4 COMMISSIONING
Fitting Factor-K (see Fig. 4.4 )
The fitting factor (K) adjusts the pulses generated by the paddle wheel to the electronic
system. The fitting factor indicates how many pulses the paddle wheel emits per volume
flow. The volume unit for the flow rate is determined by the fitting factor and does not
therefore have to be given in addition. Any unit can be used (ml, l, m
(K-factor value: refer to the instruction manual type S030 according to fittings used).
Time Unit (see Fig. 4.3)
The time unit is selected from hours (h), minutes (m) and seconds (s).
The time unit is continuously displayed while in standard mode.
h m
120 . 00
Fig. 4.3 Selecting the time unit
The Lower Range Value (4 mA)
The lower range value determines which flow rate value is allocated to the 4mA output
signal. Its unit is determined by the previously set data (fitting factor and time unit).
The Upper Range Value (20 mA)
The upper range value determines which flow value is allocated to the 20 mA output signal.
Its unit is the same as the lower range value. The upper range value must always be
greater than the lower range value.
The control unit can be removed from the 8023 flow rate transmitter, e.g. after programming
completion, without affecting the set process. The housing cover must then be placed back
on the device and screwed in place.
The programmed values are stored in the flow rate transmitter.
Flow Rate Transmitter Settings on Delivery
Multiplier:
Fitting factor (K):
Time unit:
s
x1
46,6 (Pulse/l)
minutes (m)
E-18-
FLOW SENSOR TYPE 8030
Lower range value (4 mA):
Upper range value (20 mA):
3
, gal, etc.).
0.00
180.0
8030