2.2

Description of the solar thermal system and the solar functions

Description of the solar thermal system
Additional solar systems can be created by adding functions to
a solar thermal system. You will find examples of possible solar
systems in the connection diagrams.
Solar thermal system (1)
Table 2
Description of the solar functions
Adding functions to the solar thermal system forms the
required solar system. Not all functions can be combined.
Ext heat exchanger cyl 1 (E)
Transfer system (I)
Table 3
MS 100
Solar thermal system for solar DHW heating ( Fig. 17, page 199)
If the collector temperature exceeds the temperature at the bottom of
the cylinder by the set switch-on temperature differential, the solar
pump is switched on.
Control of the flow rate (Match-Flow) in the solar circuit via a solar
pump with PWM or 0-10 V interface (adjustable)
Monitoring of the temperature in the collector array and in the
6 720 647 922-17.1O
cylinder
External heat exchanger for solar system at cylinder 1 ( Fig. 18,
page 200)
If the temperature at the heat exchanger exceeds the temperature at
the bottom of cylinder 1 by the set switch-on temperature
differential, the cylinder primary pump is switched on. The frost
protection function for the heat exchanger is ensured.
6 720 647 922-22.1O
Transfer system with solar-heated pre-heating cylinder for DHW heating
( Fig. 19, page 201)
If the temperature of the pre-heating cylinder (cylinder 1 - left)
exceeds the temperature of the standby cylinder (cylinder 3 - right)
by the set switch-on temperature differential, the transfer pump is
switched on.
6 720 647 922-26.1O