Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data - Bosch FMR‑5000‑C Installationsanleitung

Remote keypad
Vorschau ausblenden Andere Handbücher für FMR‑5000‑C:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 20
Remote keypad
Consider the maximum cable length of 2 m when using the USB and RS232 interfaces (see 10,
page 12 ).
Notice!
You will find detailed information about the CAN and Ethernet networking of the fire panels in
the Networking Guide available for download at www.boschsecurity.com.
Caution!
If Ethernet networking is planned, the Remote Keypad must be grounded.
!
Address Setting and Configuration
1.
2.
3.
5

Technical Data

LCD display / touch screen
Operating and display elements
Interfaces
Signal inputs
Permissible length of CAN cable for system
networking
Power supply connection
Input voltage
Maximum line resistance of power supply
Maximum current consumption
Permissible operating temperature
Permissible storage temperature
Housing material and color
Dimensions (H x W x D)
Weight
Bosch Sicherheitssysteme GmbH
2 CAN interfaces (CAN1/CAN2) for networking
2 Ethernet interfaces (ETH1/ETH2) for networking
2 signal inputs (IN1/IN2)
1 USB and 1 RS232 interface
Assign a unique physical address to each Panel Controller and Remote Keypad by setting
the rotary switches and write it down on the label (see 13, page 16 , step 1 and 2).
For configuration, set the 6-pin DIP switch (see 13, page 16 , step 3).
Mark the setting on the provided label (step 4).
LCD display with 320 x 240 pixels, touch screen with
127,5 mm x 170 mm active surface
22 buttons, 1 key switch, 12 LEDs, 1 Reboot button
CAN1, CAN2, ETH1, ETH2, USB, RS232
IN1/IN2
Lmax = 1000 m, depending on configuration, cable type and
topology
DC1 (power supply), DC2 (redundant power supply)
From FPA-5000/FPA-1200 or FPP‑5000
18 Ω
-5 °C to +50 °C
-20 °C to +70 °C
ABS plastic, light gray (similar RAL 7035)
280 mm x 340 mm x 87 mm
Approx. 3 kg
Standby operation: 140 mA at 24 V DC
During an alarm: 230 mA at 24 V DC
Installation Guide
Technical Data | en
27
2020.07 | 5 | F.01U.258.926

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis