Herunterladen Inhalt Inhalt Diese Seite drucken

Bosch FLM-420-NAC-D Installationsanleitung Seite 13

Signaling devices interface module
Vorschau ausblenden Andere Handbücher für FLM-420-NAC-D:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 10
Signaling Devices Interface Module
Max. current consumption from external power
supply
External power supply
Max. output current
EOL resistance
Classes of equipment as per IEC 60950
Protection class as per IEC 60529
Operating temperature / Storage temperature
Relative humidity
Material interface module housing
Material surface-mount housing
Notice!
Electrical data for the built-in short circuit isolator according to EN 54-17:2005, you find in
F.01U.003.287 FLM-I 420-S Installation Guide.
Bosch Sicherheitssysteme GmbH
15 mA (normal operation) + output current
20.4 V DC to 29 V DC
3 A (during an alarm, from ext. power supply)
3.9 kΩ
Class III equipment
FLM-420-NAC-S: IP 54
FLM-420-NAC-D: IP 30
-20°C to 50°C / -25°C to 85°C
< 96%, non-condensing
PPO (Noryl)
ABS + PC-Blend
Installation Guide
Technical specifications | en
2018.02 | 7 | F.01U.003.284
13