7-3. Others
(1) Checking After Installation
1) Check that there are no gaps between the unit and the
panel for cassette, or between the panel for cassette
and the ceiling surface.
* Gaps may cause water leakage and condensation.
2) Check that the wiring is securely connected.
* If it is not securely connected, the auto flap will not
operate.
("P09" is displayed on the remote controller.)
In addition, the water leakage and condensation may
occur.
(2) Operating the Wireless Remote Controller
For details of installation, refer to the section "Wireless
Signal Receiver" in the supplied installation instructions.
(3) Selecting DC Fan Motor Tap (4-Way Cassette)
Check the optional parts accordingly in the following
table.
Table for DC Fan Motor Tap Settings
Remote controller
Setting No.
setting data
Item code 5d
(1)
0001
(3)
0003
(6)
0006
*1 When using optional parts in different setting No. in
combination with multiple units, conform it to the larger
setting No.
*2 Ceiling height (m)
Indoor unit type
Standard
(factory setting)
High-ceiling setting 1
High-ceiling setting 2
Air-flow blocking kit
(for 3-way air flow)
Air-flow blocking kit
(for 2-way air flow)
Contents &
optional parts name
Air-flow blocking kit
(for 3-way air flow)*
2
Air-flow blocking kit
(when a duct is
connected.)
High-ceiling setting 1*
2
2
High-ceiling setting 2*
Air-flow blocking kit
2
(for 2-way air flow)*
22,28,36
106,140,
60,73,90
45,56
160
2.7
3.0
3.6
3.2
3.3
4.3
3.5
3.6
5.0
3.8
3.8
4.7
4.2
4.2
5.0
1) When setting on the P.C. Board
<Procedure>
Stop the system before performing these steps.
1 Open the electrical component box cover, then
check the indoor unit control PCB.
2 Change the DIP switch on the indoor unit control
PCB in accordance with the setting number which
was confirmed in Table for DC Fan Motor Tap
Settings.
Setting No.
(1)
(3)
1 2 3
ON
1
2 3
Indoor unit control PCB
<Procedure of CZ-RTC5A>
Stop the system before performing these steps.
1 Keep pressing the
simultaneously for 4 or more seconds.
The "Maintenance func" screen appears on the LCD
display.
2 Press the
If you wish to see the next screen instantly, press the
or
Select "8. Detailed settings" on the LCD display and
press the
The "Detailed settings" screen appears on the LCD display.
22
DIP switch
Setting No.
ON
(6)
1 2 3
1 2 3
ON
1 2 3
Setting example
ON
1: OFF
2: OFF
3: ON
1 2 3
,
and
or
button to see each menu.
button.
button.
DIP switch
ON
1 2 3
1 2 3
buttons