Herunterladen Inhalt Inhalt Diese Seite drucken

Victron energy Phoenix Inverter VE.Direct 24/250 Anleitung Seite 5

Vorschau ausblenden Andere Handbücher für Phoenix Inverter VE.Direct 24/250:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

High start-up power
Needed to start loads such as power converters for LED lamps, filament lamps or electric tools.
ECO mode
When in ECO mode, the inverter will switch to standby when the load decreases below a preset
value. It will switch on and check every few seconds, adjustable, if the load has increased again.
Remote on/off connector
A remote on/off switch can be connected to a two pole connector or between battery plus and the
left hand contact of the two pole connector.
LED diagnosis
A red and a green LED indicate inverter operation and status of the different protections.
To transfer the load to another AC source: the automatic transfer switch
For our low power inverters we recommend our Filax Automatic Transfer Switch. The Filax
features a very short switchover time (less than 20 milliseconds) so that computers and other
electronic equipment will continue to operate without disruption.
Available with different output sockets
Schuko, UK (BS-1363), AU/NZ (3112) or IEC-320 (male plug included)
3. Installation
3.1 Location of the inverter
1
Ceiling mounting (inverted).
2.
Base mounting.
3
Vertical wall mounting, fan at
bottom.
4
Vertical wall mounting, fan on top.
5
Horizontal wall mounting.
For best operating results, the inverter should be placed on a flat surface. To ensure a trouble free
operation of the inverter, it must be used in locations that meet the following requirements:
a) Avoid any contact with water. Do not expose the inverter to rain or moisture.
b) Do not place the unit in direct sunlight. Ambient air temperature should be between
-20°C and 40 °C (humidity < 95% non condensing). Note that in extreme situations the
inverter's case temperature can exceed 70 °C.
c) Do not obstruct the airflow around the inverter. Leave at least 10 centimetres clearance
around the inverter. When the inverter is running too hot, it will shut down. When the
inverter has reached a safe temperature level the unit will automatically restart again.
2
Not recommended
OK
OK (beware of small objects falling through the
ventilation openings on top).
Not recommended
OK

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Phoenix inverter ve.direct 12/250Phoenix inverter ve.direct 48/250Phoenix inverter ve.direct 12/375Phoenix inverter ve.direct 24/375Phoenix inverter ve.direct 48/375Phoenix inverter ve.direct 12/500 ... Alle anzeigen

Inhaltsverzeichnis