Power driver and wiring
• To allow for variance in the installation, it is not recommended to load the power driver beyond 90% of it's rated maximum power
- LED Power Driver 20 W (logistic code 929000654006) max 18 W
- LED Power Driver 80 W (logistic code 929001669406) max 72 W
- LED Power Driver 100 W (logistic code 929001669506) max 90 W
• Use Philips InteGrade LED power cable of 1 m (39 inch) or 2.5 m (98 inch)
• If InteGrade power cables are extended, only use 0.75 mm2 (AWG 18) or
thicker cable uptil a length of max 10 m (32 feet) between driver and Philips LED power cable
• If you wish to make any other configuration, please contact Philips.
Parallel connection
• You can make any combination of engines but:
- do not exceed the maximum total load on one driver and
- stay within the boundaries of the maximum load allowed for series connection, see diagrams below!
Series connection with Xitanium driver*
• You can make any combination of engines but:
• Series connections of InteGrade engines always need to be placed into the InteGrade Profiles
• Do not exceed the maximum total load on one driver/or string
• Stay within the boundaries of the maximum allowed number of engine indicated in the datasheet
11 - 12