Parameterization
P060 = 3
P071 = ?
P095 = ?
1
2
P096 = ?
P097 = ?
P115 = 1
P130 = ?
P367 = ?
P368 = ?
P368 = 0,1,2,3
4,7 5
P700.01 = ?
P740 = ?
P918.01 = ?
8-12
Select "Quick parameterization" menu
Enter the unit supply voltage in V
(direct voltage for DC supply,
rms value of AC voltage for AC supply)
Select type of motor
0: No motor connected
1: Synchronous servomotor 1FT6/1FK6
2: Induction servomotor 1PH7(=1PA6)/1PL6/1PH4
Enter the code number for the connected
1FK6/1FT6 motor (for list see attachment)
Enter the code number for the connected
1PH7(=1PA6) /1PH4 /1PL6 motor (for list see attachment)
Start calculation of motor model
(no longer necessary from V1.40 onwards)
Select motor encoder
0: Without encoder
1: 2-pole resolver
2: Resolver with pole pair number of motor
3: Encoder 2048/rev.
4: Multiturn encoder 2048/rev.
5: Pulse encoder 1024/rev.
Select type of control for quick parameterization
0: V/f open-loop control
2: Torque closed-loop control
3: Speed closed-loop control
Select setpoint and command source
0: PMU
1: Analog and digital inputs on the terminal strip
6
2: Fixed setpoints and digital inputs on the terminal strip
3: Motorized potentiometer and digital inputs on terminal strip
4: USS1 (e.g. with SIMATIC)
5: SIMOLINK (SLB) (without fig.)
6: PROFIBUS (CBP) (without fig.)
7: OP1S and fixed setpoints via SCom1 (X300: PMU)
Enter the USS bus address
Enter the SIMOLINK module address
Enter the PROFIBUS address
6SE7087-6JD50
Operating Instructions
SIMOVERT MASTERDRIVES
01.2000