Potential levelling

6 Operation

12
Please take note when installing the transmitter remotely in a field
housing: The screen on the 4 to 20 mA signal output must have the same
potential as the screen at the sensor connections!
When using earthed thermocouples screening of the output 4 to 20 mA
cable is recommended. In plants with strong electromagnetic fields
screening of all cables with a low ohm connection to the transmitter
housing is recommended.
PC-Configuration software ReadWin
Presettable parameters
Standard settings
■ Sensor type
■ Connection (2-, 3- or 4-wire connection)
■ Units (°C/°F)
■ Measurement range limits (depends on selected sensor
type)
Expanded settings ■ Cold junction compensation
(internal/external on TC connection)
■ Temperature external
(on TC with cold junction compensation external)
■ Compensation resistance (0 to 20 Ω) on
2-wire connection
■ Fault condition reaction (
configuration
guaranteed
■ Output (4 to 20 mA / 20 to 4 mA)
■ Filter, optional from 0 to 8 s
■ Zero point, offset (-9.9 to +9.9 K / -18 to +18 °F)
■ TAG (Measurement point description)
®
2000 interactive menu operation:
3.6 mA or
21.0 mA), for
21.0 mA, output
21.5 mA is