Dimplex LA 60TUR+ Montage- Und Gebrauchsanweisung Seite 25

Reversible luft/wasserwärmepumpe für außenaufstellung
Vorschau ausblenden Andere Handbücher für LA 60TUR+:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

8
Additional model features
8.1
Type of defrosting
8.2
Frost protection condensate tray /
water in device protected against freezing
8.3
Max. operating overpressure (heat source/heat sink)
8.4
Hydraulic 4-way reversing valve (external)
9
Heat output / COP
7 9 10 11
9.1
Heat output / COP
Cooling capacity / COP
10 12
9.2
Cooling capacity / COP
1. For air temperatures between -20 °C and 0 °C. flow temperature increasing from 50 °C to 60 °C (see operating limits diagram).
2. 1-compressor operating mode
3. 2-compressor operating mode
4. In 2-compressor operating mode at A35/W18 this results in a cooling water temperature spread of 5 K ± 1 K.
Necessary for ensuring waste heat recovery in cooling operation.
5. The specified sound pressure level corresponds to the operating noise of the heat pump in heating operation with a flow temperature of 35 °C. The specified sound pressure level
represents the free sound area level. The measured value can deviate by up to 16 dB(A), depending on the installation location.
6. Please note that additional space is required for pipe connections, operation and maintenance.
7. These data indicate the size and capacity of the system according to EN 14511. For an analysis of the economic and energy efficiency of the system, the bivalence point and
regulation should be taken into consideration. These specifications can only be achieved with clean heat exchangers. Information on maintenance, commissioning and operation
can be found in the respective sections of the installation and operating instructions. The specified values have the following meaning, e.g. A7 / W35: Heat source temperature
7 °C and heating water flow temperature 35 °C.
8. The heat circulating pump and the heat pump manager must always be ready for operation.
9. In order to obtain the values specified, the optionally available hydraulic 4-way reversing valve (external) must be used.
Without the reversing valve, the heat output is reduced by approximately 10 %, the COPs by approximately 12 %.
10.Domestic hot water preparation via additional heat exchanger operating in parallel. The waste heat output and/or the attainable cylinder temperature is dependent on the present
operating point (temperature level/performance level). The waste heat output falls when the cylinder temperature rises.
11.The specified coefficients of performance are also achieved in parallel hot water preparation via additional heat exchangers.
12.Considerably higher COPs are achieved by means of cooling operation and waste heat recovery using additional heat exchangers
www.dimplex.de
8
9
Performance level
at A-7 / W35
kW / ---
at A2 / W35
kW / ---
at A7 / W35
kW / ---
at A7 / W45
kW / ---
at A10 / W35
kW / ---
Performance level
at A27 / W9
kW / ---
at A27 / W7
kW / ---
at A27 / W18
kW / ---
at A35 / W9
kW / ---
at A35 / W7
kW / ---
at A35 / W18
kW / ---
452163.66.40 · FD 9512
Reverse circulation
bar
Accessories (recommended)
1
20.4 / 2.8
26.4 / 3.5
34.1 / 4.2
31.7 / 3.5
37.0 / 4.5
1
27.1 / 3.0
41.8 / 4.0
24.0 / 2.4
36.0 / 3.2
LA 60TUR+
Yes
3.0
EN 14511
2
39.7 / 3.0
47.6 / 3.4
55.3 / 3.8
54.9 / 3.3
59.6 / 4.0
EN 14511
2
54.5 / 2.8
72.7 / 3.4
49.0 / 2.3
65.8 / 2.8
EN-11