP: < 5 W
yes, Software monitoring
screw terminals max. 2.5 mm²
F1 main: Print-fuse 1.25 A/T TE5 250 V
2 x 14 V, 1.2 Ah, VdS
lead gel battery
72 h
20 h for emergency power
max 1.5 mm², 4.8 blade terminal with insulating bush 200 mm long
yes, cyclical, total discharge prot.
F3 battery, FKS 5A
Drives/Magnetic clamps: 27 V DC (nominal), (-25 % / +10 %)
Drives/Magnetic clamps: <1 %
Drives: 2 amp 30 % ED
Magnetic clamps: 0.7 amp 100 % ED
2.6 amp (≤600 ms)
reversal of voltage polarity
200 ms
yes, alteration of direction of travel every 2 min
Open/Close direction: after 3 min* (at ventilation operation)
Open direction: after 30 min (at SHE operation)
via third monitoring circuit in con junction with monitoring diodes
max. 2.5 mm², screw terminal
in accordance with max. current draw of the drives / magnetic clamps
FKS 5A
24 V nominal
max. 60 mA, 100 % ED
max. 1 mm², spring terminal
10
yes
24 V nominal
max. 150 mA, 100 % ED
max. 1 mm², spring terminal
End resisted 10k or active end module
10
yes
71