Herunterladen Inhalt Inhalt Diese Seite drucken

Fresh Air Renewal And Conditioned Air Supply To Adjacent Room - Carrier 40KQM012 Installationsanweisung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 48
40KQM
Fresh air renewal and conditioned air supply to an adjacent room
C
Ø
Air intake grille
• Side knockouts allow connection of fresh air inlet ducts and
ducts to deliver conditioned air to an adjacent room.
• Remove the external prepunched anti-condensate insulation and
take away the knockout panels using a punch.
Air distribution to adjacent room
With a pencil, trace a line on the polystyrene around the inside
edges of the panel that was previously removed.
Cut away the polystyrene with a knife, taking care not to damage
the heat exchange coil.
Fresh air intake
Remove the polystyrene partition.
Introduce baffle supplied after frame has been hooked as per
above figure.
Following that screw the frame/grille assembly using the 4 screws.
GB - 12
All manuals and user guides at all-guides.com
B
Model
Ø A
mm
B
mm
Ø C
mm
Wall
Undercut door
Wall-fitted grille
Door-fitted grille
40KQM012, 015
150
120
70
• Use locally purchased material, suitable for operating
temperatures of 60 °C (continuous).
Conduits can be of flexible polyester (with spiral core) or
corrugated aluminium, externally covered with anti-condensate
material (fibre glass from 12 to 25 mm thickness).
• To complete the installation, all non-insulated ducts must be
covered with anti-condensate insulation (ex. expanded neoprene,
6 mm thickness).
Not observing of these instructions may cause condensate
dripping; the manufacturer will not be held responsible for
any damage caused.
• The two prepunched side knockouts must not be used at the
same time to deliver conditioned air to an adjacent room.
• The return and supply duct lengths can be calculated in
accordance with the "air distribution to an adjacent room" and
"fresh air renewal" diagrams (also taking into account the
pressure drop through air diffusers, grilles and fresh air filters),
as well as the increase in noise caused by these ducts.
Duct connection flange
Clip
6 mm neoprene gasket
Insulated flexible duct
Fresh air intake
Conditioned air supply to an
adjacent room
Polystyrene partition
Baffle
Frame

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

40kqm

Inhaltsverzeichnis