4 CONFIGURATION
4.2.4 »EXT.MEM» Option
Generation of a volume previously entered into the memory (7 in total) from a remote
position by using the binary data inputs (See § 4.2.2.). The following example describes
the various methods of connection.
Batch controller 8035
Fig. 6 Connection example
The selection of a volume from the memory (1 to 7) is carried out by encoding the binary
data at inputs IN1,IN2 and IN3. The following table shows the logic value at each input to
provide each of the desired seven quantities:
Volume
V1
Input IN1
1
Input IN2
0
Input IN3
0
1: Input enabled (switch closed)
0: Input disabled (switch open)
Input IN4: Start / Pause function (from a push button, for example).
Output OUT: Transistor output (open collector)
Provides Batch controller status information. For example, it can be used to feed an
indicator lamp.
The following status can be indicated:
Lamp off
Lamp on
Slow flashing (1 Hz)
Rapid flashing (3.5 Hz)
1 2 3 4 5 6 7 8 9 10 11
V2
V3
V4
0
1
0
1
1
0
0
0
1
BATCH CONTROLLER 8035
+
-
Supply
12..30Vdc
V5
V6
V7
1
0
1
0
1
1
1
1
1
No dosing in progress
Dosing in progress
Pause in dosing operation
Alarm (problem during dosing operation)
E-16-
Volume selection
Start/stop
LED