5.4.5 The control menu
By pressing
the next control menu tree.
1) Start Battery Test: this is one command that control the UPS to
do the battery test.
2) Clear EPO status: once EPO status is enabled, the UPS output
would be cut off. To recover to normal status, first EPO
connector should be open, and enter this menu to clear EPO
status, then UPS would stop alarm and recover to Bypass
model. And UPS needs be turned on by manual operation.
3) Reset Fault status: when fault occurs, UPS would keep in Fault
mode and alarm. To recover to normal status, enter this menu
42
Figure. 5-16 Measurement menu tree
on the menu of "Control", the display would enter