8.2

Mounting / Dismounting, Operating Position

8.2.1 Mounting / Dismounting

Malfunction or device damage caused by improper mounting.
Non-compliance may lead to material damage!
• Only install and operate the device in a vertical or horizontal position!
(Horizontal orientation: Reading direction from below)
Mounting on BusRail
230230 / 947160310010
2019-03-08·BA00·III·en·01
BusRail
BusRail
NOTICE
• Position the module vertically at the
intended slot of the BusRail and press
lightly to snap it into place.
• Press the module down onto the
BusRail to ensure that it is properly
secured! There should not be any gap
between the module and BusRail!
05683E00
The module must not be able to
disconnect without the handle being
actuated.
• Plug the pluggable terminals X1 and
X2 into the module and secure them
against loosening using safety screws
(tightening torque 0.5 to 0.6 Nm).
• To ensure a distance of at least 50 mm
between the intrinsically safe and
non-intrinsically safe electrical circuits,
if necessary, mount a partition
(220101) on the adjacent Ex i module
or leave a space between the Ex i and
non-Ex i modules.
Digital Input Output Module NAMUR
for Ex n Zone 2
Series 9471/35
Mounting and Installation