Installation Guide
AQUARIUS S / P
1.
General information on the installation guide
This installation guide is intended for trained personne.
For this reason no basic working steps are included.
The seal on the meter must not be damaged!
A damaged seal will result in immediate invalidation of the factory
warranty and verification / conformity.
ƒ
For installation, please observe the requirements in
EO6 / EN 14154.
ƒ
The meter must only be installed in areas free from the risk
of frost.
ƒ
Please also observe any additional regulations for potable
water installations (e.g. DIN 1988).
ƒ
Medium: potable water
2.
Scope of supply
ƒ
Base meter
- prepared for retrofitting with pulse output
ƒ
2 flat gaskets for the screw connection
3.
Installation location
ƒ
Capture all outlets in one system.
ƒ
Do not install meters in circulation conduits.
ƒ
Install meters at easily accessible points (take read-outs or replacement
into consideration).
4.
Assembly
ƒ
Install a closing device to the conduit in front of the meter.
ƒ
Rinse the conduit thoroughly.
ƒ
Shut off the water supply and empty the pipeline.
Take necessary precautions to ensure that any devices connected
to the pipeline are not damaged.
ƒ
Use ½ or ¾ inch screw connections. Use a reducing sleeve if necessary.
ƒ
Protect meters against impacts, shocks or vibrations which could arise
at the installation location.
ƒ
Protect meters against stress or forces which could be caused by pipes
or fittings (e.g. offset, alignment) and use connecting brackets if nec-
essary.
ƒ
Remove old seals and clean sealing surfaces - only use the seals pro-
vided!
ƒ
Install meter- observe the flow direction (arrow indicating the flow on
the meter) and medium temperature range!
ƒ
For meters with plastic housing, do not exceed the maximum torque
of 15 - 25 Nm, as otherwise the meter may be damaged.
ƒ
Open outlet.
ƒ
Open the closing device in front of the meter slowly to prevent any
damage to the measurement insert.
ƒ
Check function.
ƒ
Turn the register to an easy-to-read position.
ƒ
Close the outlet and check the system for leaks.
ƒ
Seal the connection fitting.
ƒ
Reactivate any previously connected devices.
Meters with plastic housing must not be used for tap connections!
Additional installation instructions for tap connections (e.g.
washing machine, garden hose, etc.)
ƒ
Screw the connection fitting with seal to the meter inlet.
ƒ
Screw the hose or washing machine connection and seal to the outlet
of the meter.
Important: observe the flow direction (arrow indicating the flow on the
meter)!
5.
pulse output
Qn 1,5
A/BH
9 0
1
D96
8
2
6.XXX.XX
7
3
6
XX°C
4
5
20XX
The
conformity with the declaration".
6.
Transport and storage
Ensure frost-free storage!
Water measurement devices are precision devices and must be pro-
tected from impact, shock and vibration!
When sending wireless measuring instruments / components by air,
deactivate the wireless before shipping.
7.
Environmental note
The device must not be disposed together with the domestic waste.
Return it to the manufacturer for recycling.
8.
EC Declaration of conformity
The full text of the EU declaration of conformity is available at the following
internet address:
https://www.diehl.com/metering/en/support-center/download-center/
Observe the pulse value of the meter!
There are two versions:
ƒ
Pulse value 10 l/pulse
ƒ
Pulse value 100 l/pulse
Contact load:
max. 24 V ~ 0.2 A
with pulse output is only available „not in