Herunterladen Inhalt Inhalt Diese Seite drucken

Status Diagnosis And Troubleshooting; Safety - Fronius String Control 250/25 DCD DF Bedienungsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Status diagnosis and troubleshooting

Safety

Status diagno-
90x
sis and trou-
Service codes of the Fronius String Control 250/25 logged by the Datalog-
bleshooting
ger or sent, depending on the settings
x ... identifies the measuring channel
Cause:
Remedy:
Missing logging data during the day
Cause:
Remedy:
WARNING! An electrical shock can be fatal. Danger from DC
voltage from solar modules.
-
Make sure that the input and output sides in front of the
device are not charged before making any connections or
settings.
-
Any and all connections and settings should only be carried
out by qualified electricians.
-
Follow the safety rules in these operating instructions.
Unacceptable deviation of a measuring channel from
the set value
x = 1 ...Measuring Channel 1
x = 2 ... Measuring Channel 2
x = 3 ... Measuring Channel 3
x = 4 ... Measuring Channel 4
x = 5 ... Measuring Channel 5
Check string fuses, check solar module strings, check
Fronius Solar.access settings
Solar Net is open (the 'Connection' LED on the Data-
logger lights up red)
-
Set jumper to manual restoration of the energy
supply
-
Check wires, connections and the supply:
the error can be found after the first Fronius
String Control 250/25 in the OUT direction for
which the 'X' LED (1) lights red or there is no
power supply
37
(1)

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis