Fault detection and elimination
Fault
Cause
Motor not connected
identification
Fault in motor
l
phase
(only generated if
l
C0597 = 1)
phase
(only generated if
C0597 = 2)
Mains voltage too low
undervoltage
d
lt
DC-bus voltage too low
400 V controller connected to
240 V mains
Short-circuit
Short-circuit
Excessive capacitive charging
current of the motor cable
Earth fault
a t au t
Grounded motor phase
Excessive capacitive charging
current of the motor cable
Overload inverter
Acceleration time too short
during acceleration
(C0012)
or short circuit
or short circuit
Defective motor cable
Interturn fault in the motor
Controller overload
Deceleration time set too short
during deceleration
(C0013)
EDK82EV222 DE/EN/FR 6.0
Failure of one/several motor
phase(s)
Motor current too low
Fault messages
Remedy
Connect motor
Check motor cables,
l
Check V
boost
l
min
Connect motor to corresponding
l
power or adapt the motor under
power or adapt the motor under
C0599.
Check mains voltage
Check supply module
Connect controller to the appropriate
mains voltage
Find reason for short-circuit;
l
check motor cable
Check brake resistor
l
Use shorter motor cables with lower
charging current
Check motor, check motor cable
Use shorter motor cables with lower
charging current
For testing purposes the earth fault
detection can be deactivated
Increase acceleration time
l
Check drive selection
l
Check wiring
Check motor
Increase deceleration time
l
Check rating of external brake
l
resistor
?
61