5. Commissioning, operation
With capacitive loads, cable lengths greater than 50 m or the
connection to a process control system with capacitive input,
to limit the peak current, a protective resistance of 47 Ω (with
25 VA contacts) should be connected in series.
EN
Current limitation with
capacitive loads, e.g. PLC's,
PCS's and cable lengths
= 47 Ω with contacts up to 25 VA
R
s
C
= internal capacitance
1
The following maximum values for the switching power must
be observed: 50 V AC; 25 VA; 0.5 A, 50 V DC; 25 W; 0.5 A
An overloading of the switch can lead to the destruction of the
integrated reed contact. This can lead to a malfunction in the
downstream control and thus lead to injury to personnel or
damage to equipment.
With the switches, it is possible for the case to become live in
the event of a malfunction. Any contact can result in physical
or even fatal injury. These switch may only be operated on
safety extra-low voltage in accordance with VDE0100 (e.g.
contact protection relay) or must be fitted so that the switch
is electrically connected to the equipotential bonding.
12
S1
C
1
SPS
operating instructions magnetic float switch, model HLS-M
> 50 m