4. Electrical work

4.8. Electrical characteristics

Model
PLFY-P20VBM-E
PLFY-P25VBM-E
PLFY-P32VBM-E
PLFY-P40VBM-E
PLFY-P50VBM-E
PLFY-P63VBM-E
PLFY-P80VBM-E
PLFY-P100VBM-E
PLFY-P125VBM-E
4.9. How to set the fixed up/down air direction (Only
for wired remote controller)
• For PLFY-BM, only the particular outlet can be fixed to certain direction with
the procedures below. Once fixed, only the set outlet is fixed every time air
conditioner is turned on. (Other outlets follow UP/DOWN air direction setting of
the remote controller.)
■ Explanation of word
• "Address No. of indoor unit" is the number given to each air conditioner.
• "Outlet No." is the number given to each outlet of air conditioner.
(Refer to the right.)
• "Up/Down air direction" is the direction (angle) to fix.
Manual vane angle
Main
Main menu
Maintenance
Initial setting
Service
Main display:
Cursor
Page
F1
F2
F3
F4
Maintenance menu
Auto descending panel
Manual vane angle
Main menu:
Cursor
F1
F2
F3
F4
Power supply
Volts/ Hz
Range +- 10%
Max.: 264V
220-240V / 50Hz
Min.: 198V
Select "Maintenance" from the Main
menu, and press the [SELECT]
button.
Select "Manual vane angle" with
the [F1] or [F2] button, and press
the [SELECT] button.
Symbols: MCA: Max. Circuit Amps (= 1.25×FLA)
IFM: Indoor Fan Motor
MCA (A)
Output (kW)
0.28
0.05
0.28
0.05
0.28
0.05
0.36
0.05
0.36
0.05
0.45
0.05
0.64
0.05
1.25
0.12
1.34
0.12
Horizontal airflow
Remote controller setting
The airflow direction of
this outlet is controlled by
the airflow direction setting of
remote controller.
Outlet No.3
Outlet No.2
Note: "0" indicates all outlets.
Manual vane angle
M-NET address
Identify unit Check button
Input display:
Cur.
Address
Check
F1
F2
F3
F4
FLA: Full Load Amps
Output: Fan motor rated output
IFM
FLA (A)
0.22
0.22
0.22
0.29
0.29
0.36
0.51
1.00
1.07
Downward
Fixed setting
The airflow direction of
this outlet is fixed
in particular direction.
* When it is cold because of direct airflow,
the airflow direction can be fixed
horizontally to avoid direct airflow.
Outlet No.4
MITSUBISHI
ELECTRIC
label
Outlet No.1
Select the "M-NET address" for
the units to whose vanes are to be
fixed, with the [F2] or [F3] button,
and press the [SELECT] button.
Press the [F4] button to confirm the
unit.
The vane of only the target indoor
unit is pointing downward.