Locking/unlocking modes > 4
1
(operating step 0/1)
2
3
(= acknowledgment)
Unlocking: Press both buttons for approx. 5s; as acknowledgment
digit 1 is flashing in the LED display.
Error messages
28
PAGE
Select mode
Mode
Set
Press twice
Mode
Set
Press once
Display of missing/defective slaves
(digit 2 = master; digits 3 and 4 = slave no.);
the slaves are displayed at intervals of seconds.
The list of failed slaves can be stored until the slaves
have been replaced.
- Press the SET button twice (for the list of master 1)
or SET -MODE - SET (for the list of master 2). The
lowest address of the error list is displayed flashing.
- Replace the failed slave by a slave with the same
configuration and with the address 0; it will receive
the indicated address; (the function "automatic
addressing" must be activated). If other addresses
are displayed, proceed in the same way until the list
has been completed.
- The function will be ended when the slaves have
been replaced or the SET button has been pressed.
Display of the selected mode
Display of locking flashing
Display locking active

Werbung

loading

Diese Anleitung auch für:

As interface ac1014As-interface ac1008