4 OPERATION
ENTER
CURRENT
PULSE
4.3.5 Pulse output
The pulse output is available either on the on open collector transistor or on relay reed. In
this menu, the parameters of the pulse output are defined and the flow rate, that shall
correspond to one pulse is determined. First enter the unit, then the value. Example: 1
pulse corresponds to 5 m
ENTER
PULSE
FILTER
4.3.6 Relay
The parameter definition of the limit contacts is done in this menu. Two limit values are
entered for each relay ; 1- and 1+ or 2- and 2+. The user also has the possibility to invert
the relays. The unit and decimal place, as selected in the sub-menu "UNIT" are activated.
Caution! The following condition must be observed: 1- ≤ 1+, 2- ≤ 2+.
!
Not available on transmitter with relay Reed option.
4 = 0000
Entering the beginning of the
0......9
measuring range
ENTER
4 = 0000
ENTER
3
.
L
M3
USGAL
IMPGAL
E-26-
FLOW TRANSMITTER 8025
20 = 0000
Entering the end
of the measuring
0......9
range
20 = 0180
ENTER
PU = 000.00
0......9
ENTER
PU = 005.00
Input of the quantity
corresponding to one
pulse
8025 - 8025RR