Lenze ECS Montageanleitung
Vorschau ausblenden Andere Handbücher für ECS:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

EDKCSDE040
.ROY
Montageanleitung
Mounting Instructions
Instructions de montage
ECS
ECSDExxx
Versorgungsmodul "Durchstoß−Technik"
Power supply module in push−through technique
Module d'alimentation en montage traversant
l

Werbung

Inhaltsverzeichnis
loading

Inhaltszusammenfassung für Lenze ECS

  • Seite 1 EDKCSDE040 .ROY Montageanleitung Mounting Instructions Instructions de montage ECSDExxx Versorgungsmodul "Durchstoß−Technik" Power supply module in push−through technique Module d’alimentation en montage traversant...
  • Seite 3 Lesen Sie zuerst diese Anleitung, bevor Sie mit den Arbeiten beginnen! Beachten Sie die enthaltenen Sicherheitshinweise. Please read these instructions before you start working! Follow the enclosed safety instructions. Veuillez lire attentivement cette documentation avant toute action ! Les consignes de sécurité doivent impérativement être respectées.
  • Seite 4: Lieferumfang

    Lieferumfang Position Beschreibung Anzahl Versorgungsmodul ECSDExxx Beipack mit Befestigungsmaterial Montageanleitung Bohrschablone Hinweis! Das Steckverbinder−Set ECSZE000X0B muss gesondert bezogen werden. 0Abb. 0Tab. 0 Anschlüsse und Schnittstellen ECSDE_002A EDKCSDE040 DE/EN/FR 5.0...
  • Seite 5: Statusanzeigen

    Position Beschreibung Ausführliche Informationen Anschlüsse Externer Bremswiderstand DC−Zwischenkreisspannung LEDs: Anzeige Status und Störung Automatisierungs−Interface (AIF) für Kommunikationsmodul Bedienmodul (Keypad XT) PE−Anschluss AIF nicht belegt Anschluss CAN Systembus (CAN) Schnittstelle für – übergeordnete Steuerung und weitere Module – PC / HMI zur Parametrierung und Diagnose Anschlüsse Niederspannungsversorgung Digitale Eingänge und Ausgänge...
  • Seite 6 4 = 400 V/480 V Technische Ausführung B = Standard V = verlackt Variante Stand Hardware VA oder höher Stand Betriebssoftware (B−SW) 1.2 oder höher Tipp! Informationen und Hilfsmittel rund um die Lenze−Produkte finden Sie im Download−Bereich unter www.lenze.com EDKCSDE040 DE/EN/FR 5.0...
  • Seite 7: Inhaltsverzeichnis

    Allgemeine Sicherheits− und Anwendungshinweise für Lenze−Versorgungsmodule ........
  • Seite 8: Sicherheitshinweise

    Erreichen der angegebenen Produkteigenschaften. – Die in dieser Dokumentation dargestellten verfahrenstechnischen Hinweise und Schaltungsausschnitte sind Vorschläge, deren Übertragbarkeit auf die jeweilige Anwendung überprüft werden muss. Für die Eignung der angegebenen Verfahren und Schaltungsvorschläge übernimmt Lenze Automation GmbH keine Gewähr. EDKCSDE040 DE/EN/FR 5.0...
  • Seite 9 Sicherheitshinweise Allgemeine Sicherheits− und Anwendungshinweise für Lenze−Versorgungsmodule Lenze−Versorgungsmodule und zugehörige Komponenten können ƒ während des Betriebs ˘ ihrer Schutzart entsprechend ˘ spannungsführende Teile haben. Oberflächen können heiß sein. – Bei unzulässigem Entfernen der erforderlichen Abdeckung, bei unsachgemäßem Einsatz, bei falscher Installation oder Bedienung besteht die Gefahr von schweren Personen−...
  • Seite 10 Sicherheitshinweise Allgemeine Sicherheits− und Anwendungshinweise für Lenze−Versorgungsmodule Aufstellung Sie müssen die Versorgungsmodule nach den Vorschriften der zugehörigen Do- kumentation aufstellen und kühlen. Die Umgebungsluft darf den Verschmutzungsgrad 2 nach EN 61800−5−1 nicht überschreiten. Sorgen Sie für sorgfältige Handhabung und vermeiden Sie mechanische Überla- stung.
  • Seite 11 Sicherheitshinweise Allgemeine Sicherheits− und Anwendungshinweise für Lenze−Versorgungsmodule Betrieb Sie müssen Anlagen mit eingebauten Versorgungsmodulen ggf. mit zusätzli- chen Überwachungs− und Schutzeinrichtungen gemäß den jeweils gültigen Si- cherheitsbestimmungen ausrüsten (z. B. Gesetz über technische Arbeitsmittel, Unfallverhütungsvorschriften). Sie dürfen die Versorgungsmodule an Ihre An- wendung anpassen.
  • Seite 12: Restgefahren

    Sicherheitshinweise Restgefahren Restgefahren Personenschutz Überprüfen Sie vor Arbeiten am Versorgungsmodul, ob alle ƒ Leistungsklemmen spannungslos sind, da – nach dem Abschalten der Netzspannung die Leistungsklemmen +UG, −UG, BR0 und BR1 noch mindestens 3 Minuten gefährliche Spannung führen. – bei gestopptem Motor die Leistungsklemmen +UG, −UG, BR0 und BR1 gefährliche Spannung führen.
  • Seite 13 Sicherheitshinweise Restgefahren Beachten Sie die maximal zulässige Netzspannung. Eine höhere Spannung ƒ zerstört das Versorgungsmodul. Der Betrieb ist nicht zulässig ƒ – ohne Verwendung eines Bremswiderstandes. – bei gleichzeitiger Verwendung des internen Bremswiderstandes mit einem externen Bremswiderstand. – bei Parallelschaltung mehrerer Versorgungsmodule. EDKCSDE040 DE/EN/FR 5.0...
  • Seite 14: Sicherheitshinweise Für Die Installation Nach Ul

    Sicherheitshinweise Sicherheitshinweise für die Installation nach UL Sicherheitshinweise für die Installation nach UL Warnings! General markings: Use 60/75 °C or 75 °C copper wire only. ƒ Maximum ambient temperature 55 °C, with reduced output ƒ current. Markings provided for the supply units: Suitable for use on a circuit capable of delivering not more than ƒ...
  • Seite 15: Verwendete Hinweise

    Sicherheitshinweise Verwendete Hinweise Verwendete Hinweise Um auf Gefahren und wichtige Informationen hinzuweisen, werden in dieser Dokumentation folgende Piktogramme und Signalwörter verwendet: Sicherheitshinweise Aufbau der Sicherheitshinweise: Gefahr! (kennzeichnet die Art und die Schwere der Gefahr) Hinweistext (beschreibt die Gefahr und gibt Hinweise, wie sie vermieden werden kann) Piktogramm und Signalwort Bedeutung...
  • Seite 16: Spezielle Sicherheitshinweise Und Anwendungshinweise

    Sicherheitshinweise Verwendete Hinweise Spezielle Sicherheitshinweise und Anwendungshinweise Piktogramm und Signalwort Bedeutung Warnings! Sicherheitshinweis oder Anwendungshinweis für den Betrieb nach UL− oder CSA−Anforderungen. Die Maßnahmen sind erforderlich, um die Anforderun- gen nach UL oder CSA zu erfüllen. Warnings! EDKCSDE040 DE/EN/FR 5.0...
  • Seite 17: Technische Daten

    Technische Daten Allgemeine Daten und Einsatzbedingungen Technische Daten Allgemeine Daten und Einsatzbedingungen Normen und Einsatzbedingungen Konformität Niederspannungsrichtlinie (2006/95/EG) Über die Sicherheit von Niederspannungsausrü- TP TC 004/2011 stung; Eurasische Konformität TR ZU: Technische Regulierung der Zollunion (TR ZU 004/2011) Elektromagnetische Verträglichkeit von techni- TP TC 020/2011 schen Erzeugnissen;...
  • Seite 18 Technische Daten Allgemeine Daten und Einsatzbedingungen Allgemeine elektrische Daten Einhaltung der Anforderungen nach EN 61800−3 Störaussendung Einhaltung der Grenzwertklasse C2 nach EN 61800−3(erreicht mit an- wendungstypischem Summenfilter) Störfestigkeit Anforderungen nach EN 61800−3 Anforderung Norm Schärfegrade EN 61000−4−2 3, d. h. 8 kV bei Luftentladung 6 kV bei Kontaktentla- dung...
  • Seite 19: Bemessungsdaten

    Technische Daten Bemessungsdaten Bemessungsdaten Bemessungsdaten ECSxE012 ECSxE020 ECSxE040 Netzspannung 3 x 200 −10 % ... 3 x 480 +10 % Netz Netzbemessungsspannung 3 x 400 V Netz N Netzfrequenz [Hz] 45 ... 66 Netz Netzbemessungsstrom 15,9 31,3 Netz N maximaler Netzstrom 5 x I für 50 ms / 0 x I für 1,2 s...
  • Seite 20: Externe Bremswiderstände

    Technische Daten Externe Bremswiderstände Externe Bremswiderstände Zuordnung externer Bremswiderstände Versorgungsmodul (Standard−Varianten) Bremswiderstand ECSEE... ECSDE... ECSCE... [kW] ERBM039R120W 0,12 ERBM020R150W 0,15 ERBD047R01K2 1,20 ERBD022R03K0 3,00 ERBS039R01K6 1,64 ERBS020R03K2 3,20 Dauerleistung Bremswiderstände Typ ERBM... Bremswiderstände mit speziell abgestimmter Impulsfähigkeit in IP50−Ausfüh- rung. Bemessungsdaten Bremswiderstand ERBM039R120W...
  • Seite 21 Technische Daten Externe Bremswiderstände Bremswiderstände Typ ERBD... Bremswiderstände mit erhöhter Verlustleistung in IP20−Ausführung (Berühr- schutz nach NEMA 250 Typ 1). Bemessungsdaten Bremswiderstand ERBD047R01K2 ERBD022R03K0 Widerstand [] Dauerleistung 1200 3000 Wärmemenge [kWs] Max. Einschaltzeit Motwendige Erholzeit Betriebsspannung Wärmemenge Q Max. Bremsleistung [kW] Bmax Bmax...
  • Seite 22: Mechanische Installation

    Mechanische Installation Wichtige Hinweise Mechanische Installation Wichtige Hinweise Versorgungsmodule der Reihe ECS verfügen über die Schutzart IP20 und ƒ sind daher nur für den Einbau in Schaltschränken bestimmt. Bei verunreinigter Kühlluft (Staub, Flusen, Fette, aggressive Gase): ƒ – Ausreichende Gegenmaßnahmen treffen, z. B. separate Luftführung, Einbau von Filtern, regelmäßige Reinigung.
  • Seite 23: Montage Mit Thermischer Separierung (Durchstoß−Technik)

    65 % über separarierten Kühler – ca. 35 % im Innenraum des ECS−Moduls Schutzklasse des separierten Kühlers: IP54 ƒ – Die Dichtfläche des ECS−Moduls am Kühlkörper muss vollständig an der Montageplatte aufliegen. – Schrauben für Klemmbügel mit flüssiger Gewindedichtung verkleben. Kühlung des Antriebssystems: ƒ...
  • Seite 24: Montage Mit Thermischer Separierung (Durchstoß−Technik) Abmessungen

    Mechanische Installation Montage mit thermischer Separierung (Durchstoß−Technik) Abmessungen 3.2.1 Abmessungen Hinweis! Montage mit Schirmbefestigung ECSZS000X0B: Einbaufreiraum unterhalb des Moduls > 195 mm ƒ ECSXA007 Abb. 3−1 Abmessungen bei Bauform "Durchstoß−Technik" Z Einbauausschnitt (a1 x b1), ^ 25 Versorgungsmodul Maße [mm] Bau- größe ECSDE012...
  • Seite 25: Abmessungen Einbauausschnitt

    Mechanische Installation Montage mit thermischer Separierung (Durchstoß−Technik) Abmessungen Abmessungen Einbauausschnitt Hinweis! Montage mit Schirmbefestigung ECSZS000X0B: Einbaufreiraum unterhalb des Einbauausschnitts > 220 mm ƒ ECSXA063 Abb. 3−2 Abmessungen Einbauausschnitt Montagefläche Einbauausschnitt für Baugröße 0 Einbauausschnitt für Baugröße 1 Versorgungsmodul Maße [mm] Baugröße ECSDE012 78,5...
  • Seite 26: Montageschritte

    Mechanische Installation Montage mit thermischer Separierung (Durchstoß−Technik) Montageschritte 3.2.2 Montageschritte So montieren Sie das Versorgungsmodul: 1. Befestigungsbohrungen für die Klemmbügel auf Montagefläche vorbereiten. – Dazu Bohrschablone anlegen. 2. Einbauausschnitt vorbereiten. – Die Kanten des Einbauausschnitts und der Befestigungsbohrungen für die Klemmbügel müssen leicht nach innen (zum Versorgungsmodul) gewölbt sein.
  • Seite 27: Elektrische Installation

    Betrieb der Maschine keine vom Antriebssystem verursachten EMV−Probleme auftreten und die EMV−Richtlinie bzw. das EMV−Gesetz erfüllt ist. – Werden in der Nähe der ECS−Module Geräte betrieben, die der CE−Anforderung hinsichtlich der Störfestigkeit EN 61000−6−2 nicht genügen, können diese Geräte durch die ECS−Module elektromagnetisch beeinträchtigt werden.
  • Seite 28 Elektrische Installation EMV−gerechte Installation (Aufbau des CE−typischen Antriebssystems) Aufbau ECS−Module, Funk−Entstörfilter und Netzdrossel großflächig mit geerdeter ƒ Montageplatte verbinden: – Montageplatten mit elektrisch leitender Oberfläche (verzinkt oder rostfreier Stahl) erlauben eine dauerhafte Verbindung. – Lackierte Platten sind nicht geeignet für die EMV−gerechte Installation.
  • Seite 29 Diese wird in der Regel durch Einbau in handelsübliche, geschlossene, metallische und geerdete Schaltschränke oder −kästen erreicht. Erdung Alle metallisch leitfähigen Komponenten (z. B. ECS−Module, ƒ Funk−Entstörfilter, Motorfilter, Netzdrosseln) durch entsprechende Leitungen von einem zentralen Erdungspunkt (PE−Schiene) erden. Die in den Sicherheitsvorschriften definierten Mindestquerschnitte ƒ...
  • Seite 30: Antriebssystem Am Netz

    Elektrische Installation Antriebssystem am Netz Potenzialtrennung Antriebssystem am Netz Diese Informationen gelten für das ECS−Antriebssystem, bestehend aus: Versorgungsmodul ECSxE... ƒ Kondensatormodul ECSxK... (optional) ƒ Achsmodul ECSxS/P/M/A... ƒ Motor ƒ Zubehör ƒ Verdrahtung ƒ 4.2.1 Potenzialtrennung Die integrierte Potenzialtrennung zwischen dem Leistungsteil und dem Steuer- teil ist eine Schutztrennung (verstärkte Isolierung) nach EN 61800−5−1.
  • Seite 31: Netzformen / Netzbedingungen

    Einrichtungen, die den Erdschluss erfassen. das Versorgungsmodul unmittel- bar vom Netz getrennt wird. Hinweis! Netzspannungseinbrüche können Sie vermindern durch ƒ Verringern der maximalen Ladestromgrenze (C0022). Deaktivieren Sie die Ladestrombegrenzung (Laderelais) der ƒ angeschlossenen ECS−Achsmodule mit C0175 = 3. EDKCSDE040 DE/EN/FR 5.0...
  • Seite 32: Betrieb An Öffentlichen Netzen (Einhaltung Der En 61000−3−2)

    Elektrische Installation Antriebssystem am Netz Betrieb an öffentlichen Netzen (Einhaltung der EN 61000−3−2) 4.2.3 Betrieb an öffentlichen Netzen (Einhaltung der EN 61000−3−2) In der Europäischen Norm EN 61000−3−2 sind Grenzwerte zur Begrenzung von Oberschwingungsströmen im Versorgungsnetz festgelegt. Nicht lineare Ver- braucher (z.
  • Seite 33: Leistungsanschlüsse

    Elektrische Installation Leistungsanschlüsse Leistungsanschlüsse Gefahr! Gefährliche elektrische Spannung Der Ableitstrom gegen Erde (PE) ist > 3.5 mA AC bzw. > 10 mA DC. Mögliche Folgen: Tod oder schwere Verletzungen beim Berühren des Gerätes im ƒ Fehlerfall. Schutzmaßnahmen: Die in der EN 61800−5−1 geforderten Maßnahmen umsetzen. Insbesondere: Festinstallation ƒ...
  • Seite 34: Leitungsquerschnitte Und Schraubenanzugsmomente

    Elektrische Installation Leistungsanschlüsse Belegung der Steckerleisten Klemme Funktion Elektrische Daten Anschluss Netz anwendungs− und typabhängig X21/L1 Netzphase L1 0 ... 480 V X21/L2 Netzphase L2 bis 31,3 A ( X21/L3 Netzphase L3 X21/PE Anschluss PE−Leiter Anschluss DC−Zwischenkreisspannung Interner Bremswiderstand, Anschluss 1 anwendungs−...
  • Seite 35: Netzanschluss

    Elektrische Installation Leistungsanschlüsse Netzanschluss 4.3.1 Netzanschluss Wichtige Hinweise Leitungen zwischen Funk−Entstörfilter und Versorgungsmodul möglichst ƒ kurz ausführen. – Auf kurzschlusssichere Verlegung achten! Netzleitungen und ±U −Leitungen dürfen sich nicht berühren. ƒ Bei paralleler Verlegung der Netzleitungen und ±U −Leitungen: ƒ –...
  • Seite 36 Elektrische Installation Leistungsanschlüsse Netzanschluss Verdrahtungsvarianten beim Versorgungsmodul ECSxE ƒ ƒ  ‚ „ ECSXE040 Abb. 4−2 Verdrahtungsvarianten beim Versorgungsmodul ECSxE  Einfache Verdrahtung ‚/„ Verdrahtung mit Netzdrosseln ƒ Verdrahtung mit Funk−Entstörfiltern Versorgungsmodul ECSxE Netzdrossel Funk−Entstörfilter Komponentenverdrahtung Netzleitung EDKCSDE040 DE/EN/FR 5.0...
  • Seite 37 Elektrische Installation Leistungsanschlüsse Netzanschluss Sicherungen Verwenden Sie zum Schutz der Netzleitung folgende Leitungsschutzschalter oder UL−approbierte Schmelzsicherungen (siehe dazu Abb. 4−2 (¶ 36)): Versorgungs- Auslegung nach IEC/EN Auslegung nach UL modul Leitungsschutz- Leitungsquer- UL−Sicherung schalter schnitt ECSxE012 C16 A 25 A ECSxE020 C16 A 25 A...
  • Seite 38: Anschluss An Den Dc−Zwischenkreis (+Ug, −Ug)

    Anschluss an den DC−Zwischenkreis (+U , −U 4.3.2 Anschluss an den DC−Zwischenkreis (+U , −U Stop! Die Versorgung von Lenze−Geräten der Reihen 82xx und 93xx ist ƒ nicht zulässig. Bei der Verwendung von Synchron−Motoren mit hoher ƒ Schwungmasse kann eine erhebliche Energiemenge in den Zwischenkreis zurückgespeist werden.
  • Seite 39: Anschlussplan Für Die Mindestverdrahtung Mit Internem Bremswiderstand

    Anschlussplan für die Mindestverdrahtung mit internem Bremswiderstand Stop! ECS−Versorgungsmodule immer mit einem Bremswiderstand (intern/extern) betreiben. Die ECS−Versorgungsmodule in den Ausführungen Standard−Einbaugerät und Durchstoß−Technik (ECSEE / ECSDE) verfügen über einen Geräte−internen Bremswiderstand. Zur Nutzung des internen Bremswiderstandes (Rb) nehmen Sie folgende Ver- drahtung vor: Brücke zwischen Klemmen X22/+UG und X22/BR0 (CR)
  • Seite 40 Elektrische Installation Leistungsanschlüsse Anschlussplan für die Mindestverdrahtung mit internem Bremswiderstand F1...F3 " " L3 PE +UG +UG +UG +UG ECSEE... ECSxS/P/M/A... ECSxS/P/M/A... ECSDE... BD1 BD2 BD1 BD2 U V W PE U V W PE " " " " " "...
  • Seite 41: Anschlussplan Für Die Mindestverdrahtung Mit Externem Bremswiderstand

    Elektrische Installation Leistungsanschlüsse Anschlussplan für die Mindestverdrahtung mit externem Bremswiderstand 4.3.4 Anschlussplan für die Mindestverdrahtung mit externem Bremswiderstand Stop! ECS−Versorgungsmodule immer mit einem Bremswiderstand ƒ betreiben. Eine parallele Verdrahtung von internem und externem ƒ Bremswiderstand ist nicht zulässig! Den Thermokontakt des Bremswiderstands so in die ƒ...
  • Seite 42 Elektrische Installation Leistungsanschlüsse Anschlussplan für die Mindestverdrahtung mit externem Bremswiderstand F1...F3 " " L3 PE +UG +UG +UG +UG ECSxE... ECSxS/P/M/A... ECSxS/P/M/A... BD1 BD2 U V W PE BD1 BD2 U V W PE " " " " " " "...
  • Seite 43 Elektrische Installation Leistungsanschlüsse Anschlussplan für die Mindestverdrahtung mit externem Bremswiderstand Verdrahtung externer Bremswiderstand ERBM... ERBM... ERBM... B_ext B_ext < 10 cm " " … … +UG -UG PE T1 T2 +UG -UG PE T1 T2 ECSCE... ECSCE... ECSXE011 Abb. 4−5 Anschluss externe Bremswiderstände, Reihe ERBM...
  • Seite 44: Anschluss Eines Kondensatormoduls Ecsxk

    Elektrische Installation Leistungsanschlüsse Anschluss eines Kondensatormoduls ECSxK... (optional) 4.3.5 Anschluss eines Kondensatormoduls ECSxK... (optional) Die ECS−Kondensatormodule stützen die Zwischenkreisspannung für das An- triebssystem. Diese Kondensatormodul−Typen sind erhältlich: ECSxK001 (705 mF, ±20 %) ƒ ECSxK002 (1410 mF, ±20 %) ƒ Bauform/Montage−Technik: E = Standard−Einbau...
  • Seite 45 Elektrische Installation Leistungsanschlüsse Anschluss eines Kondensatormoduls ECSxK... (optional) F1...F3 " " ECSxE... ECSxK... ECSxS/P/M/A... BD1 BD2 U V W PE " " " " " " 24 V DC ECSXX004 Abb. 4−7 Verdrahtung Kondensatormodul ECSxK... " HF−Schirmabschluss durch großflächige Anbindung an Funktionserde (siehe Montageanleitung Schirmbefestigung ECSZS000X0B) verdrillte Leitungen Netzschütz...
  • Seite 46: Steueranschlüsse

    Elektrische Installation Steueranschlüsse Steueranschlüsse Für die Versorgung der Steuerelektronik ist eine externe ƒ 24 V−Gleichspannung an den Klemmen X6/+24 und X6/GND erforderlich. An die Klemmen X6/T1 und X6/T2 schließen Sie den Temperaturfühler ƒ eines externen Bremswiderstandes an. Wird kein externer Bremswiderstand benötigt, brücken Sie die Klemmen X6/T1 und X6/T2.
  • Seite 47 Elektrische Installation Steueranschlüsse L3 PE +UG +UG ECSxE... ECSxS/P/M/A... " " " " " " " +24 VDC 24 VDC ECSXA013 Abb. 4−8 Verbund: Steuersignale mit internem Bremswiderstand " HF−Schirmabschluss durch großflächige Anbindung an Funktionserde (siehe Montageanleitung Schirmbefestigung ECSZS000X0B) 0 / 1 Hilfsschütz/−relais Spannungsversorgung Motorhaltebremse 23 ...
  • Seite 48 Relais 0 den Digitaleingang X6/DI2 (zentrale Reglerfreigabe) des Versorgungsmoduls. – In den ECS−Achsmodulen ist in der Lenze−Werkseinstellung DO1 auf "Betriebsbereit" eingestellt. "Betriebsbereit" steht erst an, wenn mindestens eine bestimmte DC−Zwischenkreisspannung erreicht ist. 3. Über den Ausgang X6/DO1 des Versorgungsmodules erfolgt die zentrale Reglerfreigabe für die Achsmodule.
  • Seite 49 Elektrische Installation Steueranschlüsse Belegung der Steckerleisten Klemmenleiste X6 Ansicht Klemme Funktion Elektrische Daten X6/+24 Niederspannungsversorgung 20 ... 30 V DC, 0,5 A (max. 1 A) der Steuerelektronik bei 24 V Einschaltstrom: max. 2 A für 50 ms X6/GND Bezugspotenzial Niederspan- nungsversorgung X6/T1 Temperaturschalter−Kontakt 1...
  • Seite 50: Digitale Eingänge Und Ausgänge

    Elektrische Installation Steueranschlüsse Digitale Eingänge und Ausgänge 4.4.1 Digitale Eingänge und Ausgänge Stop! Bei Anschluss induktiver Last an X6/DO1 ein Funkenlöschglied mit einer Begrenzungsfunktion auf max. 50 V ± 0 % vorsehen. X6/DI1 − Netzfreigabe des Versorgungsmodules Über den Eingang X6/DI1 wird das gesteuerte Aufladen des ƒ...
  • Seite 51: Automatisierungs−Interface (Aif)

    Kommunikationsmodul stecken. Das Aufstecken und Abziehen ist auch wäh- rend des Betriebs möglich. Das Keypad XT dient zur Eingabe und Visualisierung von Parametern und ƒ Codestellen. Über Kommunikationsmodule können die Module des Servosystems ECS ƒ mit dem Leitsystem (SPS oder PC) vernetzt werden. Folgende Kombinationen sind möglich: Bedien−/Kommunikati-...
  • Seite 52: Systembus (Can) Verdrahten

    Elektrische Installation Systembus (CAN) verdrahten Systembus (CAN) verdrahten Über die Systembus−Schnittstelle (X4) kommunizieren die Module der Reihe ECS. ƒ kann parametriert oder Codestelleninhalt angezeigt werden. ƒ Verdrahtung des Systembus (CAN) ECSxE092 Abb. 4−9 Beispiel zur Verdrahtung des Systembus (CAN) ECSxE...
  • Seite 53: Belegung Der Steckerleisten

    Elektrische Installation Systembus (CAN) verdrahten Belegung der Steckerleisten X4 (CAN) X14 (CAN−AUX) Beschreibung CAN−HIGH CAN−LOW Bezugspotenzial Spezifikation des Übertragungskabels Wir empfehlen CAN−Kabel nach ISO 11898−2 zu verwenden: CAN−Kabel nach ISO 11898−2 Kabeltyp Paarverseilt mit Abschirmung 120 W (95 ... 140 W) Impedanz Leitungswiderstand/−querschnitt Kabellänge £...
  • Seite 54 Elektrische Installation Systembus (CAN) verdrahten Busleitungslänge Hinweis! Halten Sie die zulässigen Leitungslängen unbedingt ein. 1. Überprüfen Sie die Einhaltung der Gesamt−Leitungslänge in Tab. 4−1. Durch die Übertragungsrate ist die Gesamt−Leitungslänge festgelegt. CAN−Übertragungsrate [kBit/s] Max. Buslänge [m] 1500 1000 Tab. 4−1 Gesamt−Leitungslänge 2.
  • Seite 55: Beispiel: Auswahlhilfe

    Vorgaben Leitungsquerschnitt: 0,5 mm (gemäß Kabel−Spezifikation 53 ) Teilnehmeranzahl: Repeater: Lenze−Repeater, Typ EMF2176IB (Leitungsreduzierung: 30 m) Bei max. Teilnehmeranzahl (63) sind aus den Vorgaben folgende Leitungslän- gen / Anzahl Repeater einzuhalten: Übertragungsrate [kBit/s] 1000 Max. Leitungslänge [m] 1500 Segment−Leitungslänge [m] Anzahl der Repeater −...
  • Seite 56 Elektrische Installation Systembus (CAN) verdrahten Ergebnis Verwendet wird der Lenze−Repeater, Typ EMF2176IB (Leitungsreduzierung: 30 m) Berechnung der max. Leitungslänge: Erste Segment: 360 Zweite Segment: 360 m (entsprechend Tab. 4−1) minus 30 m (Leitungsreduzierung bei Einsatz eines Repeaters) à Max. erreichbare Leitungslänge mit einem Repeater: 690 m.
  • Seite 57: Installation Überprüfen

    Installation überprüfen Installation überprüfen Überprüfen Sie nach Abschluss der Installation ... die Verdrahtung auf Vollständigkeit, Kurzschluss und Erdschluss. ƒ den Leistungsanschluss: ƒ – Netzanschluss über Klemmen L1, L2, L3 (X21) – Anschluss des Funk−Entstörfilters / der Netzdrossel – Anschluss des Bremswiderstandes (intern/extern) über Klemmen BR0, BR1 (X22) –...
  • Seite 58: Scope Of Supply

    Scope of supply Position Description Number Power supply module ECSDExxx Accessory kit with attachment material Mounting instructions Drilling jig Note! The ECSZE000X0B connector set must be ordered separately. 0Fig. 0Tab. 0 Connections and interfaces ECSDE_002A EDKCSDE040 DE/EN/FR 5.0...
  • Seite 59: Status Displays

    Position Description Detailed information Connections External brake resistor DC−bus voltage LEDs: Status and fault display Automation interface (AIF) for Communication module Operating module (XT keypad) PE connection AIF Not assigned CAN connection System bus (CAN) Interface for – master control and other modules –...
  • Seite 60 Technical version B = standard V = coated Variant Hardware version VA or higher Operating software version (B−SW) 1.2 or higher Tip! Information and tools concerning the Lenze products can be found in the download area under www.lenze.com EDKCSDE040 DE/EN/FR 5.0...
  • Seite 61 ..........General safety and application notes for Lenze power supply modules Residual hazards .
  • Seite 62: Safety Instructions

    Safety instructions General safety and application notes for Lenze power supply modules Safety instructions General safety and application notes for Lenze power supply modules (acc. to Low−Voltage Directive 2006/95/EC) For your personal safety Disregarding the following basic safety measures may lead to severe personal injury and damage to material assets! Only use the product as directed.
  • Seite 63 Safety instructions General safety and application notes for Lenze power supply modules High amounts of energy are produced in the power supply module. ƒ Therefore it is required to wear personal protective equipment (body protection, headgear, eye protection, ear protection, hand guard).
  • Seite 64 Safety instructions General safety and application notes for Lenze power supply modules Electrical connection When working on live power supply modules, applicable national regulations (e.g. VBG 4) must be observed. The electrical installation must be carried out according to the appropriate regulations (e.g.
  • Seite 65: Residual Hazards

    Safety instructions Residual hazards Residual hazards Protection of persons Before working on the power supply module, check that no voltage is ƒ applied to the power terminals, because – the power terminals +UG, −UG, BR0 and BR1 remain live for at least 3 minutes after mains disconnection.
  • Seite 66 Safety instructions Residual hazards Device protection The power supply module may only be driven from balanced mains ƒ supplies. Mains supplies with earthed phase are not permitted. The power supply module contains electrostatic sensitive devices. The ƒ personnel must be free of electrostatic charge prior to assembly and service operations.
  • Seite 67: Safety Instructions For The Installation According To Ul

    Safety instructions Safety instructions for the installation according to UL Safety instructions for the installation according to UL Warnings! General markings: Use 60/75 °C or 75 °C copper wire only. ƒ Maximum ambient temperature 55 °C, with reduced output ƒ current.
  • Seite 68: Notes Used

    Safety instructions Notes used Notes used The following pictographs and signal words are used in this documentation to indicate dangers and important information: Safety instructions Structure of safety instructions: Danger! (characterises the type and severity of danger) Note (describes the danger and gives information about how to prevent dangerous situations) Pictograph and signal word Meaning...
  • Seite 69 Safety instructions Notes used Special safety instructions and application notes Pictograph and signal word Meaning Warnings! Safety note or application note for the operation according to UL or CSA requirements. The measures are required to meet the requirements according to UL or CSA. Warnings! EDKCSDE040 DE/EN/FR 5.0...
  • Seite 70: Technical Data

    Technical data General data and operating conditions Technical data General data and operating conditions Standards and operating conditions Conformity Low−Voltage Directive (2006/95/EC) On safety of low voltage equipment TP TC 004/2011 Eurasian Conformity (TR CU 004/2011) TR CU: Technical Regulation of Customs Union Electromagnetic compatibility of technical means TP TC 020/2011 Eurasian Conformity...
  • Seite 71 Technical data General data and operating conditions General electrical data Compliance with the requirements acc. to EN 61800−3 Noise emission Compliance with the limit class C2 according to EN 61800−3(achieved with a collective filter typical for the application) Noise immunity Requirements acc.
  • Seite 72: Rated Data

    Technical data Rated data Rated data Rated data Type ECSxE012 ECSxE020 ECSxE040 Mains voltage 3 x 200 −10 % ... 3 x 480 +10 % mains Rated mains voltage mains rated 3 x 400 V Mains frequency [Hz] 45 ... 66 mains Rated mains current mains rated...
  • Seite 73: External Brake Resistors

    Technical data External brake resistors External brake resistors Assignment of external brake resistors Power supply module (standard variants) Brake resistor ECSEE... ECSDE... ECSCE... [kW] ERBM039R120W 0.12 ERBM020R150W 0.15 ERBD047R01K2 1.20 ERBD022R03K0 3.00 ERBS039R01K6 1.64 ERBS020R03K2 3.20 Continuous power Brake resistors of type ERBM... Brake resistors with specifically adapted pulse capability in IP50 design Rated data Type...
  • Seite 74: Brake Resistors With An Increased Power Loss In Ip20 Design (Protection Against Accidental Contact Acc. To Nema 250 Type 1)

    Technical data External brake resistors Brake resistors of type ERBD... Brake resistors with an increased power loss in IP20 design (protection against accidental contact acc. to NEMA 250 type 1) Rated data Type Brake resistor ERBD047R01K2 ERBD022R03K0 Resistance [] Continuous power 1200 3000 Amount of heat...
  • Seite 75: Mechanical Installation

    – Ensure unimpeded ventilation of cooling air and outlet of exhaust air. – Several modules of the ECS series can be installed in the control cabinet next to each other without any clearance. The mounting plate of the control cabinet ƒ...
  • Seite 76: Mounting With Thermal Separation (Push−Through Technique)

    35 % in the inside of the ECS module Protection class of the separated cooler: IP54 ƒ – The sealing surface at the heatsink of the ECS module must rest completely against the mounting plate. – Use a liquid thread sealant to bond the screws of the clamps.
  • Seite 77: Dimensions

    Mechanical installation Mounting with thermal separation (push−through technique) Dimensions 3.2.1 Dimensions Note! Mounting with ECSZS000X0B shield mounting kit: Mounting clearance below the module > 195 mm ƒ ECSXA007 Fig. 3−1 Dimensions for "push−through design" Z Mounting cutout (a1 x b1), ^ 78 Power supply module Dimensions [mm] Type...
  • Seite 78 Mechanical installation Mounting with thermal separation (push−through technique) Dimensions Dimensions of mounting cutout Note! Installation with shield mounting ECSZS000X0B: Clearance below the mounting cutout > 220 mm ƒ ECSXA063 Fig. 3−2 Dimensions of mounting cutout Mounting surface Mounting cutout for size 0 Mounting cutout for size 1 Power supply module Dimensions [mm]...
  • Seite 79: Mounting Steps

    Mechanical installation Mounting with thermal separation (push−through technique) Mounting steps 3.2.2 Mounting steps Proceed as follows to mount the power supply module: 1. Prepare the fixing holes for the clamps on the mounting surface. – Use the drilling jig for this purpose. 2.
  • Seite 80: Electrical Installation

    EMC Directive and the EMC law is achieved. – If devices which do not comply with the CE requirement concerning noise immunity EN 61000−6−2 are operated close to the ECS modules, these devices may be electromagnetically affected by the ECS modules. EDKCSDE040 DE/EN/FR 5.0...
  • Seite 81 Electrical installation Installation according to EMC (installation of a CE−typical drive system) Assembly Connect the ECS modules, RFI filters, and mains choke to the earthed ƒ mounting plate with a surface as large as possible: – Mounting plates with conductive surfaces (zinc−coated or stainless steel) allow for permanent contact.
  • Seite 82 ³10 dB . This can be achieved by using standard, closed, metallic, and earthed control cabinets or boxes. Earthing Earth all metallically conductive components (e.g. ECS modules, RFI filters, ƒ motor filters, mains chokes) using suitable cables connected to a central earthing point (PE rail).
  • Seite 83: Drive System On The Mains

    Electrical installation Drive system on the mains Electrical isolation Drive system on the mains This information applies to the ECS drive system, consisting of: ECSxE... power supply module ƒ ECSxK series capacitor module (optional) ƒ ECSxS/P/M/A series axis module ƒ...
  • Seite 84: Supply Forms / Electrical Supply Conditions

    Note! Mains voltage dips can be reduced by decreasing the max. ƒ charging current limit (C0022). Deactivate the charging current limitation (charge relay) of the ƒ connected ECS axis modules with C0175 = 3. EDKCSDE040 DE/EN/FR 5.0...
  • Seite 85: Operation On Public Supply Systems (Compliance With En 61000−3−2)

    Electrical installation Drive system on the mains Operation on public supply systems (compliance with EN 61000−3−2) 4.2.3 Operation on public supply systems (compliance with EN 61000−3−2) The European Standard EN 61000−3−2 determines limit values for limiting harmonic currents in the supply system. Non−linear loads (e.g. frequency inverters) produce harmonic currents which may "pollute"...
  • Seite 86: Power Terminals

    Electrical installation Power terminals Power terminals Danger! Hazardous electrical voltage The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC. Possible consequences: Death or severe injuries when touching the device in the event of ƒ...
  • Seite 87: Cable Cross−Sections And Screw−Tightening Torques

    Electrical installation Power terminals Assignment of the plug connectors Terminal Function Electrical data Mains connection Dependent on application and X21/L1 Mains phase L1 type X21/L2 Mains phase L2 0 ... 480 V X21/L3 Mains phase L3 up to 31.3 A ( X21/PE Connection of PE conductor DC−bus voltage connection...
  • Seite 88: Mains Connection

    Electrical installation Power terminals Mains connection 4.3.1 Mains connection Important notes Keep the cables between the RFI filter and the power supply module as ƒ short as possible. – Make sure that no short−circuit can occur! Mains cables and ±U cables must not contact each other.
  • Seite 89 Electrical installation Power terminals Mains connection Wiring variants for the ECSxE power supply module ƒ ƒ  ‚ „ ECSxE040 Fig. 4−2 Wiring variants for the ECSxE power supply module  Simple wiring ‚/„ Wiring with mains chokes ƒ Wiring with RFI filters Power supply module ECSxE Mains choke RFI filter...
  • Seite 90: Protective Measures

    Electrical installation Power terminals Mains connection Fuses Use the following circuit−breakers or UL−approved fuses to protect the mains cable (see Fig. 4−2 (¶ 89)): Power supply Dimensioning according to IEC/EN Dimensioning to UL module Circuit−breaker Cable UL fuse cross−section ECSxE012 C16 A ECSxE020 C16 A...
  • Seite 91: Connection To The Dc Bus (+Ug, −Ug)

    , −U 4.3.2 Connection to the DC bus (+U , −U Stop! The supply of Lenze controllers of the 82xx and 93xx series is not ƒ permitted. If synchronous motors with a high centrifugal mass are used, a ƒ considerable amount of energy can be fed back into the DC bus.
  • Seite 92: Connection Plan For Mimimum Wiring With Internal Brake Resistor

    Always operate the ECS power supply modules with a brake resistor (internal/external). The ECS power supply modules in the standard built−in unit and push−through design (ECSEE / ECSDE) are provided with a device−internal brake resistor. In order to use the internal brake resistor (Rb), carry out the following wiring: Bridge between the terminals X22/+UG and X22/BR0 (CR) ƒ...
  • Seite 93 Electrical installation Power terminals Connection plan for mimimum wiring with internal brake resistor F1...F3 " " L3 PE +UG +UG +UG +UG ECSEE... ECSxS/P/M/A... ECSxS/P/M/A... ECSDE... BD1 BD2 BD1 BD2 U V W PE U V W PE " " "...
  • Seite 94: Connection Plan For Mimimum Wiring With External Brake Resistor

    Connection plan for mimimum wiring with external brake resistor 4.3.4 Connection plan for mimimum wiring with external brake resistor Stop! Always operate the ECS power supply modules with a brake ƒ resistor. A parallel wiring of internal and external brake resistor is not ƒ...
  • Seite 95 Electrical installation Power terminals Connection plan for mimimum wiring with external brake resistor F1...F3 " " L3 PE +UG +UG +UG +UG ECSxE... ECSxS/P/M/A... ECSxS/P/M/A... BD1 BD2 U V W PE BD1 BD2 U V W PE " " " "...
  • Seite 96 Electrical installation Power terminals Connection plan for mimimum wiring with external brake resistor Wiring of external brake resistor ERBM... ERBM... ERBM... B_ext B_ext < 10 cm " " … … +UG -UG PE T1 T2 +UG -UG PE T1 T2 ECSCE...
  • Seite 97: Connection Of An Ecsxk

    Power terminals Connection of an ECSxK... capacitor module (optional) 4.3.5 Connection of an ECSxK... capacitor module (optional) The ECS capacitor modules support the DC−bus voltage for the drive system. These capacitor module types are available: ECSxK001 (705 mF, ±20 %) ƒ...
  • Seite 98 Electrical installation Power terminals Connection of an ECSxK... capacitor module (optional) F1...F3 " " ECSxE... ECSxK... ECSxS/P/M/A... BD1 BD2 U V W PE " " " " " " 24 V DC ECSXX004 Fig. 4−7 Wiring of capacitor module ECSxK... "...
  • Seite 99: Control Terminals

    Electrical installation Control terminals Control terminals The supply of the control electronics requires an external 24 V DC voltage ƒ at terminals X6/+24 and X6/GND. Connect the thermal detector of an external brake resistor to the ƒ terminals X6/T1 and X6/T2. If no external brake resistor is required, jumper terminals X6/T1 and X6/T2.
  • Seite 100 Electrical installation Control terminals L3 PE +UG +UG ECSxE... ECSxS/P/M/A... " " " " " " " +24 VDC 24 VDC ECSXA013 Fig. 4−8 Interconnection: Control signals with internal brake resistor " HF−shield termination by large surface connection to functional earth (see mounting instructions for shield mounting ECSZS000X0B) 0 / 1 Contactor relay...
  • Seite 101 X6/DI2 digital input (central controller enable) of the power supply module via the relay 0. – In the default Lenze setting of the ECS axis modules, DO1 is set to "ready". "Ready" is only present if a specified DC−bus voltage has been reached.
  • Seite 102 Electrical installation Control terminals Assignment of the plug connectors Terminal strip X6 View Terminal Function Electrical data X6/+24 Low−voltage supply of control 20 ... 30 V DC, 0.5 A (max. 1 A) electronics for 24 V starting current: max. 2 A for 50 ms X6/GND Reference potential low−voltage supply...
  • Seite 103: Digital Inputs And Outputs

    Electrical installation Control terminals Digital inputs and outputs 4.4.1 Digital inputs and outputs Stop! If an inductive load is connected to X6/DO1, a spark suppressor with a limiting function to max. 50 V ± 0 % must be provided. Power supply enable of the power supply module The X6/DI1 input serves to start the controlled charge of the DC bus by ƒ...
  • Seite 104: Automation Interface (Aif)

    (X1). This is also possible during operation. The keypad XT serves to enter and visualise parameters and codes. ƒ The communication modules serve to network the modules of the ECS ƒ servo system with the host system (PLC or PC).
  • Seite 105: Wiring Of System Bus (Can)

    Electrical installation Wiring of system bus (CAN) Wiring of system bus (CAN) The modules of the ECS series communicate via the system bus interface (X4). ƒ set parameters and display code contents. ƒ System bus (CAN) wiring ECSxE092 Fig. 4−9...
  • Seite 106 Electrical installation Wiring of system bus (CAN) Assignment of the plug connectors X4 (CAN) X14 (CAN−AUX) Description CAN−HIGH CAN−LOW Reference potential Specification of the transmission cable We recommend the use of CAN cables in accordance with ISO 11898−2: CAN cable in accordance with ISO 11898−2 Cable type Paired with shielding 120 W (95 ...
  • Seite 107 Electrical installation Wiring of system bus (CAN) Bus cable length Note! The permissible cable lengths must be observed. 1. Check the compliance with the total cable length in Tab. 4−1. The baud rate determines the total cable length. CAN baud rate [kbit/s] Max.
  • Seite 108 (according to cable specifications 106) Number of nodes: Repeater: Lenze−repeater, type EMF2176IB (cable reduction: 30 m) For the max. number of nodes (63), the following cable lengths / number of repeaters from the specifications must be observed: Baud rate [kbit/s] 1000 Max.
  • Seite 109: Service Interface

    Electrical installation Wiring of system bus (CAN) Result The Lenze repeater type EMF2176IB is used (cable reduction: 30 m) Calculation of the maximum cable length: First segment: 360 m Second segment: 360 m (according to Tab. 4−1) minus 30 m (cable reduction when a repeater is used) à...
  • Seite 110: Installation Check

    Installation check Installation check After completing the installation, check ... The wiring for completeness, short circuit and earth fault. ƒ The power connection: ƒ – Mains connection via terminals L1, L2, L3 (X21) – Connection of RFI filter / mains choke –...
  • Seite 111 Installation check EDKCSDE040 DE/EN/FR 5.0...
  • Seite 112: Équipement Livré

    Équipement livré Position Description Nombre Module d’alimentation ECSDExxx Matériel de fixation Instructions de montage Gabarit Remarque importante ! Le jeu de connecteurs ECSZE000X0B doit être acheté séparément. 0Fig. 0Tab. 0 Raccordements et interfaces ECSDE_002A EDKCSDE040 DE/EN/FR 5.0...
  • Seite 113 Position Description Informations détaillées Raccordements Résistance de freinage externe Tension du bus CC LEDs : affichages d’état et de défaut Interface d’automatisation (AIF) pour module de communication module de commande (clavier de commande type XT) Raccordement PE de l’interface d’automatisation (AIF) Non affectée Raccordement CAN Bus Système CAN...
  • Seite 114 V = variante "Vernis" Variante Version matérielle VA ou supérieure Version du système d’exploitation (B−SW) 1.2 ou supérieure Conseil ! Toutes les informations relatives aux produits Lenze peuvent être téléchargées sur notre site à l’adresse suivante : www.Lenze.com EDKCSDE040 DE/EN/FR 5.0...
  • Seite 115 Instructions générales de sécurité et d’utilisation relatives aux modules d’alimentation Lenze ....... .
  • Seite 116: Consignes De Sécurité

    Les procédures à suivre et les plans de raccordement fournis constituent des recommandations dont l’adéquation avec l’application concernée doit être vérifiée. La société Lenze Automation GmbH n’assumera aucune responsabilité pour les dommages liés à un problème d’adéquation des procédures et plans de raccordements indiqués.
  • Seite 117 Consignes de sécurité Instructions générales de sécurité et d’utilisation relatives aux modules d’alimentation Lenze Selon leur indice de protection, les modules d’alimentation Lenze et leurs ƒ composants peuvent comporter, pendant leur fonctionnement, des parties accessibles sous tension. Les surfaces peuvent aussi être brûlantes.
  • Seite 118 Consignes de sécurité Instructions générales de sécurité et d’utilisation relatives aux modules d’alimentation Lenze Installation L’installation et le refroidissement des modules d’alimentation doivent répondre aux prescriptions de la documentation fournie avec le produit. L’air ambiant ne doit pas dépasser le degré de pollution 2 selon EN 61800−5−1.
  • Seite 119 Consignes de sécurité Instructions générales de sécurité et d’utilisation relatives aux modules d’alimentation Lenze Fonctionnement Les installations dans lesquelles sont incorporées des modules d’alimentation doivent être équipées de dispositifs de surveillance et de protection supplémentaires prévus par les prescriptions de sécurité en vigueur (loi sur le matériel technique, prescriptions pour la prévention d’accidents, etc.).
  • Seite 120: Dangers Résiduels

    Consignes de sécurité Dangers résiduels Dangers résiduels Sécurité des personnes Avant de procéder aux travaux sur le module d’alimentation, vérifier si ƒ toutes les bornes de puissance sont hors tension. En effet, – les bornes de puissance +UG, −UG, BR0 et BR1 sont encore sous tension pendant 3 min au minimum après coupure réseau.
  • Seite 121 Consignes de sécurité Dangers résiduels Protection des appareils Le fonctionnement du module d’alimentation est uniquement autorisé ƒ sur les réseaux symétriques. Il est interdit sur les réseaux mis à la terre par conducteur extérieur. Le module d’alimentation comprend des pièces sensibles aux contraintes ƒ...
  • Seite 122: Consignes De Sécurité Pour L'installation Selon Ul

    Consignes de sécurité Consignes de sécurité pour l’installation selon U Consignes de sécurité pour l’installation selon U Avertissements ! Marquages d’ordre général : Utiliser exclusivement des conducteurs en cuivre 60/75 °C ou ƒ 75 °C. Température ambiante maximale de 55 °C, avec courant de ƒ...
  • Seite 123 Consignes de sécurité Consignes de sécurité pour l’installation selon U Schéma de câblage AWG Borne X21, X22, X23, X24 12 ... 8 X4, X6, X14 28 ... 16 24 ... 12 EDKCSDE040 DE/EN/FR 5.0...
  • Seite 124: Consignes Utilisées

    Consignes de sécurité Consignes utilisées Consignes utilisées Pour indiquer des risques et des informations importantes, la présente documentation utilise les mots et pictogrammes suivants : Consignes de sécurité Présentation des consignes de sécurité Danger ! (Le pictogramme indique le type de risque.) Explication (L’explication décrit le risque et les moyens de l’éviter.) Pictogramme et mot associé...
  • Seite 125 Consignes de sécurité Consignes utilisées Consignes de sécurité et d’utilisation spéciales Pictogramme et mot associé Description Avertissements ! Consigne de sécurité ou d’utilisation pour le fonctionnement selon les normes UL ou CSA. Les mesures sont requises pour répondre aux exigences des normes UL ou CSA.
  • Seite 126: Spécifications Techniques

    Spécifications techniques Caractéristiques générales et conditions d’utilisation Spécifications techniques Caractéristiques générales et conditions d’utilisation Normes et conditions d’utilisation Norme appliquée Directive Basse Tension (2006/95/CE) Sécurité des équipements à basse tension TP TC 004/2011 Conformité eurasienne (RT UD 004/2011) RT UD : Règlement technique de l’Union Douanière Compatibilité...
  • Seite 127 Spécifications techniques Caractéristiques générales et conditions d’utilisation Conditions ambiantes Conditions climatiques Classe 3k3 selon CEI/EN 60721−3−3 Condensation, vaporisations d’eau et formation de glace non autorisées Stockage CEI/EN 60721−3−1 1K3 (−25 ... + 55 °C) Transport CEI/EN 60721−3−2 Classe 2K3 (−25 ... +70 °C) Fonctionnement CEI/EN 60721−3−3 Classe 3K3 (0 ...
  • Seite 128 Spécifications techniques Caractéristiques générales et conditions d’utilisation Caractéristiques électriques générales Respect des exigences selon EN 61800−3 Perturbations radioélectriques : Respect des valeurs limites classe C2 selon EN 618003 (par la mise en émission place d’un filtre commun adapté) Protection contre les parasites Exigences selon EN 61800−3 Domaine Norme...
  • Seite 129: Caractéristiques Assignées

    Spécifications techniques Caractéristiques assignées Caractéristiques assignées Caractéristiques assignées Type ECSxE012 ECSxE020 ECSxE040 Tension réseau 3 x 200 −10 % ... 3 x 480 +10 % réseau Tension réseau assigné 3 x 400 V réseau N Fréquence réseau [Hz] 45 ... 66 réseau Courant réseau assigné...
  • Seite 130: Résistances De Freinage Externes

    Spécifications techniques Résistances de freinage externes Résistances de freinage externes Affectation des résistances de freinage externes Module d’alimentation (variantes standard) Résistance de ECSEE... ECSDE... ECSCE... freinage [kW] ERBM039R120W 0,12 ERBM020R150W 0,15 ERBD047R01K2 1,20 ERBD022R03K0 3,00 ERBS039R01K6 1,64 ERBS020R03K2 3,20 Puissance permanente Résistances de freinage de type ERBM...
  • Seite 131 Spécifications techniques Résistances de freinage externes Résistances de freinage de type ERBD... Résistances de freinage avec puissance dissipée accrue en version IP20 (protection contre contacts accidentels selon NEMA 250 type 1) Caractéristiques assignées Type Résistance de freinage ERBD047R01K2 ERBD022R03K0 Résistance [] Puissance permanente 1200...
  • Seite 132: Installation Mécanique

    Installation mécanique Remarques importantes Installation mécanique Remarques importantes Conçus avec l’indice de protection IP20, les modules d’alimentation ECS ƒ doivent impérativement être installés dans une armoire électrique. Lorsque l’air de refroidissement contient des impuretés (poussières, ƒ peluches, graisses, gaz agressifs) : –...
  • Seite 133: Montage Avec Séparation Thermique (Montage Traversant)

    épaisseur minimale de 3 mm. Le chanfreinage de l’encoche de montage et des trous de fixation pour les étriers de serrage doit être légèrement courbé vers l’intérieur (vers le module ECS). Refroidissement Le montage séparé du radiateur permet de réduire la dissipation de chaleur dans l’armoire électrique.
  • Seite 134: Cotes

    Installation mécanique Montage avec séparation thermique (montage traversant) Cotes 3.2.1 Cotes Remarque importante ! Montage avec fixation de blindage ECSZS000X0B : espace de montage en dessous du module > 195 mm. ƒ ECSXA007 Fig.3−1 Encombrements pour la variante "montage traversant" Z Encoche de montage (a1 x b1), ^ 135 Module Cotes [mm]...
  • Seite 135 Installation mécanique Montage avec séparation thermique (montage traversant) Cotes Cotes de l’encoche de montage Remarque importante ! Montage avec fixation de blindage ECSZS000X0B : espace de montage en dessous de l’encoche de montage ƒ > 220 mm ECSXA063 Fig.3−2 Cotes de l’encoche de montage Surface de montage Encoche de montage pour taille de construction 0 Encoche de montage pour taille de construction 1...
  • Seite 136: Opérations De Montage

    Installation mécanique Montage avec séparation thermique (montage traversant) Opérations de montage 3.2.2 Opérations de montage Pour le montage du module d’alimentation, procéder comme suit : 1. Préparer les trous de fixation pour les étriers de serrage sur la surface de montage.
  • Seite 137: Installation Électrique

    Lorsque des appareils qui ne répondent pas aux exigences CE au sens de la compatibilité électromagnétique selon la norme EN 61000−6−2 sont utilisés à proximité des modules ECS, ces appareils risquent de subir l’influence électromagnétique des modules ECS. EDKCSDE040 DE/EN/FR 5.0...
  • Seite 138 Installation électrique Câblage conforme CEM (installation d’un système d’entraînement CE) Montage Pour les modules ECS, les filtres antiparasites et les selfs réseau, il est ƒ nécessaire d’appliquer une surface de contact importante sur la plaque de montage reliée à la terre.
  • Seite 139 Mise à la terre Prévoir une mise à la terre de tous les éléments métalliques conducteurs ƒ (exemples : modules ECS, filtre antiparasite, filtre réseau, self réseau) par des câbles adéquats à partir d’un point central de mise à la terre (barre PE).
  • Seite 140: Fonctionnement Du Système D'entraînement Sur Le Réseau

    Installation électrique Fonctionnement du système d’entraînement sur le réseau Séparation du potentiel Fonctionnement du système d’entraînement sur le réseau Ces informations s’appliquent au système d’entraînement ECS comprenant les éléments suivants : Module d’alimentation ECSxE... ƒ Module condensateur ECSxK... (en option) ƒ...
  • Seite 141: Configurations Réseau/Conditions Réseau

    Il est possible de réduire les chutes de tension réseau en ƒ diminuant la limite maximale du courant de charge (C0022). Désactiver le régulateur du courant de charge (relais de charge) ƒ du module d’axe ECS connecté avec C0175 = 3. EDKCSDE040 DE/EN/FR 5.0...
  • Seite 142: Fonctionnement Sur Réseaux Publics (Respect De La Norme En 61000−3−2)

    Installation électrique Fonctionnement du système d’entraînement sur le réseau Fonctionnement sur réseaux publics (respect de la norme EN 61000−3−2) 4.2.3 Fonctionnement sur réseaux publics (respect de la norme EN 61000−3−2) La norme européenne EN 61000−3−2 définit des valeurs limites pour la limitation des courants harmoniques dans le réseau d’alimentation.
  • Seite 143: Partie Puissance

    Installation électrique Partie puissance Partie puissance Danger ! Tension électrique dangereuse Le courant de fuite vers la terre (PE) est > 3.5 mA CA ou > 10 mA CC. Risques encourus : Mort ou blessures graves en cas de contact accidentel avec ƒ...
  • Seite 144: Affectation Des Bornes

    Installation électrique Partie puissance Affectation des bornes Borne Fonction Caractéristiques électriques Raccordement au réseau En fonction de l’application et du X21/L1 Phase réseau L1 type X21/L2 Phase réseau L2 0 ... 480 V X21/L3 Phase réseau L3 jusqu’à 31.3 A ( 129) X21/PE Raccordement pour conducteur PE...
  • Seite 145: Raccordement Au Réseau

    Installation électrique Partie puissance Raccordement au réseau 4.3.1 Raccordement au réseau Remarques importantes Veiller à ce que les câbles entre le filtre antiparasite et le module ƒ d’alimentation soient aussi courts que possible. – Assurer une pose de câble sans risque de court−circuit ! Les câbles réseau et les câbles ±U doivent être posés séparément.
  • Seite 146 Installation électrique Partie puissance Raccordement au réseau Variantes de câblage pour le module d’alimentation ECSxE ƒ ƒ  ‚ „ ECSxE040 Fig.4−2 Variantes de câblage pour le module d’alimentation ECSxE  Câblage simple ‚/„ Câblage avec selfs réseau ƒ Câblage avec filtres antiparasites Module d’alimentation ECSxE Self réseau Filtre antiparasite...
  • Seite 147: Avertissements

    Installation électrique Partie puissance Raccordement au réseau Fusibles Pour protéger le câble réseau, utiliser les disjoncteurs ou fusibles homologués UL suivants (voir Fig.4−2 (¶ 146)): Module Dimensionnement selon CEI/EN Dimensionnement selon UL d’alimentation Disjoncteur Section de câble Fusible UL automatique ECSxE012 C16 A 25 A...
  • Seite 148: Raccordement Du Bus Cc (+Ug, −Ug)

    Documentation relative au module condensateur ECSxK Respecter les consignes figurant dans cette documentation. Fusibles Il n’est pas nécessaire d’utiliser un fusible de bus CC avec les modules d’alimentation de la série ECS équipés d’un fusible côté réseau. Section de câble Longueur Embout Section de câble Couple de serrage...
  • Seite 149: Plan De Raccordement Avec Résistance De Freinage Interne (Câblage Min.)

    (interne ou externe). En version montage sur panneau et montage traversant (ECSEE/ECSDE), les modules d’alimentation ECS disposent d’une résistance de freinage intégrée dans l’appareil. Pour utiliser la résistance de freinage intégrée (Rb), procéder au câblage suivant : Ponter les bornes X22/+UG et X22/BR0 (CR).
  • Seite 150 Installation électrique Partie puissance Plan de raccordement avec résistance de freinage interne (câblage min.) F1...F3 " " L3 PE +UG +UG +UG +UG ECSEE... ECSxS/P/M/A... ECSxS/P/M/A... ECSDE... BD1 BD2 BD1 BD2 U V W PE U V W PE " "...
  • Seite 151: Plan De Raccordement Avec Résistance De Freinage Externe (Câblage Min.)

    Plan de raccordement avec résistance de freinage externe (câblage min.) 4.3.4 Plan de raccordement avec résistance de freinage externe (câblage min.) Stop ! Les modules d’alimentation ECS doivent impérativement ƒ fonctionner avec une résistance de freinage. Le câblage en parallèle des résistances de freinage interne et ƒ...
  • Seite 152 Installation électrique Partie puissance Plan de raccordement avec résistance de freinage externe (câblage min.) F1...F3 " " L3 PE +UG +UG +UG +UG ECSxE... ECSxS/P/M/A... ECSxS/P/M/A... BD1 BD2 U V W PE BD1 BD2 U V W PE " " "...
  • Seite 153 Installation électrique Partie puissance Plan de raccordement avec résistance de freinage externe (câblage min.) Câblage d’une résistance de freinage externe ERBM... ERBM... ERBM... B_ext B_ext < 10 cm " " … … +UG -UG PE T1 T2 +UG -UG PE T1 T2 ECSCE...
  • Seite 154 Installation électrique Partie puissance Plan de raccordement avec résistance de freinage externe (câblage min.) Câblage d’une résistance de freinage externe ERBS.../ERBD... ERBS... / ERBD... ERBS... / ERBD... T1 T2 T1 T2 " " … … +UG -UG T1 T2 +UG -UG T1 T2 ECSxE...
  • Seite 155: Raccordement D'un Module Condensateur Ecsxk

    Raccordement d’un module condensateur ECSxK... (option) 4.3.5 Raccordement d’un module condensateur ECSxK... (option) Les modules condensateurs ECS permettent de maintenir la tension du bus CC du système d’entraînement. Types de modules condensateurs proposés : ECSxK001 (705 mF, ±20 %) ƒ...
  • Seite 156 Installation électrique Partie puissance Raccordement d’un module condensateur ECSxK... (option) F1...F3 " " ECSxE... ECSxK... ECSxS/P/M/A... BD1 BD2 U V W PE " " " " " " 24 V DC ECSXX004 Fig.4−7 Câblage du module condensateur ECSxK... " Raccordement de blindage HF via une connexion par une surface importante à...
  • Seite 157: Partie Commande

    Installation électrique Partie commande Partie commande Pour l’alimentation de la carte de commande, une tension continue ƒ externe de 24 V doit être appliquée aux bornes X6/+24 et X6/GND. Les bornes X6/T1 et X6/T2 servent à raccorder la sonde thermique d’une ƒ...
  • Seite 158 Installation électrique Partie commande L3 PE +UG +UG ECSxE... ECSxS/P/M/A... " " " " " " " +24 VDC 24 VDC ECSXA013 Fig.4−8 Appareils reliés en réseau : signaux de commande avec résistance de freinage interne " Raccordement de blindage HF via une connexion par une surface importante à...
  • Seite 159 X6/DI2 (déblocage variateur centralisé) du module d’alimentation. – Sur les modules d’axe ECS, DO1 est réglé à "Opérationnel" (réglage Lenze). L’état "Opérationnel" est uniquement activé si au moins une tension min. déterminée du bus CC est atteinte. 3. Le déblocage variateur centralisé pour les modules d’axe passe par la sortie X6/DO1 du module d’alimentation.
  • Seite 160: Affectation Des Bornes

    Installation électrique Partie commande Affectation des bornes Bornier X6 Aperçu Borne Fonction Caractéristiques électriques X6/+24 Alimentation basse tension de la 20 ... 30 V CC, 0.5 A (1 A max.) carte de commande Avec courant de démarrage 24 V : X6/GND Potentiel de référence 2 A max.
  • Seite 161: Entrées Et Sorties Numériques

    Installation électrique Partie commande Entrées et sorties numériques 4.4.1 Entrées et sorties numériques Stop ! En cas de raccordement d’une charge inductive à X6/DO1, prévoir l’utilisation d’un souffleur d’étincelles afin d’assurer une limitation à 50 V ± 0 % max. X6/DI1 −...
  • Seite 162: Interface D'automatisation (Aif)

    Le clavier de commande type XT sert à saisir et à visualiser des paramètres ƒ et des codes. Les modules de communication servent à relier les modules du système ƒ servo ECS avec le système maître (API ou PC). Les combinaisons suivantes sont possibles : Module de Type/référence de commande Compatible avec...
  • Seite 163: Remarque Importante

    Installation électrique Câblage du Bus Système (CAN) Câblage du Bus Système (CAN) L’interface Bus Système (X4) permet aux modules de la série ECS de communiquer entre eux. ƒ de paramétrer ou d’afficher le contenu d’un code. ƒ Câblage du Bus Système CAN ECSxE092 Fig.4−9...
  • Seite 164 Installation électrique Câblage du Bus Système (CAN) Affectation des bornes X4 (CAN) X14 (CAN−AUX) Description CAN−HIGH (HAUT) CAN−LOW (BAS) Potentiel de référence Spécifications pour le câble de transmission Il est recommandé d’utiliser des câbles CAN conformes à la norme ISO 11898−2 : Câbles CAN conformes à...
  • Seite 165 Installation électrique Câblage du Bus Système (CAN) Longueur de câble bus Remarque importante ! Respecter impérativement les longueurs de câbles autorisées. 1. Vérifier que la longueur de câble totale indiquée dans le Tab. 4−1 est respectée. La longueur de câble totale est déterminée par la vitesse de transmission. Vitesse de transmission CAN Longueur de bus max.
  • Seite 166 164) Nombre de participants : Répétiteur : Répétiteur Lenze type EMF2176IB (réduction de la longueur de câble : 30 m) Lorsque le nombre max. de participants (63) est atteint, respecter les longueurs de câble et le nombre de répétiteurs indiqués ci−dessous :...
  • Seite 167 Installation électrique Câblage du Bus Système (CAN) Résultat Répétiteur utilisé : Répétiteur Lenze de type EMF2176IB (réduction de la longueur de câble : 30 m) Calcul de la longueur de câble max. : Premier segment : 360 Deuxième segment : 360 m (selon Tab. 4−1) moins 30 m (réduction de la longueur de câble avec répétiteur)
  • Seite 168: Vérification De L'installation

    Vérification de l’installation Vérification de l’installation Une fois l’installation terminée, vérifier ... le câblage dans son intégralité pour éviter un court−circuit ou un défaut de ƒ mise à la terre. la partie puissance : ƒ – raccordement au réseau via les bornes L1, L2, L3 (X21) –...
  • Seite 169 Vérification de l’installation EDKCSDE040 DE/EN/FR 5.0...
  • Seite 170 ã K Q © 07/2015 Lenze Automation GmbH Service Lenze Service GmbH Postfach 10 13 52, 31763 Hameln Breslauer Straße 3, D−32699 Extertal Hans−Lenze−Str. 1, 31855 Aerzen GERMANY Germany HR Hannover B 205381 +49 5154 82−0 008000 2446877 (24 h helpline) Ê...

Inhaltsverzeichnis