Technical Data
RCD– Reacting time
Load time:
Test time:
Limit value for reacting time :
Accuracy of limit value:
Rotary field
Voltage range:
Frequency:
Max. different of
phase voltage:
General
Display:
Battery type:
Current consumption:
Battery life time:
Auto-Power-Off:
Fuse:
Case:
Maximum rating voltage:
Over voltage category:
According to:
Degree of contamination:
Protection class:
Dimensions (LxWxH):
Weight:
Ambient Conditions
Reference temperature range:
Operation temperature range:
Storage temperature range:
Height above MSL:
42
300 ms with 1/3 of selcted nominal fault current
300 ms with nominal fault current
ca. 4 s
300 ms
+0 %, -10 %
175 V ... 415 V (between the phases)
50 ... 60 Hz
± 15 %
LCD with additional red and green LED
6 x 1,5 V, IEC LR6, Mignon, Type AA
ca. 20 mA (standby)
at average use approx. 1year
approx. 5 min
2 pcs F 500 mA / 500 V, 6,3 x 32 mm
Safety class II
500 V AC/DC
CAT III / 440 V against ground
DIN VDE 0413, part 1, 2, 3, 4, 6, 7, 10
EN 61557, part 1, 2, 3, 4, 6, 7, 10
IEC 61557, part 1, 2, 3, 4, 6, 7, 10
DIN VDE 0411, part 1
EN 61010, part 1
IEC 61010, part 1
2
IP50
235 x 105 x 68 mm
ca. 660 g incl. batteries
+17°C...22 ...27°C, max. 70% rel. humidity
0 °C...+40 °C, max. 80% relative humidity without dewfall
-10 °C...+60 °C, max. 80% relative humidity without dewfall
up to 2000 m