Herunterladen Inhalt Inhalt Diese Seite drucken

Honeywell 3 Nm Serie Installationsanleitung Seite 2

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

3 NM SERIES SPRING RETURN DIRECT COUPLED ACTUATORS
Humidity Ratings:
 5% to 95% R.H., Non-Condensing
Auxiliary Switches (Two SPST):
 Fixed switches on 10 and 80 degrees
 125 VAC, 1A, res. load
Mounting: Self-centering shaft adapter (shaft cou-
pling):
 Round damper shafts: 3/8 to 5/8 in. (9 to 16 mm)
 Square damper shafts: 1/4 to 1/2 in. (6 to 13 mm)
Nominal tightening torque for self-centering shaft
adapter screw is 106 lb-in (12Nm).
Minimum Damper Shaft Length:
 3.25 in. (83 mm) recommended for self-centering
adapter.
Spring Return Timing (at rated load):
 < 25 seconds @ -22°F to 150°F (-30°C to 65°C)
< 60 seconds @ -40°F to -22°F (-40°C to -30°C)
Cable Specification:
 Power Cable: Plenum Rated, 3 ft (0.914 m) length from
end of access cover, 18 AWG
 Switch Cable: Appliance Rated, 3 ft (0.914 m) length
from end of access cover, 18 AWG
3-1/8 (78)
2-7/8 (72)
B
5-3/8
(137)
3-17/64 (83)
Fig. 1. Dimensional drawing of actuator in in. (mm).
See Table 2 for A and B dimensions.
Table 2. Shaft Adapters.
Type of Shaft Adapter
Self-centering adapter
31-00141M—03
A
6-1/2
(164)
7
(179)
M37461
A
B
3.54 in.
1.54 in.
(90 mm)
(39 mm)
3-1/8 (78)
2-7/8 (72)
1-1/2
(37)
5-3/8
(137)
3-17/64 (83)
Fig. 2. Dimensional drawing of actuator without conduit
Stroke:
 95° ±3°, mechanically limited.
Approvals:
 UL60730
 IEC 60730-1 and Part 2–14
 UL1097 for Double Insulation
 CE Certification Low Voltage Directive 2014/35/EU
 CE EMC 2004/108/EC
 Switch cables are UL certified only
Waste Electrical and Electronic Equipment (WEEE):
Correct disposal of this product (applicable
in the European Union and other European
countries with separate collection systems).
This product should be disposed of, at the
end of its useful life, as per applicable local
laws, regulations, and procedures.
Enclosure Ratings:
 IP54, depends on position according to "Determine
Appropriate Mounting Orientation" on page 3.
 NEMA 2
 Flame Resistance UL94-5VA
 UL2043, switch wiring dependent on conduit
installation
Input Impedance:
 95 kOhm minimum for analog modulating input.
Feedback Signal:
 2-10 VDC, 1 mA source, 0.5 mA sink
2
3-1/2 (90)
6-1/2
(164)
in in. (mm).
M37351

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Ms7103Ms7503Ms3103

Inhaltsverzeichnis