Changing parameters,
Alarm mapping
The last section in the parameters file is covering overall handling of system alarm
events.
19.Alarm Mapping
1.Pwr Save Mode [PSM][0/1]:
2.Room Temp H/L [THL][0/1]:
3.Fan 1
4.Fan 2
5.Fan 3
6.Onbrd. Sens
7.Room Sens
8.Amb.
9.Supp. Sens
10.Cond.
11.Digi.1 I/P
12.Digi.2 I/P
13.Door Xtch I/P [DI][0/1]:
14.Filt Grd I/P
15.Phase I/P
The table below explains each parameter
1.Pwr Save Mode
2.Room Temp H/L
3.Fan 1
7.Room Sens
8.Amb. Sens
11.Digi.1 I/P
14.Filt Grd I/P
Only parameters in this above table are relevant in Flexibox!
continued
RED LED on the PCB´s edge is lit, if any of the alarms states are active on any of
the outputs. This means that if both outputs are disabled on a specific parame-
ter, the LED doesn't switch on, regardless of the alarm state.
Pwr Save Mode
The
alarm will stop Flexibox operation. Any other alarm doesn't
affect the operation, except for heater if connected.
By default operation alarms is active on output 1, and maintenance warnings
(filter change) is active on output 2
If alarm is triggered and parameters
is "1", the specific output is activated
[F1][0/1]:
[F2][0/1]:
[F3][0/1]:
[OS][0/1]:
[RS][0/1]:
Sens
[AS][0/1]:
[SS][0/1]:
Sens
[CS][0/1]:
[FIL][0/1]:
[FI][0/1]:
[FI][0/1]:
[FI][0/1]:
Parameter
Alarm if the voltage is outside
range, and the controller enters
power save mode
Gives alarm if the temperatures is
outside range
Faulty fan
Defective room sensor
Defective outdoor sensor
Input 1 activate alarm
Filter guard is active
1.Alarm1
2.Alarm2
1
:
0
1
:
0
1
:
0
0
:
0
0
:
0
0
:
0
1
:
0
1
:
0
0
:
0
0
:
0
0
:
0
0
:
0
0
:
0
0
:
1
0
:
0
Function
Range is defined in parame-
ter 3 and 4 in section
Control Configurations
External connection to input
1
By default the filter is only
activating output 2 dividing
the 2 alarm outputs in a
"warning" and a "emergency"
outputs.
Dependencies
System
27