MAIN SAFETY DEVICES

12 MAIN SAFETY DEVICES

Compressor Protection
High pressure switch:
This switch cuts out the operation of the compressor when the discharge pressure exceeds the setting.

Fan Motor Protection
When the fan motor current is reached to the setting, motor output is decreased.
The other way, when the fan motor current becomes lower, limitation is cancelled.
Model
For Compressor
Pressure Switches
High
Low
for control
Fuse
1~ 230V 50Hz
CCP Timer
Setting Time
For Condenser Fan Motor
Internal Thermostat
For Control Circuit
Fuse on PCB
15
PMML0548 rev.0 - 04/2020 - A10648790A
-
Cut-Out
MPa
Cut-In
MPa
Cut-Out
MPa
Cut-In
MPa
-
A
-
min.
-
A
RAS-3HVRC2
Automatic Reset, Non-Adjustable (each one for each compressor)
4.15
3.20
0.20
0.30
40
Non-Adjustable
Automatic Reset, Non-Adjustable (each one for each motor)
3
5