BAE PS-XA-1W-24-150-6_ _-I / BAE PS-XA-3Y-24-250-6_ _-I
Power supply units

2.5. Event Data

This set of data is on read only. Event data reports on parameter errors and warns of device failures of the power
supply to the IO-Link master. It is triggered when certain critical conditions or control settings are exceeded. Typical
events are e.g. ambient temperature too hot, high input voltage, etc.
Events
Parameter error – Check data
sheet and values
Device temperature over-run –
Clear source of heat
Events. DC-Warning
Events. Bonus Power
Events. Over Load
Events. High Voltage Input
Events. Low Voltage Input
Events. Power Supply down
Events. Predictive
Maintenance
Power Supply
Events. Two phase AC supply
Events. PSU setting changed
via
HMI
Events. PSU hardware failure
Events. PSU output current
Pre-alarm
Events. E-Fuse channel 1 to
channel 4 Tripped
Events. Output current
Pre-alarm channel 1 to
channel 4

2.6. Process Data

This set of data is on read only. Process data reports on the current state and conditions of the power supply to
the IO-Link master. Typical process data are, e.g. actual output voltage of each output channel, internal
temperatures, tripping status reports, etc.
Process
Actual Output total Current
Actual Output Voltage
E-Fuse Current
channel 1 to channel 4
E-Fuse channel states
E-Fuse overload trip states
E-Fuse short circuit states
10 |
english
Event-type
Error
Warning
Warning
Notification
Warning
Warning
Warning
Warning
Warning
Warning
Warning
Warning
Warning
Warning
Notification
Value range
A
V
A
Description
Output voltage dips more than 10% below
adjusted output voltage
Output current is 5% more than maximum for
more than 3s
Load higher than allowed
Input to high
Input to low
No link from IO-Link Transceiver to Power
Supply
The estimated remaining lifetime has reached
10%. Performance of PSU might be limited due
to aging effects of components.
One leg of the 3-phase system is missing
A PSU setting was changed via man-machine
interface.
Critical PSU hardware failure detected. PSU shut
down.
Total PSU output current exceeds pre-alarm limit
For each E-Fuse channel when is tripped due to
overcurrent
For each E-Fuse channel when Output current
exceeds pre-alarm limit
Description
Actual Output Voltage
Actual Output Current from each E-Fuse
Channel
Actual state of E-Fuse outputs (on/off)
Overload trip state of E-Fuse outputs (ok/tripped)
Short circuit trip state of E-Fuse outputs
(ok/tripped)