Herunterladen Inhalt Inhalt Diese Seite drucken
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 83

5. CONFIGURATION

- Settings may only be changed by a qualified electrical engineer.
- Read the instructions thoroughly before implementing changes.
- During setting of the charger, the DC fuse in the battery connections must be
removed.
5.1 Standard settings: ready for use
On delivery, the Quattro is set to standard factory values. In general, these settings are selected for single-unit operation.
Settings, therefore, do not require changing in the event of stand-alone use.
Warning: Possibly, the standard battery charging voltage is not suitable for your batteries! Refer to the manufacturer's
documentation, or to your battery supplier!
Standard Quattro factory settings
Inverter frequency
Input frequency range
Input voltage range
Inverter voltage
Stand-alone / parallel / 3-phase
AES (Automatic Economy Switch)
Ground relay
Charger on/ off
Charging characteristics
Charging current
Battery type
Discharge)
Automatic equalisation charging
Absorption voltage
Absorption time
Float voltage
Storage voltage
Repeated absorption time
Absorption repeat interval
Bulk protection
Generator (AC-in-1) / shore current (AC-in-2)
UPS feature
Dynamic current limiter
WeakAC
BoostFactor
Programmable relay
PowerAssist
5.2 Explanation of settings
Settings that are not self-explanatory are described briefly below. For further information, please refer to the help files in the
software configuration programs (see Section 5.3).
Inverter frequency
Output frequency if no AC is present at the input.
Adjustability: 50Hz; 60Hz
Input frequency range
Input frequency range accepted by the Quattro. The Quattro synchronises within this range with the voltage present on AC-in-1
(priority input) or AC-in-2. Once synchronised, the output frequency will be equal to the input frequency.
Adjustability: 45 – 65 Hz; 45 – 55 Hz; 55 – 65 Hz
Input voltage range
Voltage range accepted by the Quattro. The Quattro synchronises within this range with the voltage present on AC-in-1 (priority
input) or on AC-in-2. After the back feed relay has closed, output voltage will be equal to input voltage.
Adjustability:
Lower limit: 180 - 230V
Upper limit: 230 - 270V
Note: the standard lower limit setting of 180V is intended for connection to a weak mains supply, or to a generator with
unstable AC output. This setting may result in a system shut down when connected to a 'brushless, self excited, externally
voltage regulated, synchronous AC generator' (synchronous AVR generator). Most generators rated at 10kVA or more are
synchronous AVR generators. The shut down is initiated when the generator is stopped and revs down while the AVR
simultaneously 'tries' to keep the output voltage of the generator at 230V.
The solution is to increase the lower limit setting to 210VAC (the output of AVR generators is generally very stable), or to
disconnect the Multi(s) from the generator when a generator stop signal is given (with help of an AC contacor installed in series
with the generator).
12
50 Hz
45 - 65 Hz
180 - 265 VAC
230 VAC
stand-alone
off
on
on
four-stage adaptive with BatterySafe mode
75% of the maximum charging current
Victron Gel Deep Discharge (also suitable for Victron AGM Deep
off
14.4 / 28.8 / 57.6 V
up to 8 hours (depending on bulk time)
13.8 / 27.6 / 55.2 V
13.2V (not adjustable)
1 hour
7 days
on
50A/30A (= adjustable current limit for PowerControl and
PowerAssist functions)
on
off
off
2
alarm function
on

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Quattro 12/3000/70Quattro 12/3000/35

Inhaltsverzeichnis