Herunterladen Inhalt Inhalt Diese Seite drucken

DigiTrace HTC-915 Installationshandbuch Seite 4

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

APPENDIx - CONFIgURATION ShEET
915 hTC Configuration - Firmware versions V1.Ox
BASIC MODE MENU
(All other parameters are set as shown in the Advanced Mode Sub-Menus)
CONFIgURATION MODE MENU
Parameter
Factory
Control Setpoint
68°F (20°C)
Lo TS 1
14°F (–10°C)
Lo Load
1.0 A
Switch Control Mode
Deadband
Circuit Breaker
*n/a (30. A)
Temp. Units
°C
Feature Mode
Basic
ADVANCED MODE MENUS
CONFIgURATION MODE MENU
Parameter
Factory
Control Setpoint
68°F (20°C)
Lo TS 1
14°F (–10°C)
Lo Load
1.0 A
Switch Control Mode
Deadband
Circuit Breaker
*n/a (30. A)
Temp. Units
°C
Feature Mode
Basic
TS ALARMS CONFIgURATION SUB MENU
Parameter
Factory
TS 1 Fail
Enable
Lo TS 1
Enable
Lo TS 1
14°F (–10°C)
Hi TS 1
Disable
*n/a
Hi TS 1
212°F (100.0°C)
TS 2 Fail
Disable
Lo TS 2
Disable
*n/a
Lo TS 2
14°F (–10°C)
Hi TS 2
Disable
*n/a
Lo TS 2
212°F (100.0°C)
Lo TS Filter
0 min
Hi TS Filter
*n/a (0 min)
Latch TS Alarms
Yes
CTL TS Fail
Enable
Parameter
Lo Load
Lo Load
Lo Load Filter
Hi Load
User
Hi Load
Hi Load Filter
Hi GFI
Hi GFI
Hi GFI Filter
GFI Trip
GFI Trip
Lo Volt
Lo Volt
Lo Volt Filter
Hi Volt
User
Hi Volt
Hi Volt Filter
Lo Resist
Lo Resist
Lo Resist Filter
Hi Resist
Hi Resist
Hi Resist Filter
Nominal Resist
Overcurrent Trip
Switch fail
User
HTC Reset
C.B. Limiting
Output Limiting
Switch Limiting
Contactor Count
Contactor Count
EEROM data Fail
Parameter
Tag
Switch Control Mode
Deadband
Prop Band
Cycle time
Switch Rating
Circuit Breaker
Outlet Limit Mode
Max. Power
OThER ALARMS CONFIgURATION SUB MENU
Factory
User
Enable
1.0 A
0 sec
Disable
*n/a (30.0 A)
*n/a (0 sec)
Enable
20 mA
0 sec
Enable
30 mA
Enable
90 V
0 sec
Disable
*n/a (270 V)
*n/a (0 sec)
Disable
*n/a (50%)
*n/a (0 sec)
Disable
*n/a (50%)
*n/a (0 sec)
*n/a (6.00 Ω)
*n/a (Enable)
Enable
Disable
*n/a (Disable)
*n/a (Disable)
*n/a (Disable)
Enable
200,000
Enable
POINT SETUP SUB-MENU
Factory
User
TAG-(factory ID)
Deadband
5°F (3°C)
*n/a (4°F (2°C))
*n/a (10 min)
*n/a (30.0 A)
*n/a (30.0 A)
Disable
*n/a (7200 W)
Max. Current
*n/a (30.0 A)
3 Ph Pwr Calc
No
TS Fail Mode
Off
TS CTL Mode
TS1-Fail Off
TS 1 Hi Limit
*n/a Disable
TS 2 Hi Limit
*n/a Disable
Volt Turns Ratio
1.00 to 1
Current Turns Ratio
1.00 to 1
Auto-cycle
Enable
Auto-cycle Interval
8
Auto-cycle Units
Hours
Override Source
Remote
Load Shedding
*n/a
Limiter Cutout Temp.
*n/a (50.0°C)
Limiter Current Sense
*n/a (Disable)
MISC. SETUP SUB-MENU
Parameter
Factory
Temp. Units
°C
Version
V1.0X.XX
Limiter version
*n/a (V1.0X.XX)
Ext. Input
Not used
Flash Alarm Output
Yes
Alarm output
N.C.
Language
English
Passcode
0
Scroll Delay
0.15 secs
Load Defaults
(See user manual)
Limiter Installed
No
COMMUNICATION SETUP SUB-MENU
Parameter
Factory
Protocol
Modbus RTU
Modbus Addr
*n/a (1)
Modbus Sub Addr
*n/a (0)
Baud Rate
Auto
Parity
*n/a (None)
Tx Deley
0.06 secs
* n/a: Parameter may only appear if certain features are enabled. Values shown
in brackets are the Factory defaults if the settings are enabled.
This information defines the default 915 Series Control Module configuration
as set by the Factory for firmware V1.0X. These settings are subject to change
without notice.
It is the user's responsibility to verify that all configuration parameters are
chosen appropriately for the intended application.
User
n/a
User

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis