Slow-Scan-Schreiber
4.9 Triggerfunktionen 3-phasig
Adr.
Max-Trigger
_:9601:101
_:9601:105
_:9601:118
_:9601:119
_:9601:120
_:9601:113
Min-Trigger
_:9601:102
_:9601:106
_:9601:121
_:9601:122
_:9601:123
_:9601:114
dM/dt steig. (/Filterzeit)
_:9601:103
_:9601:107
_:9601:124
_:9601:125
_:9601:126
_:9601:115
dM/dt fallend (/Filterzeit)
_:9601:104
_:9601:108
_:9601:127
_:9601:128
_:9601:129
80
Parameter
C
U RMS Trig 1:Max. aktiv
U RMS Trig 1:Max. (Nicht
phasensel.)
U RMS Trig 1:Max.
L1(L12)
U RMS Trig 1:Max.
L2(L23)
U RMS Trig 1:Max.
L3(L31)
U RMS Trig 1:Max. Hyste-
rese
U RMS Trig 1:Min. aktiv
U RMS Trig 1:Min. (Nicht
phasensel.)
U RMS Trig 1:Min.
L1(L12)
U RMS Trig 1:Min.
L2(L23)
U RMS Trig 1:Min.
L3(L31)
U RMS Trig 1:Min. Hyste-
rese
U RMS Trig 1:+dM/dt
aktiv
U RMS Trig 1:+dM/dt
(Nicht phasensel.)
U RMS Trig 1:+dM/dt
L1(L12)
U RMS Trig 1:+dM/dt
L2(L23)
U RMS Trig 1:+dM/dt
L3(L31)
U RMS Trig 1:+dM/dt
Hysterese
U RMS Trig 1:-dM/dt
aktiv
U RMS Trig 1:-dM/dt
(Nicht phasensel.)
U RMS Trig 1:-dM/dt
L1(L12)
U RMS Trig 1:-dM/dt
L2(L23)
U RMS Trig 1:-dM/dt
L3(L31)
Einstellmöglichkeiten
•
nein
•
ja
0,300 V bis 340,000 V
0,300 V bis 340,000 V
0,300 V bis 340,000 V
0,300 V bis 340,000 V
0,900 p.u. bis 0,990 p.u.
•
nein
•
ja
0,300 V bis 340,000 V
0,300 V bis 340,000 V
0,300 V bis 340,000 V
0,300 V bis 340,000 V
1,010 p.u. bis 1,100 p.u.
•
nein
•
ja
0,300 V bis 340,000 V
0,300 V bis 340,000 V
0,300 V bis 340,000 V
0,300 V bis 340,000 V
0,900 p.u. bis 0,990 p.u.
•
nein
•
ja
0,300 V bis 340,000 V
0,300 V bis 340,000 V
0,300 V bis 340,000 V
0,300 V bis 340,000 V
SIPROTEC 5, Aufzeichnung, Gerätehandbuch
C53000-H5000-C089-1, Ausgabe 08.2021
Voreinstellung
ja
120,000 V
120,000 V
120,000 V
120,000 V
0,980 p.u.
ja
80,000 V
80,000 V
80,000 V
80,000 V
1,020 p.u.
nein
20,000 V
20,000 V
20,000 V
20,000 V
0,980 p.u.
nein
20,000 V
20,000 V
20,000 V
20,000 V