AS-Interface installation

10.
as-inTerface insTallaTiOn
10.1. as-interface connection
AS-Interface (Actuator Sensor Interface) is a field bus system which is used primarily for networking binary sensors
and actuators (slaves) with a higher-level control (master).
Bus line
Unshielded two-wire line (AS-Interface line as AS-Interface cable harness) along which both information (data) and
energy (supply voltage for the actuators and sensors) are transmitted.
network topology
Freely selectable within wide limits, i.e. star, tree and line networks are possible. Further details describe the AS-
Interface specification (A/B slave model conforms to the version 3.0 specification).
10.2. Technical data for as-interface pcBs
Supply:
via AS-Interface (29,5 V – 31,6 V)
Outputs:
1 valve Y1, max. 1 W, power reduction after approx. 100 ms
with integrated Watch Dog function
Certification:
Licence no. 77601 according to version 3.0
10.3. programming data
I/O configuration
ID code
Extended ID code 1
Extended ID code 2
Profile
Table 6:

Programming data

Bit configuration
data bit
d3
0 Top not reached
Input
1 Top reached
Output
parameter bit
p3
Output
not used
Table 7:
Bit configuration
aS-interface
31 slaves
B hex (1 input, 2 outputs)
F hex
F hex
F hex
S-B.F.F
d2
d1
0 Bot not reached
1 Bot reached
not used
p2
p1
not used
not used
aS-interface
62 slaves
A hex
7 hex
E hex
S-B.A.E
d0
0 Pilot valve
OFF
1 Pilot valve
ON
p0
"0" START teach function
"1" STOP teach function