The ground conductor leakage current must not exceed the limit value of 3.5 mA during
this measurement (direct or differential current method**).
**) These requirements comply with DIN VDE 0701-0702 and ÖVE/ÖNORM E8701-1. Also
refer to the applicable requirements and standards in your country.

Contact Current

-
-
The Measurement Is Taken Between A Grounded Point And The Touchable, Conductive
Part That Is Not Connected To The Ground Conductor.
The Contact Current Must Not Exceed 0.5 Ma *).
1 Measuring Device
2 Inverter
6.2 Touchable, Conductive Part Not Connected To
The Ground Conductor
8 Isolated Setup Of Test Piece
9 Measuring Line
Ri 1 - 2 K
*) These Requirements Comply With Din Vde 0701-0702 And Öve/önorm E8701-1. Also
Refer To The Applicable Requirements And Standards In Your Country.
150
Only Perform The Measurement If A Ground Conductor Current Measurement Has
Been Carried Out Successfully
As Before, The Device Must Be Switched On.
PE
L1
R i
mA
1-2kΩ
1
9
9
PE
L1
6.2
N
N
2
8
Touchable, Conductive Parts Not Connected To The
Ground Conductor